WebGraph-Thermo-Hygro-Barometer-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
8
Rows
8
Columns
63
.1.3.6.1.4.1.5040.1.2.37.1.2
·
1 row entry
·
1 columns
List of sensors.
List of sensor numbers.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroSensorNo
mandatory
Sensor number.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.37.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.37.1.3
·
1 row entry
·
1 columns
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroTempValue
mandatory
Measurement value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.37.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.37.1.4
·
1 row entry
·
1 columns
List of binary measurement values corresponding to the channel numbers.
Binary measurement values of the sensors.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroBinaryTempValue
mandatory
Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an invalid measured value. |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.37.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.37.1.8
·
1 row entry
·
1 columns
List of measurement values corresponding to the channel numbers.
Measurement values of the sensors.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroTempValuePkt
mandatory
Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.37.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
wtWebGraphThermoBaroAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroAlarmNo
mandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3
·
1 row entry
·
49 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
wtWebGraphThermoBaroAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroAlarmTrigger
mandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.1 |
|
wtWebGraphThermoBaroAlarmMin
mandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.2 |
|
wtWebGraphThermoBaroAlarmMax
mandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.3 |
|
wtWebGraphThermoBaroAlarmHysteresis
mandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.4 |
|
wtWebGraphThermoBaroAlarmDelay
mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.5 |
|
wtWebGraphThermoBaroAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.6 |
|
wtWebGraphThermoBaroAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog enable Bit 4: FTP enable Bit 5: HTTP… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.7 |
|
wtWebGraphThermoBaroAlarmEMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.8 |
|
wtWebGraphThermoBaroAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.9 |
|
wtWebGraphThermoBaroAlarmMailText
mandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.10 |
|
wtWebGraphThermoBaroAlarmManagerIP
mandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.11 |
|
wtWebGraphThermoBaroAlarmTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.12 |
|
wtWebGraphThermoBaroAlarmMailOptions
mandatory
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.13 |
|
wtWebGraphThermoBaroAlarmTcpIpAddr
mandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.14 |
|
wtWebGraphThermoBaroAlarmTcpPort
mandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.15 |
|
wtWebGraphThermoBaroAlarmTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.16 |
|
wtWebGraphThermoBaroAlarmClearMailSubject
mandatory
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.17 |
|
wtWebGraphThermoBaroAlarmClearMailText
mandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.18 |
|
wtWebGraphThermoBaroAlarmClearTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.19 |
|
wtWebGraphThermoBaroAlarmClearTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.20 |
|
wtWebGraphThermoBaroAlarmDeltaTemp
mandatory
Maximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.21 |
|
wtWebGraphThermoBaroAlarmRHMin
mandatory
Minimum rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.22 |
|
wtWebGraphThermoBaroAlarmRHMax
mandatory
Maximum rel.Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.23 |
|
wtWebGraphThermoBaroAlarmRHHysteresis
mandatory
Hysterese rel. Humidity in percent with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.24 |
|
wtWebGraphThermoBaroAlarmAHMin
mandatory
Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.25 |
|
wtWebGraphThermoBaroAlarmAHMax
mandatory
Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.26 |
|
wtWebGraphThermoBaroAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
RFC1155-SMIIpAddressr/w Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.27 |
|
wtWebGraphThermoBaroAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.28 |
|
wtWebGraphThermoBaroAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.29 |
|
wtWebGraphThermoBaroAlarmSyslogClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.30 |
|
wtWebGraphThermoBaroAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.31 |
|
wtWebGraphThermoBaroAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.32 |
|
wtWebGraphThermoBaroAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.33 |
|
wtWebGraphThermoBaroAlarmFtpClearText
mandatory
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.34 |
|
wtWebGraphThermoBaroAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.35 |
|
wtWebGraphThermoBaroAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.36 |
|
wtWebGraphThermoBaroAlarmName
mandatory
Alert name
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.39 |
|
wtWebGraphThermoBaroAlarmActive
mandatory
Alert active
1 = ON 0 = OFF |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.40 |
|
wtWebGraphThermoBaroAlarmHttpReqAuthEnable
mandatory
Binary coded options, select only one option at the same time:
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.61 |
|
wtWebGraphThermoBaroAlarmHttpReqAuthUser
mandatory
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.62 |
|
wtWebGraphThermoBaroAlarmHttpReqAuthPassword
mandatory
HTTP Request: Password
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.63 |
|
wtWebGraphThermoBaroAlarmHttpReqSetUrl
mandatory
HTTP Request: Set URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.64 |
|
wtWebGraphThermoBaroAlarmHttpReqClearUrl
mandatory
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.65 |
|
wtWebGraphThermoBaroAlarmHttpReqServerPort
mandatory
HTTP Request: Server Port
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.66 |
|
wtWebGraphThermoBaroAlarmMqttTopicPath
mandatory
MQTT Publish: Topic path
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.67 |
|
wtWebGraphThermoBaroAlarmMqttTopicSetTopic
mandatory
MQTT Publish: Topic SET message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.68 |
|
wtWebGraphThermoBaroAlarmMqttTopicClear
mandatory
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.69 |
|
wtWebGraphThermoBaroAlarmSensorLostSelection
mandatory
Binary coded options:
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 3-7: unused Bit 2 : Sensor 2 Bit 1 : Sensor 1 Bit 0 : Sensor 0 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.70 |
|
wtWebGraphThermoBaroAlarmLimitWindow
mandatory
If window type is INSIDE the alarm is genereted when the temperature
is greater minumum value and lower than maximum value. If window type is OUTSIDE the alarm is generated when the measured value is lower than the mini… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.71 |
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3
·
1 row entry
·
2 columns
List of sensor colors for the praphical presentation.
Numbers of the sensors.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroGraphicsSensorColor
mandatory
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3.1.1 |
|
wtWebGraphThermoBaroGraphicsSelectScale
mandatory
Assignes one of 4 scales to a sensor:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2 : Use Scale 3 Bit 3-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3.1.2 |
.1.3.6.1.4.1.5040.1.2.37.3.2.1
·
1 row entry
·
7 columns
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
wtWebGraphThermoBaroSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebGraphThermoBaroPortName
mandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.1 |
|
wtWebGraphThermoBaroPortText
mandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.2 |
|
wtWebGraphThermoBaroPortOffset1
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.3 |
|
wtWebGraphThermoBaroPortTemperature1
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.4 |
|
wtWebGraphThermoBaroPortOffset2
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.5 |
|
wtWebGraphThermoBaroPortTemperature2
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.6 |
|
wtWebGraphThermoBaroPortComment
mandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.37.3.2.1.1.7 |