pdu3InputPhaseEntry
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.11.2.2.1
Object
row
mandatory
The input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or 3.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.11.2.2.1- Type
- row
- Status
- mandatory
- Parent
- pdu3InputPhaseTable
- Table
- pdu3InputPhaseTable
- Children
- 24
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu3InputPhaseIndex mandatory Index for the Pdu3InputEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.1 |
| pdu3InputPhaseCurrentRating mandatory Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Return value is divided by 100. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.10 |
| pdu3InputPhaseCurrent mandatory An input current measurement value. Return value is divided by 100. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.11 |
| pdu3InputPhaseCurrentThStatus mandatory Status of the measured input current relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.232.165.11.2.2.1.12 |
| pdu3InputPhaseCurrentThLowerWarning mandatory Lower warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.13 |
| pdu3InputPhaseCurrentThLowerCritical mandatory Lower critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.14 |
| pdu3InputPhaseCurrentThUpperWarning mandatory Upper warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.15 |
| pdu3InputPhaseCurrentThUpperCritical mandatory Upper critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.16 |
| pdu3InputPhaseCurrentPercentLoad mandatory Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative
value indicates that this object is not a… | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.17 |
| pdu3InputPhasePowerMeasType mandatory Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. | column | Enumeration | .1.3.6.1.4.1.232.165.11.2.2.1.18 |
| pdu3InputPhasePowerVA mandatory An input VA value. Units are VA. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.19 |
| pdu3InputPhaseVoltageMeasType mandatory Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phas… | column | Enumeration | .1.3.6.1.4.1.232.165.11.2.2.1.2 |
| pdu3InputPhasePowerWatts mandatory An input Watts value. Units are Watts. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.20 |
| pdu3InputPhasePowerWattHour mandatory A kWatt-Hour value for each Input phase. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3InputPhasePowerWattHourTimer will be reset as well
A ne… | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.21 |
| pdu3InputPhasePowerWattHourTimer mandatory Timestamp of when input phase kWatt-hours (kWh) was last reset. | column | OctetString | .1.3.6.1.4.1.232.165.11.2.2.1.22 |
| pdu3InputPhasePowerFactor mandatory An input PF value. Return value is divided by 100, for example a power factor
of 0.95 would be returned as 95. A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.23 |
| pdu3InputPhasePowerVAR mandatory An input VA Reactive value. Units are in VAR. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.24 |
| pdu3InputPhaseVoltage mandatory An input voltage measurement value. Return value is divided by 10. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.3 |
| pdu3InputPhaseVoltageThStatus mandatory Status of the measured input voltage relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.232.165.11.2.2.1.4 |
| pdu3InputPhaseVoltageThLowerWarning mandatory Lower warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.5 |
| pdu3InputPhaseVoltageThLowerCritical mandatory Lower critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.6 |
| pdu3InputPhaseVoltageThUpperWarning mandatory Upper warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.7 |
| pdu3InputPhaseVoltageThUpperCritical mandatory Upper critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.8 |
| pdu3InputPhaseCurrentMeasType mandatory Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. | column | Enumeration | .1.3.6.1.4.1.232.165.11.2.2.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdu3IdentIndex mandatory Index for the Pdu3IdentEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.11.1.2.1.1 |
| pdu3InputPhaseIndex mandatory Index for the Pdu3InputEntry table. | column | Integer32 | .1.3.6.1.4.1.232.165.11.2.2.1.1 |