acsPowerMgmtPDUTableTemperature2Max
ACS8000-MIB ·
.1.3.6.1.4.1.10418.26.2.5.3.1.20
Object
Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature.
Context
- MIB
- ACS8000-MIB
- OID
.1.3.6.1.4.1.10418.26.2.5.3.1.20- Type
- column
- Access
- readwrite
- Status
- obsolete
- Parent
- acsPowerMgmtPDUTableEntry
- Table
- acsPowerMgmtPDUTable
- Siblings
- 66
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| acsPowerMgmtPDUTablePortNumber Number of serial port when the PDU is connected. | column | IF-MIBInterfaceIndex | .1.3.6.1.4.1.10418.26.2.5.3.1.1 |
| acsPowerMgmtPDUTableCurrent1Value obsolete Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.10 |
| acsPowerMgmtPDUTableCurrent1Max obsolete Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.11 |
| acsPowerMgmtPDUTableCurrent2Value obsolete Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.12 |
| acsPowerMgmtPDUTableCurrent2Max obsolete Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.13 |
| acsPowerMgmtPDUTableCurrent3Value obsolete Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.14 |
| acsPowerMgmtPDUTableCurrent3Max obsolete Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.15 |
| acsPowerMgmtPDUTableTemperatureNOS obsolete Number of temperature sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.16 |
| acsPowerMgmtPDUTableTemperature1Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, t… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.17 |
| acsPowerMgmtPDUTableTemperature1Max obsolete Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actu… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.18 |
| acsPowerMgmtPDUTableTemperature2Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, t… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.19 |
| acsPowerMgmtPDUTablePduIndex A PDU position in the chain. | column | IF-MIBInterfaceIndexOrZero | .1.3.6.1.4.1.10418.26.2.5.3.1.2 |
| acsPowerMgmtPDUTableTemperature3Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, t… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.21 |
| acsPowerMgmtPDUTableTemperature3Max obsolete Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actu… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.22 |
| acsPowerMgmtPDUTableHumidityNOS obsolete Number of humidity sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.23 |
| acsPowerMgmtPDUTableHumidity1Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.24 |
| acsPowerMgmtPDUTableHumidity1Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero va… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.25 |
| acsPowerMgmtPDUTableHumidity2Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.26 |
| acsPowerMgmtPDUTableHumidity2Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero va… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.27 |
| acsPowerMgmtPDUTableHumidity3Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.28 |
| acsPowerMgmtPDUTableHumidity3Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero va… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.29 |
| acsPowerMgmtPDUTablePduId PDU identification. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.3 |
| acsPowerMgmtPDUTableVoltageNOS obsolete Number of voltage sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.30 |
| acsPowerMgmtPDUTableVoltage1Value obsolete Voltage of this sensor in this PDU unit. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.31 |
| acsPowerMgmtPDUTableVoltage1Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.32 |
| acsPowerMgmtPDUTableVoltage2Value obsolete Voltage of this sensor in this PDU unit. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.33 |
| acsPowerMgmtPDUTableVoltage2Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.34 |
| acsPowerMgmtPDUTableVoltage3Value obsolete Voltage of this sensor in this PDU unit. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.35 |
| acsPowerMgmtPDUTableVoltage3Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.36 |
| acsPowerMgmtPDUTableNumberOfPhases Number of phases of this PDU unit. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.37 |
| acsPowerMgmtPDUTableNumberOfBanks Number of banks of this PDU unit. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.38 |
| acsPowerMgmtPDUTableCurrentValue Actual value of current sensor in this PDU.( A x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.39 |
| acsPowerMgmtPDUTablePortName Name of serial port when the PDU is connected. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.4 |
| acsPowerMgmtPDUTableCurrentMax Max detected value of current sensor in this PDU.( A x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.40 |
| acsPowerMgmtPDUTableCurrentMin Min detected value of current sensor in this PDU.( A x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.41 |
| acsPowerMgmtPDUTableCurrentAvg Average value for current sensor in this PDU.( A x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.42 |
| acsPowerMgmtPDUTableCurrentReset Reset max, min and avg values of current. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.43 |
| acsPowerMgmtPDUTableVoltageType Type of voltage values. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.44 |
| acsPowerMgmtPDUTableVoltageValue Actual value of voltage sensor in this PDU unit.( V ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.45 |
| acsPowerMgmtPDUTableVoltageMax Max detected value of voltage sensor in this PDU unit.( V ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.46 |
| acsPowerMgmtPDUTableVoltageMin Min detected value of voltage sensor in this PDU unit.( V ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.47 |
| acsPowerMgmtPDUTableVoltageAvg Average value for voltage sensor in this PDU unit.( V ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.48 |
| acsPowerMgmtPDUTableVoltageReset Reset max, min and avg values of voltage. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.49 |
| acsPowerMgmtPDUTableModel Model of the PDU. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.5 |
| acsPowerMgmtPDUTablePowerType Type of power consumption values.( W x 10 ) | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.50 |
| acsPowerMgmtPDUTablePowerValue Actual value of power consumption in this PDU unit.( W x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.51 |
| acsPowerMgmtPDUTablePowerMax Max detected value of power consumption in this PDU unit.( W x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.52 |
| acsPowerMgmtPDUTablePowerMin Min detected value of power consumption in this PDU unit.( W x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.53 |
| acsPowerMgmtPDUTablePowerAvg Average value for power consumption in this PDU unit.( W x 10 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.54 |
| acsPowerMgmtPDUTablePowerReset Reset max, min and avg values of power consumption. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.55 |
| acsPowerMgmtPDUTablePowerFactorType Type of power factor values. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.56 |
| acsPowerMgmtPDUTablePowerFactorValue Actual value of power factor in this PDU unit.( PF x 100 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.57 |
| acsPowerMgmtPDUTablePowerFactorMax Max detected value of power factor in this PDU unit.( PF x 100 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.58 |
| acsPowerMgmtPDUTablePowerFactorMin Min detected value of power factor in this PDU unit.( PF x 100 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.59 |
| acsPowerMgmtPDUTableVendor Vendor of the PDU. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.6 |
| acsPowerMgmtPDUTablePowerFactorAvg Average value for power factor in this PDU unit.( PF x 100 ) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.60 |
| acsPowerMgmtPDUTablePowerFactorReset Reset max, min and avg values of power factor. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.61 |
| acsPowerMgmtPDUTableAlarm Show the PDU alarm status. | column | Enumeration | .1.3.6.1.4.1.10418.26.2.5.3.1.62 |
| acsPowerMgmtPDUTableEnvSensors Number of environmental sensor in this PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.63 |
| acsPowerMgmtPDUTableAgentSerialNumber Serial number of the agent. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.64 |
| acsPowerMgmtPDUTablePduModelNumber Model number of the PDU. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.65 |
| acsPowerMgmtPDUTablePduSerialNumber Serial number of the PDU. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.66 |
| acsPowerMgmtPDUTablePduPartNumber Part number of the PDU. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.67 |
| acsPowerMgmtPDUTableFirmwareVersion Version of the PDU firmware. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.26.2.5.3.1.7 |
| acsPowerMgmtPDUTableNumberOfOutlets Number of outlets of the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.8 |
| acsPowerMgmtPDUTableCurrentNOS obsolete Number of current sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.26.2.5.3.1.9 |