upsRecepAutoOffDelay
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.3.10.2.1.5
Object
column
mandatory
r/w
Integer32
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.3.10.2.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- upsRecepEntry
- Table
- upsRecepTable
- Siblings
- 6
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-32767
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsRecepIndex mandatory The number of the Receptacle. Serves as index for Receptacle table. | column | Integer32 | .1.3.6.1.4.1.232.165.3.10.2.1.1 |
| upsRecepStatus mandatory The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown. | column | Enumeration | .1.3.6.1.4.1.232.165.3.10.2.1.2 |
| upsRecepOffDelaySecs mandatory The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Settin… | column | Integer32 | .1.3.6.1.4.1.232.165.3.10.2.1.3 |
| upsRecepOnDelaySecs mandatory The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting … | column | Integer32 | .1.3.6.1.4.1.232.165.3.10.2.1.4 |
| upsRecepAutoOnDelay mandatory Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, b… | column | Integer32 | .1.3.6.1.4.1.232.165.3.10.2.1.6 |
| upsRecepShedSecsWithRestart mandatory Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Un… | column | Integer32 | .1.3.6.1.4.1.232.165.3.10.2.1.7 |