SDEVICE-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
33
.1.3.6.1.4.1.31034.2.8 · 1 row entry · 13 columns
This table contains all measures related to the measured
inputs of the DEVICE. Note: either 1 or 3 channels, depending
on number of phases measured.
inputmeasuresEntry entry .1.3.6.1.4.1.31034.2.8.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
channelIndex6
Column Syntax OID
channelIndex6
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.8.1.1
kWhTotalI
Either the only phase in a single phase measurement; or one of
the three phases in a multiphase measurement.
KiloWattHour
Textual Convention: KiloWattHour Integer32
.1.3.6.1.4.1.31034.2.8.1.2
kWhSubtotalI
kWh subtotal register of the only phase in a single phase
measurement; or one of three phases in a multiphase
measurement. Reset to zero with [rsimks].
KiloWattHour
Textual Convention: KiloWattHour Integer32
.1.3.6.1.4.1.31034.2.8.1.3
powerFactorI
The effective power factor in percent.
DeciPowerFactor
Textual Convention: DeciPowerFactor Integer32
.1.3.6.1.4.1.31034.2.8.1.4
actualCurrentI
Actual apparent, RMS current.
DeciAmps
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.8.1.5
peakCurrentI
Peak apparent, RMS current; highest value since last reset of
the alerts.
DeciAmps
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.8.1.6
actualVoltageI
The actual voltage.
DeciVolts
Textual Convention: DeciVolts Integer32
.1.3.6.1.4.1.31034.2.8.1.7
minVoltageI
RMS voltage dip; lowest value since reset of alerts.
DeciVolts
Textual Convention: DeciVolts Integer32
.1.3.6.1.4.1.31034.2.8.1.8
powerVAI
Power value calculated, not in data model of device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.9
powerWattI
Power value calculated by the gateway, not in data model of
device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.10
maxInletAmps
Maximum current per input phase in A; should last at least
[stpkdr] MilliSeconds before triggering an alert.
DeciAmpsr/w
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.8.1.11
inputCTratio
The multiplier to use in case of use of /5 current
transformers. Defaults to 1.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.12
inputName
User configurable naming of inputs or phases. Useful if
channels are used to measure branches..
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.31034.2.8.1.13
.1.3.6.1.4.1.31034.2.9 · 1 row entry · 2 columns
This table contains the customer specific settings,
determining toutlestablehe behaviour of the DEVICE.
outletsEntry entry .1.3.6.1.4.1.31034.2.9.1
The record containing the registers forthe channel selected by
channelIndex.
Indexes
channelIndex4
Column Syntax OID
channelIndex4
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.9.1.1
outletName
User configurable naming of individual outlets. Useful to
distinguish outlets based on customer or device name.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.31034.2.9.1.2
.1.3.6.1.4.1.31034.2.10 · 1 row entry · 9 columns
This table contains all measures related to the measured
outputs of the DEVICE. Note: up to 48 channels, depending on
number of measured outlets.
outputmeasuresEntry entry .1.3.6.1.4.1.31034.2.10.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
channelIndex7
Column Syntax OID
channelIndex7
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.10.1.1
kWhTotalO
Total kWh of selected output.
KiloWattHour
Textual Convention: KiloWattHour Integer32
.1.3.6.1.4.1.31034.2.10.1.2
kWhSubtotalO
kWh subtotal register of selected output. Reset to zero with
[rsomks].
KiloWattHour
Textual Convention: KiloWattHour Integer32
.1.3.6.1.4.1.31034.2.10.1.3
powerFactorO
Power factor of output.
DeciPowerFactor
Textual Convention: DeciPowerFactor Integer32
.1.3.6.1.4.1.31034.2.10.1.4
actualCurrentO
Actual apparent, RMS current.
DeciAmps
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.10.1.5
peakCurrentO
Peak apparent, RMS current; highest value since last reset of
alerts.
DeciAmps
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.10.1.6
actualVoltageO
Actual voltage on output.
DeciVolts
Textual Convention: DeciVolts Integer32
.1.3.6.1.4.1.31034.2.10.1.7
maxOutletAmps
Maximum current per outlet in A; should last at least [stpkdr]
MilliSeconds before triggering an alert.
DeciAmpsr/w
Textual Convention: DeciAmps Integer32
.1.3.6.1.4.1.31034.2.10.1.8
outputCTratio
The multiplier to use in case of use of /5 current
transformers. Defaults to 1.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.10.1.9
.1.3.6.1.4.1.31034.2.11 · 1 row entry · 5 columns
This table contains the current status of switchable
DEVICE's.
switchedoutletsEntry entry .1.3.6.1.4.1.31034.2.11.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
channelIndex5
Column Syntax OID
channelIndex5
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.11.1.1
currentState
The actual state of the outlet relays. The hardware will
contain max 48 outlets. Writing is only effective after setting
[swounl].
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.2.11.1.2
scheduled
A one indicates pending activity; the switch delay has not yet
expired.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.2.11.1.3
unlock
Setting the value to one will release the safety for this
outlet for a couple seconds; switching and rebooting are then
temporarily enabled.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.11.1.4
individualOutletDelay
Delay before an individual outlet switches on at power-up in
Seconds.
Secondsr/w
Textual Convention: Seconds Integer32
.1.3.6.1.4.1.31034.2.11.1.5
.1.3.6.1.4.1.31034.2.12 · 1 row entry · 4 columns
This table contains the environmental measurements. As well
internal temperature as external temperature probes.
sensorEntry entry .1.3.6.1.4.1.31034.2.12.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
channelIndex8
Column Syntax OID
channelIndex8
The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.12.1.1
sensorType
Type of connected sensor, either T, H or I for respectively
Temperature (C), Humidity (%) or dry switch contact
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.31034.2.12.1.2
sensorValue
Value of connected sensor
DeciValue
Textual Convention: DeciValue Integer32
.1.3.6.1.4.1.31034.2.12.1.3
sensorName
User definable name for sensors.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.31034.2.12.1.4