upsControlToBypassDelay
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.3.8.5
Object
scalar
mandatory
r/w
Integer32
Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.3.8.5- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsControl
- Siblings
- 5
Syntax
Integer32
Values & Constraints
Object Constraints
range: 0-2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsControlOutputOffDelay mandatory Setting this value to other than zero will cause the UPS
output to turn off after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
shutdown. | scalar | Integer32 | .1.3.6.1.4.1.232.165.3.8.1 |
| upsControlOutputOnDelay mandatory Setting this value to other than zero will cause the UPS
output to turn on after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
startup. | scalar | Integer32 | .1.3.6.1.4.1.232.165.3.8.2 |
| upsControlOutputOffTrapDelay mandatory When UpsControlOutputOffDelay reaches this value, a trap will
be sent. | scalar | Integer32 | .1.3.6.1.4.1.232.165.3.8.3 |
| upsControlOutputOnTrapDelay obsolete When UpsControlOutputOnDelay reaches this value, a
UpsOutputOff trap will be sent. | scalar | Integer32 | .1.3.6.1.4.1.232.165.3.8.4 |
| upsLoadShedSecsWithRestart mandatory Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Un… | scalar | Integer32 | .1.3.6.1.4.1.232.165.3.8.6 |