pduAcurrentL2
APNL-MODULAR-PDU-MIB ·
.1.3.6.1.4.1.29640.4.3.15
Object
The total measured ac current for phase 2 (in 1/10th Amperes).
Context
- MIB
- APNL-MODULAR-PDU-MIB
- OID
.1.3.6.1.4.1.29640.4.3.15- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- DeciAmpers
- Parent
- pdu
- Siblings
- 33
Syntax
DeciAmpers SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pduType Type of the Pdu.
PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode.
PduGateway1 (1) Gateway to connect OEC1 products with ext… | scalar | Enumeration | .1.3.6.1.4.1.29640.4.3.1 |
| pduKvarL1 The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. | scalar | KiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.10 |
| pduKvarL2 The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. | scalar | KiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.11 |
| pduKvarL3 The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. | scalar | KiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.12 |
| pdulAcurrent The total measured ac current for the pdu (in 1/10th Amperes) . | scalar | DeciAmpers SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.13 |
| pduAcurrentL1 The total measured ac current for phase 1 (in 1/10th Amperes). | scalar | DeciAmpers SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.14 |
| pduAcurrentL3 The total measured ac current for phase 3 (in 1/10th Amperes). | scalar | DeciAmpers SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.16 |
| pduCurIpAddress The current PDU IPv4 Address by which TCP/IP access is available. | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.17 |
| pduCurSubNetMask The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0). | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.18 |
| pduCurDefGwAddress The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1). | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.19 |
| pduProductIdentifier Unique serial number to identify a pdu, the number is between 1 and 65535. | scalar | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.29640.4.3.2 |
| pduNumberOfNodes Number of items in the node table. | scalar | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.29640.4.3.20 |
| pduNumberOfSensors Number of items in the sensor table. | scalar | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.29640.4.3.21 |
| pduSoftwareVersion PDU software version number. | scalar | OctetString | .1.3.6.1.4.1.29640.4.3.22 |
| pduFirmwareVersion PDU firmware version number. | scalar | OctetString | .1.3.6.1.4.1.29640.4.3.23 |
| pduBusProtocol Selected protocol used on the external bus of the pdu.
AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode.
MOD-BUS (1) Protocol used by OEC2 produ… | scalar | Enumeration | .1.3.6.1.4.1.29640.4.3.24 |
| pduAdminCommand PDU admin management Commands:
noOp (0) No operation.
rebootPdu (1) Reboot the PDU (to execute new settings).
redisc… | scalar | Enumeration | .1.3.6.1.4.1.29640.4.3.25 |
| pduStartupIpAddress Not supported. | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.26 |
| pduStartupSubNetMask Not supported. | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.27 |
| pduStartupDefGwAddress Not supported. | scalar | IPv4 Addr SNMPv2-SMIIpAddress | .1.3.6.1.4.1.29640.4.3.28 |
| pduRealTimeClock PDU Real-Time Clock. Maybe set by the manager. | scalar | SNMPv2-TCDateAndTime | .1.3.6.1.4.1.29640.4.3.29 |
| pduSerialNumber PDU onboard Serial Number. | scalar | OctetString | .1.3.6.1.4.1.29640.4.3.3 |
| pduEnableFeatures Array of bits each one an specific feature within the pdu:
globalWebEnabled (0) This bit enables the PDU webpages.
globalUsbEnabled (1) This bit enables the USB menu.… | scalar | Bits | .1.3.6.1.4.1.29640.4.3.30 |
| pduBusAddress Address used to access this PDU via the external bus.
When MOD-BUS protocol is used the address is valid between 1-247.
When AP-BUS protocol is used the address is valid between 1… | scalar | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.29640.4.3.31 |
| pduName Name of the PDU. | scalar | OctetString | .1.3.6.1.4.1.29640.4.3.32 |
| nodeTable A table of the modules on the PDU.
Each entry represents an module unit. | table | - | .1.3.6.1.4.1.29640.4.3.33 |
| sensorTable A table of the Sensors on the PDU.
Each entry represents an an Sensor unit. | table | - | .1.3.6.1.4.1.29640.4.3.34 |
| pduStatus Status of the Pdu.
pduBusy (0) Indicates that an admin command is in progress.
pduReady (1) The execution of an admin command was successfull.
pduAlarm (2) This … | scalar | Enumeration | .1.3.6.1.4.1.29640.4.3.4 |
| pduPower The total measured pdu power in Kilo Watt's*Hour. | scalar | kiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.5 |
| pduPowerL1 The total measured pdu power in Kilo Watt's*Hour for phase 1. | scalar | kiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.6 |
| pduPowerL2 The total measured pdu power in Kilo Watt's*Hour for phase 2. | scalar | kiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.7 |
| pduPowerL3 The total measured pdu power in Kilo Watt's*Hour for phase 3. | scalar | kiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.8 |
| pduKvar The total Reactive Power of the pdu. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. | scalar | KiloWattHours SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.29640.4.3.9 |