pduEhandleEntry
CPDU-MIB ·
.1.3.6.1.4.1.318.1.1.32.9.1.1
Object
row
mandatory
An entry for a contact sensor
Context
- MIB
- CPDU-MIB
- OID
.1.3.6.1.4.1.318.1.1.32.9.1.1- Type
- row
- Status
- mandatory
- Parent
- pduEhandleTable
- Table
- pduEhandleTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduEhandleIndex mandatory The index of the PDU HID table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.1 |
| pduEhandleMaxDoorOpenTime mandatory HID Max Door Open Time in seconds, Value ranges (0-32400),
critical alarm will be raised if door is left open past this time | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.10 |
| pduEhandleUserPinLength mandatory Rack Access User minimum PIN Length, value ranges(1-15) | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.11 |
| pduEhandleUserPinMode mandatory Rack Access User PIN mode setting | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.9.1.1.12 |
| pduEhandleAisleControl mandatory Rack Access Aisle Control setting,
when set to standalone each aisle will controlled seprately,
when set to combined opposite aisle can be controlled with authenticated control ac… | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.9.1.1.13 |
| pduEhandleAisle mandatory Aisle of HID handle. | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.9.1.1.2 |
| pduEhandleHandleOperation mandatory HID handle control opterations | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.9.1.1.3 |
| pduEhandleFwVer mandatory The firmware revision level of the HID | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.9.1.1.4 |
| pduEhandleMechanicalLock mandatory HID Mechanical opterations | column | Enumeration | .1.3.6.1.4.1.318.1.1.32.9.1.1.5 |
| pduEhandleSerial mandatory The Serial Number of the HID | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.9.1.1.6 |
| pduEhandleHwVer mandatory The hardware revision level of the HID | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.32.9.1.1.7 |
| pduEhandleAutoLockTime mandatory HID Electronic Latch Autolock Time in seconds, Value ranges (0-999) | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.8 |
| pduEhandleDoorOpenTime mandatory HID Door Open Time in seconds, Value ranges (0-999) | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduEhandleIndex mandatory The index of the PDU HID table entry | column | Integer32 | .1.3.6.1.4.1.318.1.1.32.9.1.1.1 |