WebGraph-OLD-Thermometer-NTC-US-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
9
Rows
9
Columns
45
.1.3.6.1.4.1.5040.1.2.18.1.2
·
1 row entry
·
1 columns
List of sensors.
Temperature sensor numbers.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcSensorNo
mandatory
Temperature sensor number.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.18.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.18.1.3
·
1 row entry
·
1 columns
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcTempValue
mandatory
Temperature value of the sensor, ASCII, 5 characters in length.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.18.1.3.1.1 |
.1.3.6.1.4.1.5040.1.2.18.1.4
·
1 row entry
·
1 columns
List of binary temperature values corresponding to the channel numbers.
Binary temperature values of the sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcBinaryTempValue
mandatory
Binary temperature value of the sensor in 1/10 degrees Celsius,
signed number, 0x7FFF indicates an invalid measured value. |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.18.1.4.1.1 |
.1.3.6.1.4.1.5040.1.2.18.1.8
·
1 row entry
·
1 columns
List of temperature values corresponding to the channel numbers.
Temperatures of the sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcTempValuePkt
mandatory
Temperature value of the sensor, ASCII, 5 characters in length, decimal point.
|
OctetString Constraints: range: 5-5 |
.1.3.6.1.4.1.5040.1.2.18.1.8.1.1 |
.1.3.6.1.4.1.5040.1.2.18.3.1.4.4
·
1 row entry
·
1 columns
List of sensor colors for the praphical presentation.
Index numbers of the sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcSensorColor
mandatory
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.18.3.1.4.4.1.1 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
wtWebioAn1GraphNtcAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcAlarmNo
mandatory
Alarm number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3
·
1 row entry
·
30 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
wtWebioAn1GraphNtcAlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcAlarmTrigger
mandatory
Binary coded trigger conditions:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3: Sensor 4 B… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.1 |
|
wtWebioAn1GraphNtcAlarmMin
mandatory
Minimum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.2 |
|
wtWebioAn1GraphNtcAlarmMax
mandatory
Maximum temperature in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.3 |
|
wtWebioAn1GraphNtcAlarmHysteresis
mandatory
Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.4 |
|
wtWebioAn1GraphNtcAlarmDelay
mandatory
Alarm will be delayed by setting this time while stable alarm
condition occur (time in minutes). |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.5 |
|
wtWebioAn1GraphNtcAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.6 |
|
wtWebioAn1GraphNtcAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.7 |
|
wtWebioAn1GraphNtcAlarmEMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.8 |
|
wtWebioAn1GraphNtcAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.9 |
|
wtWebioAn1GraphNtcAlarmMailText
mandatory
Alarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.10 |
|
wtWebioAn1GraphNtcAlarmManagerIP
mandatory
Name or IP address of the SNMP Manager which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.11 |
|
wtWebioAn1GraphNtcAlarmTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.12 |
|
wtWebioAn1GraphNtcAlarmMailOptions
mandatory
Binary coded options:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.13 |
|
wtWebioAn1GraphNtcAlarmTcpIpAddr
mandatory
Name or IP address of the TCP server which accepts the trap.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.14 |
|
wtWebioAn1GraphNtcAlarmTcpPort
mandatory
Port number of the TCP server which accepts the trap.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.15 |
|
wtWebioAn1GraphNtcAlarmTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.16 |
|
wtWebioAn1GraphNtcAlarmClearMailSubject
mandatory
Subject line for alarm clear mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.17 |
|
wtWebioAn1GraphNtcAlarmClearMailText
mandatory
Alarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.18 |
|
wtWebioAn1GraphNtcAlarmClearTrapText
mandatory
This text is sent in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.19 |
|
wtWebioAn1GraphNtcAlarmClearTcpText
mandatory
This text is sent in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.20 |
|
wtWebioAn1GraphNtcAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
RFC1155-SMIIpAddressr/w Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.21 |
|
wtWebioAn1GraphNtcAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.22 |
|
wtWebioAn1GraphNtcAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.23 |
|
wtWebioAn1GraphNtcAlarmSyslogClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.24 |
|
wtWebioAn1GraphNtcAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.25 |
|
wtWebioAn1GraphNtcAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.26 |
|
wtWebioAn1GraphNtcAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.27 |
|
wtWebioAn1GraphNtcAlarmFtpClearText
mandatory
Alarm clear message to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.28 |
|
wtWebioAn1GraphNtcAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.29 |
|
wtWebioAn1GraphNtcAlarmTimerCron
mandatory
This entry contains 5 text fields space or tab seperated for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separately. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.5.3.1.30 |
.1.3.6.1.4.1.5040.1.2.18.3.1.6.2.3
·
1 row entry
·
2 columns
List of sensor colors for the praphical presentation.
Numbers of the sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcGraphicsSensorColor
mandatory
Color of the sensors at the praphical presention.
|
OctetStringr/w Constraints: range: 3-3 |
.1.3.6.1.4.1.5040.1.2.18.3.1.6.2.3.1.1 |
|
wtWebioAn1GraphNtcGraphicsSelectScale
mandatory
Assignes one of 4 scales to a sensor:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.1.6.2.3.1.2 |
.1.3.6.1.4.1.5040.1.2.18.3.2.1
·
1 row entry
·
7 columns
List of settings depending on the sensor number.
Sensor parameters for the individual sensors.
Indexes
wtWebioAn1GraphNtcSensorNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioAn1GraphNtcPortName
mandatory
Name of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.1 |
|
wtWebioAn1GraphNtcPortText
mandatory
Description of the sensor.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.2 |
|
wtWebioAn1GraphNtcPortOffset1
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.3 |
|
wtWebioAn1GraphNtcPortTemperature1
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.4 |
|
wtWebioAn1GraphNtcPortOffset2
mandatory
Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.5 |
|
wtWebioAn1GraphNtcPortTemperature2
mandatory
Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.6 |
|
wtWebioAn1GraphNtcPortComment
mandatory
Offset calibration: informations of date, name of operator, reference devices.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.18.3.2.1.1.7 |