bankReadingPower
ATEN-PE2-CFG ·
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.3
Object
column
Integer32
Bank power value. This value indicates that 10,000 times. If this measurement value is not available, it returns value -1000000. If the station does not support this OID, it returns value -2000000. If the station is not available, it returns value -3000000.
Context
- MIB
- ATEN-PE2-CFG
- OID
.1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.3- Type
- column
- Access
- readonly
- Status
- current
- Parent
- bankReadingEntry
- Table
- bankReadingTable
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| bankReadingCur Bank electric current value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OI… | column | Integer32 | .1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.1 |
| bankReadingVol Bank voltage value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this OID, it ret… | column | Integer32 | .1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.2 |
| bankReadingPD Bank power dissipation value.
This value indicates that 10,000 times.
If this measurement value is not available, it returns value -1000000.
If the station does not support this O… | column | Integer32 | .1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.4 |
| bankReadingPF Bank power Factor value.
This value indicates that 100 times.
If the station does not support this OID, it returns value -2000000.
If the station is not available, it returns va… | column | Integer32 | .1.3.6.1.4.1.21317.1.3.2.3.2.2.4.1.5 |