pduExternalSensorStatusState

CPDU-MIB · .1.3.6.1.4.1.318.1.1.32.6.4.1.4

Object

column mandatory Enumeration
This OID reports the current state of the sensor. 
A notPresent (0) response indicates that no sensor is attached.
An alarmed (1) response indicates that the sensor is present 
and its measured reading indicates alarmed.
A normal (2) response indicates that the sensor is present 
and its measured reading lies within all thresholds.
A belowLowerCritical (3) response indicates that the sensor 
is present and its measured reading lies below the lower critical threshold.
A belowLowerWarning (4) response indicates that the sensor 
is present and its measured reading lies below the lower warning threshold.
An aboveUpperWarning (5) response indicates that the sensor 
is present and its measured reading lies above the upper warning threshold.
An aboveUpperCritical (6) response indicates that the sensor 
is present and its measured reading lies above the upper critical threshold.

Context

MIB
CPDU-MIB
OID
.1.3.6.1.4.1.318.1.1.32.6.4.1.4
Type
column
Access
readonly
Status
mandatory
Parent
pduExternalSensorStatusEntry
Table
pduExternalSensorStatusTable
Siblings
6

Syntax

Enumeration

Values & Constraints

Enumerated Values
0notPresent
1alarmed
2normal
3belowLowerCritical
4belowLowerWarning
5aboveUpperWarning
6aboveUpperCritical

Related Objects