UEC-STARLINE-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
10
Rows
10
Columns
102
cpmAcDigitalIo
table.1.3.6.1.4.1.35774.2.1.2.4
·
1 row entry
·
6 columns
Table of Digital I/O line data.
Variables pertaining to Digital I/Os.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcDigitalIoIndex
The index to the Digital I/O entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.2.4.1.1 |
|
cpmAcDigitalIoName
The Digital I/O name.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.2.4.1.2 |
|
cpmAcDigitalIoValue
The current value of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.2.4.1.3 |
|
cpmAcDigitalIoDirection
The direction of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.2.4.1.4 |
|
cpmAcDigitalIoLevel
The active level of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.2.4.1.5 |
|
cpmAcDigitalIoAlarm
Set to generate an alarm on input.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.2.4.1.6 |
cpmAcInfeedLine
table.1.3.6.1.4.1.35774.2.1.5
·
1 row entry
·
9 columns
Table of infeed line data.
Variables pertaining to infeed line.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcInfeedLineIndex
The index to the infeed line entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.5.1.1 |
|
cpmAcInfLineCurrent
The current measurement of infeed.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.3 |
|
cpmAcInfLineCurrentMin
The minimum current measured on infeed.
|
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.4 |
|
cpmAcInfLineCurrentMax
The maximum current measured on infeed.
|
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.5 |
|
cpmAcInfLineCurrRatPctOf
Infeed line current rating percent of
= (current / rated current * 100). |
% of ratedDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.6 |
|
cpmAcInfLineCurrMinAlarm
The minimum current threshold for alarm activiation.
|
amps (RMS)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.7 |
|
cpmAcInfLineCurrMaxAlarm
The maximum current threshold for alarm activiation.
|
amps (RMS)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.8 |
|
cpmAcInfLineCurrDemand
The current demand of this line.
|
amps per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.9 |
|
cpmAcInfLineCurrPeakDmd
The highest cpmAcInfLineCurrDemand measured
since the last operator reset of this value. |
amps per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.5.1.10 |
cpmAcInfeedPhase
table.1.3.6.1.4.1.35774.2.1.6
·
1 row entry
·
17 columns
Table of infeed phase data.
Variables pertaining to infeed phase.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcInfeedPhaseIndex
The index to the infeed phase entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.6.1.1 |
|
cpmAcLineToNeutVoltage
The current measurement of infeed.
|
volts (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.2 |
|
cpmAcLineToLineVoltage
Phase A,B,C voltage.
|
volts (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.3 |
|
cpmAcLineToLineVoltMin
Phase A,B,C voltage minimum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.4 |
|
cpmAcLineToLineVoltMax
Phase A,B,C voltage maximum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.5 |
|
cpmAcLinToLinVoltMinAlm
Phase A,B,C voltage minimum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.6 |
|
cpmAcLinToLinVoltMaxAlm
Phase A,B,C voltage maximum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.7 |
|
cpmAcInfPhasePowerFactor
Phase A,B,C power factor.
|
DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.8 |
|
cpmAcInfPhaseApparentPwr
Phase A,B,C apparent power.
|
VADisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.9 |
|
cpmAcInfPhaseActivePower
Phase A,B,C active power
|
WDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.10 |
|
cpmAcInfPhasePeakActPwr
Phase A,B,C peak active power.
|
WDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.11 |
|
cpmAcInfPhaseReactivePwr
Phase A,B,C reactive power.
|
varDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.12 |
|
cpmAcInfPhaseEnergy
Phase A,B,C metered energy.
|
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.13 |
|
cpmAcLineToNeutVoltMin
Line-to-neutral voltage minimum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.14 |
|
cpmAcLineToNeutVoltMax
Line-to-neutral voltage maximum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.15 |
|
cpmAcLinToNeutVoltMinAlm
Line-to-neutral voltage minimum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.16 |
|
cpmAcLinToNeutVoltMaxAlm
Line-to-neutral voltage maximum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.6.1.17 |
cpmAcOutlet
table.1.3.6.1.4.1.35774.2.1.7
·
1 row entry
·
12 columns
Table of outlet data.
Variables pertaining to the outlet table.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcOutletIndex
The index to the outlet entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.7.1.1 |
|
cpmAcOutletId
The name assigned to this outlet.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.2 |
|
cpmAcOtlLineCurrRating
The rated current of this outlet.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.3 |
|
cpmAcOtlDemandTime
The interval of time over which the demand
is calculated for the outlet parameters. |
minutesDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.4 |
|
cpmAcOtlTotalActivePower
The total active power being supplied by this outlet.
|
WDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.5 |
|
cpmAcOtlPeakTotActivePwr
The peak total active power being supplied by this outlet.
|
WDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.6 |
|
cpmAcOtlTotalReactivePwr
The total reactive power being supplied by this outlet.
|
varDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.7 |
|
cpmAcOtlTotalApparentPwr
The total apparent power being supplied by this outlet.
|
VADisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.8 |
|
cpmAcOtlTotalPowerFactor
The total power factor of this outlet.
|
DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.9 |
|
cpmAcOtlTotalEnergy
The total energy supplied by this outlet, since
the last operator reset of this cumulative value. |
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.10 |
|
cpmAcOtlCurrentMinAlarm
The minumum outlet current alarm threshold. Current
values below threshold will trigger an alarm. |
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.11 |
|
cpmAcOtlCurrentMaxAlarm
The maximum outlet current alarm threshold. Current
values above threshold will trigger an alarm. |
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.7.1.12 |
cpmAcOutletLine
table.1.3.6.1.4.1.35774.2.1.8
·
1 row entry
·
9 columns
Table of outlet line data.
Variables pertaining to the outlet line table.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcOutletOutletIndex
The index to the outlet entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.8.1.1 |
|
cpmAcOutletLineIndex
The index to the outlet line entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.8.1.2 |
|
cpmAcOtlPhaseId
The name assigned to this phase of the outlet.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.3 |
|
cpmAcOtlLineCurrent
The line current flowing through this outlet.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.4 |
|
cpmAcOtlLineCurrRatPctOf
The percent of rated line current flowing
through this outlet. |
% of ratedDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.5 |
|
cpmAcOtlLineCurrDemand
The current demand of this outlet.
|
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.6 |
|
cpmAcOtlLineCurrPeakDmd
The highest cpmAcOtlLineCurrDemand measured since
the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.7 |
|
cpmAcOtlLineCurrentMin
The lowest cpmAcOtlLineCurrent measured since
the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.8 |
|
cpmAcOtlLineCurrentMax
The highest cpmAcOtlLineCurrent measured since
the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.8.1.9 |
cpmAcTempNode
table.1.3.6.1.4.1.35774.2.1.12
·
1 row entry
·
7 columns
Table of temperature node data.
Variables pertaining to the temperature node table.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmAcNodeIndex
The index to the temperature node entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.1.12.1.1 |
|
cpmAcNodeId
The name assigned to this temperature node.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.2 |
|
cpmAcNodeTemperature
The temperature at this node.
|
degreesDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.3 |
|
cpmAcNodeTemperatureMax
The highest cpmAcNodeTemperature measured since
the last operator reset of this value. |
degreesDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.4 |
|
cpmAcNodeSysMaxAlmThresh
The factory set system maximum temperature alarm threshold.
Values above threshold will trigger an alarm. |
degreesDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.5 |
|
cpmAcNodeUsrMaxAlmThresh
The user maximum temperature alarm threshold.
Values above threshold will trigger an alarm. |
degreesDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.6 |
|
cpmAcNodeBatteryVoltage
The battery voltage of this temperature node.
|
voltsDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.1.12.1.7 |
cpmDcDigitalIo
table.1.3.6.1.4.1.35774.2.2.2.4
·
1 row entry
·
6 columns
Table of Digital I/O line data.
Variables pertaining to Digital I/Os.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmDcDigitalIoIndex
The index to the Digital I/O entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.2.2.4.1.1 |
|
cpmDcDigitalIoName
The Digital I/O name.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.2.4.1.2 |
|
cpmDcDigitalIoValue
The current value of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.2.4.1.3 |
|
cpmDcDigitalIoDirection
The direction of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.2.4.1.4 |
|
cpmDcDigitalIoLevel
The active level of the digital I/O.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.2.4.1.5 |
|
cpmDcDigitalIoAlarm
Set to generate an alarm on input.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.2.4.1.6 |
cpmDcInfCircuit
table.1.3.6.1.4.1.35774.2.2.5
·
1 row entry
·
18 columns
Table of infeed circuit data.
Variables pertaining to infeed circuit.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmDcInfeedCircuitIndex
The index to the infeed circuit entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.2.5.1.1 |
|
cpmDcCktVoltage
Circuit voltage.
|
volts (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.2 |
|
cpmDcCktVoltageMin
Circuit voltage minimum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.3 |
|
cpmDcCktVoltageMax
Circuit voltage maximum.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.4 |
|
cpmDcCktVoltageMinAlarm
Circuit voltage minimum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.5 |
|
cpmDcCktVoltageMaxAlarm
Circuit voltage maximum alarm threshold.
|
volts (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.6 |
|
cpmDcInfCktPower
Infeed circuit power
|
WDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.7 |
|
cpmDcInfCktPeakPower
Infeed circuit peak power.
|
WDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.8 |
|
cpmDcInfCktEnergyDelivrd
Infeed circuit energy delivered.
|
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.9 |
|
cpmDcInfCktEnergyRcvd
Infeed circuit energy received.
|
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.10 |
|
cpmDcInfCktCurrent
The current measured on this infeed circuit.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.11 |
|
cpmDcInfCktCurrentMin
The minimum current measured on this infeed circuit.
|
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.12 |
|
cpmDcInfCktCurrentMax
The maximum current measured on this infeed circuit.
|
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.13 |
|
cpmDcInfCktCurrRatPctOf
(current / rated current * 100) for this infeed circuit.
|
% of ratedDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.14 |
|
cpmDcInfCktCurrMinAlarm
The minimum current threshold for alarm activiation.
|
amps (RMS)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.15 |
|
cpmDcInfCktCurrMaxAlarm
The maximum current threshold for alarm activiation.
|
amps (RMS)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.16 |
|
cpmDcInfCktCurrDemand
The current demand of this infeed circuit.
|
amps per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.17 |
|
cpmDcInfCktCurrPeakDmd
The highest cpmDcInfCktCurrDemand measured
since the last operator reset of this value. |
amps per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.5.1.18 |
cpmDcOutlet
table.1.3.6.1.4.1.35774.2.2.6
·
1 row entry
·
6 columns
Table of outlet data.
Variables pertaining to the outlet table.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmDcOutletIndex
The index to the outlet entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.2.6.1.1 |
|
cpmDcOutletId
The name assigned to this outlet.
|
DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.6.1.2 |
|
cpmDcOtlCktCurrRating
The rated current of this outlet.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.6.1.3 |
|
cpmDcOtlDemandTime
The interval of time over which the demand
is calculated for the outlet parameters. |
minutesDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.6.1.4 |
|
cpmDcOtlCurrentMinAlarm
The minumum outlet current alarm threshold. Current
values below threshold will trigger an alarm. |
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.6.1.5 |
|
cpmDcOtlCurrentMaxAlarm
The maximun outlet current alarm threshold. Current
values above threshold will trigger an alarm. |
amps (rms)DisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.6.1.6 |
cpmDcOutletCircuit
table.1.3.6.1.4.1.35774.2.2.7
·
1 row entry
·
12 columns
Table of outlet circuit data.
Variables pertaining to the outlet circuit table.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
cpmDcOutletOutletIndex
The index to the outlet entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.2.7.1.1 |
|
cpmDcOutletCircuitIndex
The index to the outlet circuit entry.
|
Enumeration | .1.3.6.1.4.1.35774.2.2.7.1.2 |
|
cpmDcOtlCktCurrent
The current flowing through this outlet circuit.
|
amps (rms)DisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.3 |
|
cpmDcOtlCktCurrRatPctOf
The percent of rated current flowing
through this outlet circuit. |
% of ratedDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.4 |
|
cpmDcOtlCktCurrentDemand
The current demand of this outlet.
|
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.5 |
|
cpmDcOtlCktCurrPeakDmd
The highest cpmDcOtlCktCurrentDemand measured
since the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.6 |
|
cpmDcOtlCktCurrentMin
The lowest cpmDcOtlCktCurrent measured since
the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.7 |
|
cpmDcOtlCktCurrentMax
The highest cpmDcOtlCktCurrent measured since
the last operator reset of this value. |
amps (rms) per demand intervalDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.8 |
|
cpmDcOtlCktPower
The power being supplied by this outlet circuit.
|
WDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.9 |
|
cpmDcOtlCktPeakPower
The peak power supplied by this outlet circuit.
|
WDisplayStringr/w Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.10 |
|
cpmDcOtlCktEnergyDelivrd
The total energy delivered by this outlet, since
the last operator reset of this cumulative value. |
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.11 |
|
cpmDcOtlCktEnergyRcvd
The total energy received by this outlet, since
the last operator reset of this cumulative value. |
kWhDisplayString Textual Convention: DisplayString OctetString |
.1.3.6.1.4.1.35774.2.2.7.1.12 |