pduInputPhaseConfigOverloadRestriction
CPDU-MIB ·
.1.3.6.1.4.1.318.1.1.32.3.2.1.3
Object
column
mandatory
r/w
Enumeration
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Context
- MIB
- CPDU-MIB
- OID
.1.3.6.1.4.1.318.1.1.32.3.2.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- pduInputPhaseConfigEntry
- Table
- pduInputPhaseConfigTable
- Siblings
- 16
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnOn |
2 | restrictOnUpperWarning |
3 | restrictOnUpperCritical |
4 | notSupported |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduInputPhaseConfigIndex mandatory The index of the PDU Input Phase configuration table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.1 |
| pduInputPhaseConfigVoltageUpperCriticalThreshold mandatory User-defined upper critical input phase voltage alarm threshold in Volts(V). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.10 |
| pduInputPhaseConfigVoltageUpperWarningThreshold mandatory User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.11 |
| pduInputPhaseConfigCurrentAlarmResetThreshold mandatory The hysteresis used for current alarm deassertions in hundredths of Amps(A). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.12 |
| pduInputPhaseConfigCurrentAlarmStateChangeDelay mandatory The delay measured in samples before a current state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.13 |
| pduInputPhaseConfigCurrentEnabledThresholds mandatory A bit string indicating which current alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.318.1.1.32.3.2.1.14 |
| pduInputPhaseConfigVoltageAlarmResetThreshold mandatory The hysteresis used for voltage alarm deassertions in Volts(V). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.15 |
| pduInputPhaseConfigVoltageAlarmStateChangeDelay mandatory The delay measured in samples before a voltage state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the … | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.16 |
| pduInputPhaseConfigVoltageEnabledThresholds mandatory A bit string indicating which voltage alarm thresholds are enabled. | column | Bits | .1.3.6.1.4.1.318.1.1.32.3.2.1.17 |
| pduInputPhaseConfigCount mandatory The total number of Input Phases | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.2 |
| pduInputPhaseConfigCurrentLowerCriticalThreshold mandatory User-defined lower critical input phase current alarm threshold in hundredths of Amps(A). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.4 |
| pduInputPhaseConfigCurrentLowerWarningThreshold mandatory User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.5 |
| pduInputPhaseConfigCurrentUpperCriticalThreshold mandatory User-defined upper critical input phase current alarm threshold in hundredths of Amps(A). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.6 |
| pduInputPhaseConfigCurrentUpperWarningThreshold mandatory User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.7 |
| pduInputPhaseConfigVoltageLowerCriticalThreshold mandatory User-defined lower critical input phase voltage alarm threshold in Volts(V). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.8 |
| pduInputPhaseConfigVoltageLowerWarningThreshold mandatory User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V). | column | Unsigned32 | .1.3.6.1.4.1.318.1.1.32.3.2.1.9 |