VERTIV-BB-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
9
Rows
9
Columns
88
.1.3.6.1.4.1.21239.5.1.2 · 1 row entry · 12 columns
Internal sensors for units
internalEntry entry .1.3.6.1.4.1.21239.5.1.2.1
Entry in the internalTable table: each entry contains an index and other sensor details
Indexes
internalIndex
Column Syntax OID
internalIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.2.1.1
internalSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.2.1.2
internalLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.2.1.3
internalAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.2.1.4
internalTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.2.1.5
internalHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.6
internalDewPoint
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
0.1 DegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.2.1.7
internalIO1
Current reading for Analog Input 1
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.8
internalIO2
Current reading for Analog Input 2
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.9
internalIO3
Current reading for Analog Input 3
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.10
internalIO4
Current reading for Analog Input 4
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.2.1.11
internalRelayState
Is the relay on?
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.2.1.12
.1.3.6.1.4.1.21239.5.1.4 · 1 row entry · 5 columns
Remote Temperature (RT) sensor
tempSensorEntry entry .1.3.6.1.4.1.21239.5.1.4.1
Entry in the tempSensorTable table: each entry contains an index and other sensor details
Indexes
tempSensorIndex
Column Syntax OID
tempSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.4.1.1
tempSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.4.1.2
tempSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.4.1.3
tempSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.4.1.4
tempSensorTemp
Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.4.1.5
.1.3.6.1.4.1.21239.5.1.5 · 1 row entry · 8 columns
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
airFlowSensorEntry entry .1.3.6.1.4.1.21239.5.1.5.1
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
Indexes
airFlowSensorIndex
Column Syntax OID
airFlowSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.5.1.1
airFlowSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.5.1.2
airFlowSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.5.1.3
airFlowSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.5.1.4
airFlowSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.5.1.5
airFlowSensorFlow
Airflow reading. Still air will be less than 20, while rushing air will be around 100.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.5.1.6
airFlowSensorHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.5.1.7
airFlowSensorDewPoint
Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.5.1.8
.1.3.6.1.4.1.21239.5.1.6 · 1 row entry · 7 columns
Remote Dew Point sensor
dewPointSensorEntry entry .1.3.6.1.4.1.21239.5.1.6.1
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
Indexes
dewPointSensorIndex
Column Syntax OID
dewPointSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.6.1.1
dewPointSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.6.1.2
dewPointSensorName
User-defined label
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.6.1.3
dewPointSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.6.1.4
dewPointSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.6.1.5
dewPointSensorHumidity
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.6.1.6
dewPointSensorDewPoint
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.1.6.1.7
.1.3.6.1.4.1.21239.5.1.7 · 1 row entry · 7 columns
Remote CCAT sensor
ccatSensorEntry entry .1.3.6.1.4.1.21239.5.1.7.1
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
Indexes
ccatSensorIndex
Column Syntax OID
ccatSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.7.1.1
ccatSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.2
ccatSensorName
User-defined label
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.3
ccatSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.7.1.4
ccatSensorValue
CCAT sensor reading
Integer32
Constraints:
range: -100-5000
.1.3.6.1.4.1.21239.5.1.7.1.5
ccatSensorType
CCAT sensor type
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.6
ccatSensorDescription
CCAT sensor value description
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.7.1.7
.1.3.6.1.4.1.21239.5.1.8 · 1 row entry · 14 columns
Remote Temperature x 3, Humidity and Dewpoint Sensor
t3hdSensorEntry entry .1.3.6.1.4.1.21239.5.1.8.1
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
Indexes
t3hdSensorIndex
Column Syntax OID
t3hdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.8.1.1
t3hdSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.8.1.2
t3hdSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.8.1.3
t3hdSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.4
t3hdSensorIntLabel
Internal label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.8.1.5
t3hdSensorIntTemp
Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.8.1.6
t3hdSensorIntHumidity
Internal Humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.8.1.7
t3hdSensorIntDewPoint
Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.8.1.8
t3hdSensorExtAAvail
External A status:
0 =Unavailable
1 =Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.9
t3hdSensorExtALabel
External A label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.8.1.10
t3hdSensorExtATemp
External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.8.1.11
t3hdSensorExtBAvail
External B status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.8.1.12
t3hdSensorExtBLabel
External B label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.8.1.13
t3hdSensorExtBTemp
External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.8.1.14
.1.3.6.1.4.1.21239.5.1.9 · 1 row entry · 7 columns
Remote Temperature, Humidity and Dewpoint (THD) Sensor
thdSensorEntry entry .1.3.6.1.4.1.21239.5.1.9.1
Entry in the thdSensorTable table: each entry contains an index and other sensor details
Indexes
thdSensorIndex
Column Syntax OID
thdSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.9.1.1
thdSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.9.1.2
thdSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.9.1.3
thdSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.9.1.4
thdSensorTemp
Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.9.1.5
thdSensorHumidity
Humidity value
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.1.9.1.6
thdSensorDewPoint
Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.1.9.1.7
.1.3.6.1.4.1.21239.5.1.10 · 1 row entry · 15 columns
Remote Power Manager Sensor
rpmSensorEntry entry .1.3.6.1.4.1.21239.5.1.10.1
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
Indexes
rpmSensorIndex
Column Syntax OID
rpmSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.10.1.1
rpmSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.10.1.2
rpmSensorName
Friendly Name
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.10.1.3
rpmSensorAvail
Device availability
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.4
rpmSensorEnergy
RPM Sensor Accumulated Energy
kWhSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.5
rpmSensorVoltage
RPM Sensor Voltage
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.6
rpmSensorVoltageMax
RPM Sensor Voltage (Max)
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.7
rpmSensorVoltageMin
RPM Sensor Voltage (Min)
Volts (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.8
rpmSensorVoltagePeak
RPM Sensor Voltage (Peak)
VoltsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.9
rpmSensorCurrent
RPM Sensor Current reading in deciAmps
0.1 Amps (rms)SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.10
rpmSensorRealPower
RPM Sensor Real Power
WattsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.11
rpmSensorApparentPower
RPM Sensor Apparent Power
Volt-AmpsSNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.12
rpmSensorPowerFactor
RPM Sensor Power Factor
%SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.13
rpmSensorOutlet1
RPM Sensor Outlet 1 State: 0 = off, 1 = on
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.14
rpmSensorOutlet2
RPM Sensor Outlet 2 State:
0 = off
1 = on
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.10.1.15
.1.3.6.1.4.1.21239.5.1.11 · 1 row entry · 13 columns
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
a2dSensorEntry entry .1.3.6.1.4.1.21239.5.1.11.1
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Indexes
a2dSensorIndex
Column Syntax OID
a2dSensorIndex
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.1.11.1.1
a2dSensorSerial
Serial Number
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.21239.5.1.11.1.2
a2dSensorLabel
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.11.1.3
a2dSensorAvail
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.1.11.1.4
a2dSensorValue
Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.
Integer32
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.1.11.1.5
a2dSensorDisplayValue
For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.11.1.6
a2dSensorMode
Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMa…
Enumerationr/w
Enumerated Values:
1door
2powerFailure
3flood
4wscLeak
5wscFault
6smoke
7ivsNegGnd
8ivsPosGnd
9customVoltage
10customBinary
11customCurrent
.1.3.6.1.4.1.21239.5.1.11.1.7
a2dSensorUnits
The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.
OctetStringr/w
Constraints:
range: 0-7
.1.3.6.1.4.1.21239.5.1.11.1.8
a2dSensorMin
Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.1.11.1.9
a2dSensorMax
Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.1.11.1.10
a2dSensorLowLabel
Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.11.1.11
a2dSensorHighLabel
Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.11.1.12
a2dSensorAnalogLabel
Label for the analog measurement
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.1.11.1.13