ROOMALERT24E-MIB

Imported Objects
RFC-1212 OBJECT-TYPE
RFC-1215 TRAP-TYPE
RFC1155-SMI Counter enterprises IpAddress TimeTicks
Objects (69)
avtech .1.3.6.1.4.1.20916
products .1.3.6.1.4.1.20916.1
roomalert24e .1.3.6.1.4.1.20916.1.5
sensors .1.3.6.1.4.1.20916.1.5.1
internal .1.3.6.1.4.1.20916.1.5.1.1
temperature .1.3.6.1.4.1.20916.1.5.1.1.1
internal-tempf mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.1.1.1
internal-tempc mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.1.1.2
humidity .1.3.6.1.4.1.20916.1.5.1.1.2
internal-humidity mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.1.2.1
heat-index .1.3.6.1.4.1.20916.1.5.1.1.3
internal-heat-index mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.1.3.1
internal-heat-indexc mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.1.3.2
digital .1.3.6.1.4.1.20916.1.5.1.2
digital-sen1 .1.3.6.1.4.1.20916.1.5.1.2.1
digital-sen1-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.1.1
digital-sen1-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.1.2
digital-sen1-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.1.3
digital-sen1-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.1.4
digital-sen1-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.1.5
digital-sen2 .1.3.6.1.4.1.20916.1.5.1.2.2
digital-sen2-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.2.1
digital-sen2-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.2.2
digital-sen2-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.2.3
digital-sen2-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.2.4
digital-sen2-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.2.5
digital-sen3 .1.3.6.1.4.1.20916.1.5.1.2.3
digital-sen3-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.3.1
digital-sen3-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.3.2
digital-sen3-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.3.3
digital-sen3-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.3.4
digital-sen3-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.3.5
digital-sen4 .1.3.6.1.4.1.20916.1.5.1.2.4
digital-sen4-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.4.1
digital-sen4-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.4.2
digital-sen4-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.4.3
digital-sen4-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.4.4
digital-sen4-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.4.5
digital-sen5 .1.3.6.1.4.1.20916.1.5.1.2.5
digital-sen5-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.5.1
digital-sen5-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.5.2
digital-sen5-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.5.3
digital-sen5-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.5.4
digital-sen5-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.5.5
digital-sen6 .1.3.6.1.4.1.20916.1.5.1.2.6
digital-sen6-1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.6.1
digital-sen6-2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.6.2
digital-sen6-3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.6.3
digital-sen6-4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.6.4
digital-sen6-5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.2.6.5
switch .1.3.6.1.4.1.20916.1.5.1.3
switch-sen1 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.1
switch-sen10 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.10
switch-sen11 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.11
switch-sen12 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.12
switch-sen13 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.13
switch-sen14 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.14
switch-sen15 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.15
switch-sen16 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.16
switch-sen2 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.2
switch-sen3 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.3
switch-sen4 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.4
switch-sen5 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.5
switch-sen6 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.6
switch-sen7 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.7
switch-sen8 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.8
switch-sen9 mandatory Integer32 .1.3.6.1.4.1.20916.1.5.1.3.9
traps .1.3.6.1.4.1.20916.1.5.2
alarmmessage mandatory OctetString .1.3.6.1.4.1.20916.1.5.2.1
Notifications / Traps (28)
NameOIDDescription
tempalarm1-24e .1.3.6.1.4.1.20916.1.5.0.1
A tempalarm1 trap signifies that the current
temperature on external sensor 1 is outside the 
defined high or low threshold.
humidityclear2-24e .1.3.6.1.4.1.20916.1.5.0.10
A humidityclear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityalarm3-24e .1.3.6.1.4.1.20916.1.5.0.11
A humidityalarm3 trap signifies that the current
humidity on external sensor 3 is outside the 
defined high or low threshold.
humidityclear3-24e .1.3.6.1.4.1.20916.1.5.0.12
A humidityclear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined 
high or low threshold.
switchalarm1-24e .1.3.6.1.4.1.20916.1.5.0.13
A switchalarm1 trap signifies that switch sensor 1
is in an alarm state.
switchclear1-24e .1.3.6.1.4.1.20916.1.5.0.14
A switchclear1 trap signifies that the switch sensor 1
has returned to a normal state.
switchalarm2-24e .1.3.6.1.4.1.20916.1.5.0.15
A switchalarm2 trap signifies that switch sensor 2
is in an alarm state.
switchclear2-24e .1.3.6.1.4.1.20916.1.5.0.16
A switchclear2 trap signifies that the switch sensor 2
has returned to a normal state.
switchalarm3-24e .1.3.6.1.4.1.20916.1.5.0.17
A switchalarm1 trap signifies that switch sensor 1
is in an alarm state.
switchclear3-24e .1.3.6.1.4.1.20916.1.5.0.18
A switchclear3 trap signifies that the switch sensor 3
has returned to a normal state.
switchalarm4-24e .1.3.6.1.4.1.20916.1.5.0.19
A switchalarm4 trap signifies that switch sensor 4
is in an alarm state.
room-alert-24e-snmp-trap .1.3.6.1.4.1.20916.1.5.0.2
A room-alert-24e-snmp-trap indicates that an alarm
condition has occurred on the sensor indicated
by the alarmmessage variable.
switchclear4-24e .1.3.6.1.4.1.20916.1.5.0.20
A switchclear4 trap signifies that the switch sensor 4
has returned to a normal state.
switchalarm5-24e .1.3.6.1.4.1.20916.1.5.0.21
A switchalarm5 trap signifies that switch sensor 5
is in an alarm state.
switchclear5-24e .1.3.6.1.4.1.20916.1.5.0.22
A switchclear5 trap signifies that the switch sensor 5
has returned to a normal state.
switchalarm6-24e .1.3.6.1.4.1.20916.1.5.0.23
A switchalarm6 trap signifies that switch sensor 6
is in an alarm state.
switchclear6-24e .1.3.6.1.4.1.20916.1.5.0.24
A switchclear6 trap signifies that the switch sensor 6
has returned to a normal state.
switchalarm7-24e .1.3.6.1.4.1.20916.1.5.0.25
A switchalarm7 trap signifies that switch sensor 7
is in an alarm state.
switchclear7-24e .1.3.6.1.4.1.20916.1.5.0.26
A switchclear7 trap signifies that the switch sensor 7
has returned to a normal state.
switchalarm8-24e .1.3.6.1.4.1.20916.1.5.0.27
A switchalarm8 trap signifies that switch sensor 8
is in an alarm state.
switchclear8-24e .1.3.6.1.4.1.20916.1.5.0.28
A switchclear8 trap signifies that the switch sensor 8
has returned to a normal state.
tempalarm2-24e .1.3.6.1.4.1.20916.1.5.0.3
A tempalarm2 trap signifies that the current
temperature on external sensor 2 is outside the 
defined high or low threshold.
tempclear2-24e .1.3.6.1.4.1.20916.1.5.0.4
A tempclear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined 
high or low threshold.
tempalarm3-24e .1.3.6.1.4.1.20916.1.5.0.5
A tempalarm3 trap signifies that the current
temperature on external sensor 3 is outside the 
defined high or low threshold.
tempclear3-24e .1.3.6.1.4.1.20916.1.5.0.6
A tempclear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityalarm1-24e .1.3.6.1.4.1.20916.1.5.0.7
A humidityalarm1 trap signifies that the current
humidity on external sensor 1 is outside the 
defined high or low threshold.
humidityclear1-24e .1.3.6.1.4.1.20916.1.5.0.8
A humidityclear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityalarm2-24e .1.3.6.1.4.1.20916.1.5.0.9
A humidityalarm2 trap signifies that the current
humidity on external sensor 2 is outside the 
defined high or low threshold.