devControlOperation
ATEN-PE2-CFG ·
.1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1.1
Object
column
r/w
Enumeration
This function is used for outlet control of device. Set off(1) to turn off for outlet control of device. Set on(2) to turn on for all outlet control of device. Set reboot(3) to reboot for outlet control of device. Get this object always return nostatus(3), because there is no device status. If the station is not available, it returns value -3000000.
Context
- MIB
- ATEN-PE2-CFG
- OID
.1.3.6.1.4.1.21317.1.3.2.3.2.1.3.1.1- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- devControlEntry
- Table
- devControlTable
Syntax
Enumeration
Values & Constraints
Enumerated Values
-3000000 | staNotAvailable |
1 | off |
2 | on |
3 | reboot |
4 | nostatus |
5 | not-support |