pduInputPhaseConfigOverloadRestriction

CPDU-MIB · .1.3.6.1.4.1.318.1.1.32.3.2.1.3

Object

column mandatory r/w Enumeration
This OID controls the behavior of a Switched PDU Input Phase when an 
overload condition is possible and additional outlets are requested 
to be turned on. Setting this OID to alwaysAllowTurnON (1) will always 
allow the outlets on the corresponding Input Phase to turn on. Setting 
this OID to restrictOnUpperWarning (2) will not allow outlets on the 
corresponding Input Phase to turn on if the 
pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting 
this OID to restrictOnUpperCritical (3) will not allow outlets on 
the corresponding Input Phase to turn on if the 
pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models 
that do not support this feature will respond to this OID with a 
value of notSupported (4). Attempts to set this OID in these 
models will fail.

Context

MIB
CPDU-MIB
OID
.1.3.6.1.4.1.318.1.1.32.3.2.1.3
Type
column
Access
readwrite
Status
mandatory
Parent
pduInputPhaseConfigEntry
Table
pduInputPhaseConfigTable
Siblings
16

Syntax

Enumeration

Values & Constraints

Enumerated Values
1alwaysAllowTurnOn
2restrictOnUpperWarning
3restrictOnUpperCritical
4notSupported