pduUnitStatusActivePower
CPDU-MIB ·
.1.3.6.1.4.1.318.1.1.32.2.4.1.4
Object
column
mandatory
Integer32
Returns power consumption, in Watts(W), of the PDU being queried.
Context
- MIB
- CPDU-MIB
- OID
.1.3.6.1.4.1.318.1.1.32.2.4.1.4- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- pduUnitStatusEntry
- Table
- pduUnitStatusTable
- Siblings
- 11
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduUnitStatusIndex mandatory The index of the PDU status table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.2.4.1.1 |
| pduUnitStatusResettableEnergy mandatory A user resettable energy meter measuring PDU energy consumption
in tenths of kilowatt-hours(kWh). | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.2.4.1.10 |
| pduUnitStatusEnergyStartTime mandatory Indicates the date and time of the last device energy meter reset | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.2.4.1.11 |
| pduUnitStatusOutletsEnergyStartTime mandatory Indicates the date and time of the last outlets energy meter reset | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.2.4.1.12 |
| pduUnitStatusName mandatory A user-defined string identifying the PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.2.4.1.2 |
| pduUnitStatusLoadState mandatory Returns the present load status of the PDU based on Active Power. | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.2.4.1.3 |
| pduUnitStatusApparentPower mandatory Returns power consumption, in Volt-Amps(VA)
of the PDU load being queried. | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.2.4.1.5 |
| pduUnitStatusPeakPower mandatory Returns peak power consumption, in Watts(W),
of the PDU being queried. | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.2.4.1.6 |
| pduUnitStatusPeakPowerTimestamp mandatory Indicates the date and time that peak power consumption occurred | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.2.4.1.7 |
| pduUnitStatusPeakPowerStartTime mandatory Indicates the date and time of the last device peak power reset | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.2.4.1.8 |
| pduUnitStatusEnergy mandatory Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime. | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.2.4.1.9 |