POSEIDON-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
31

inpTable

table mandatory
.1.3.6.1.4.1.21796.3.3.1 · 1 row entry · 5 columns
A list of binary input entries.
inpEntry entry .1.3.6.1.4.1.21796.3.3.1.1
An entry containing information applicable
to a particular binary input.
Indexes
inpIndex
Column Syntax OID
inpIndex mandatory
The binary input index.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.1.1.1
inpValue mandatory
The binary input value.
OnOff
Textual Convention: OnOff Enumeration
Type Values:
0off
1on
.1.3.6.1.4.1.21796.3.3.1.1.2
inpName mandatory
The binary input name.
IONamer/w
Textual Convention: IOName OctetString
Type Constraints:
range: 0..20
.1.3.6.1.4.1.21796.3.3.1.1.3
inpAlarmSetup mandatory
You can enable alarm for this binary input.
Alarm can be inactive or active for On/Off state.
InputAlarmSetupr/w
Textual Convention: InputAlarmSetup Enumeration
Type Values:
0inactive
1activeOff
2activeOn
.1.3.6.1.4.1.21796.3.3.1.1.4
inpAlarmState mandatory
The binary input alarm state.
InputAlarmState
Textual Convention: InputAlarmState Enumeration
Type Values:
0normal
1alarm
.1.3.6.1.4.1.21796.3.3.1.1.5

outTable

table mandatory
.1.3.6.1.4.1.21796.3.3.2 · 1 row entry · 5 columns
A list of binary output entries.
outEntry entry .1.3.6.1.4.1.21796.3.3.2.1
An entry containing information applicable
to a particular binary output.
Indexes
outIndex
Column Syntax OID
outIndex mandatory
The binary output index.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.2.1.1
outValue mandatory
The binary output value. 0 off(open), 1 on(close)
OnOffr/w
Textual Convention: OnOff Enumeration
Type Values:
0off
1on
.1.3.6.1.4.1.21796.3.3.2.1.2
outName mandatory
The binary output name.
IONamer/w
Textual Convention: IOName OctetString
Type Constraints:
range: 0..20
.1.3.6.1.4.1.21796.3.3.2.1.3
outType mandatory
The binary output type. 0 relay (off, on), 1 rts (-10,+10V), 2 dtr (0,10V)
OutputType
Textual Convention: OutputType Enumeration
Type Values:
0onOff
1rts
2dtr
.1.3.6.1.4.1.21796.3.3.2.1.4
outMode mandatory
The binary output mode. 0 manual, 1 autoAlarm,
2 autoTriggerEq, 3 autoTriggerHi, 4 autoTriggerLo
OutputModer/w
Textual Convention: OutputMode Enumeration
Type Values:
0manual
1autoAlarm
2autoTriggerEq
3autoTriggerHi
4autoTriggerLo
.1.3.6.1.4.1.21796.3.3.2.1.5

sensTable

table mandatory
.1.3.6.1.4.1.21796.3.3.3 · 1 row entry · 10 columns
A list of sensor table entries. The number
of entries corresponds with number of detected sensors.
sensEntry entry .1.3.6.1.4.1.21796.3.3.3.1
An entry containing information applicable to a
particular sensor.
Indexes
sensIndex
Column Syntax OID
sensIndex mandatory
The sensor index.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.3.1.1
sensName mandatory
The sensor name.
SensorName
Textual Convention: SensorName OctetString
Type Constraints:
range: 0..15
.1.3.6.1.4.1.21796.3.3.3.1.2
sensState mandatory
The sensor state.
SensorState
Textual Convention: SensorState Enumeration
Type Values:
0invalid
1normal
2alarmstate
3alarm
.1.3.6.1.4.1.21796.3.3.3.1.4
sensString mandatory
The string representation of sensor value.
SensorString
Textual Convention: SensorString OctetString
Type Constraints:
range: 0..10
.1.3.6.1.4.1.21796.3.3.3.1.5
sensValue mandatory
The integer (decimal * 10) representation
of sensor value.
SensorValue
Textual Convention: SensorValue Integer32
.1.3.6.1.4.1.21796.3.3.3.1.6
sensValueRaw mandatory
The original raw value of sensor
(it differs for each sensor type, especially
1-Wire sensors have different precisions).
SensorValue
Textual Convention: SensorValue Integer32
.1.3.6.1.4.1.21796.3.3.3.1.7
sensID mandatory
The sensor ID.
SensorID
Textual Convention: SensorID Integer32
Type Constraints:
range: 0..65535
.1.3.6.1.4.1.21796.3.3.3.1.8
sensUnit mandatory
The sensor unit.
UnitType
Textual Convention: UnitType Enumeration
Type Values:
0celsius
1fahrenheit
2kelvin
3percent
4volt
5miliAmper
6noUnit
7pulse
8switch
9dewPoint
10absoluteHumidity
11pressure
12universal
.1.3.6.1.4.1.21796.3.3.3.1.9
sensUnitString mandatory
The string representation of sensor unit.
SensorUnitString
Textual Convention: SensorUnitString OctetString
Type Constraints:
range: 0..4
.1.3.6.1.4.1.21796.3.3.3.1.10
sensPortID mandatory
The sensor port ID.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21796.3.3.3.1.11

tsAlarmTable

table mandatory
.1.3.6.1.4.1.21796.3.3.50.2 · 1 row entry · 5 columns
A list of alarm table entries.  The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect.  The table
is initially empty at agent startup.  The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.  The agent creates the first row with
tsAlarmId equal to 1, and increments the value of
tsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of tsAlarmId would otherwise be
exceeded.  Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
tsAlarmId might have wrapped.
          
The number of rows in the table at any given time is
reflected by the value of tsAlarmsPresent.
tsAlarmEntry entry .1.3.6.1.4.1.21796.3.3.50.2.1
An entry containing information applicable
to a particular alarm.
Indexes
tsAlarmIdx
Column Syntax OID
tsAlarmIdx mandatory
An index to alarm table.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.50.2.1.1
tsAlarmId mandatory
A unique identifier for an alarm condition.
This value must remain constant.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.50.2.1.2
tsAlarmDescr mandatory
Description of the alarm condition.
Enumeration
Enumerated Values:
1inputStateAlarm
2temperatureOutOfRange
.1.3.6.1.4.1.21796.3.3.50.2.1.3
tsAlarmSensName mandatory
Name of sensor with alarm condition.
SensorName
Textual Convention: SensorName OctetString
Type Constraints:
range: 0..15
.1.3.6.1.4.1.21796.3.3.50.2.1.4
tsAlarmTime mandatory
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected
at the time of agent startup and presumably existed
before agent startup, the value of tsAlarmTime shall equal 0.
TimeStamp
Textual Convention: TimeStamp Unsigned32
.1.3.6.1.4.1.21796.3.3.50.2.1.5

sensSetupTable

table mandatory
.1.3.6.1.4.1.21796.3.3.99.1.2 · 1 row entry · 6 columns
A list of sensor table setup entries. The number
of entries corresponds with number of detected sensors.
sensSetupEntry entry .1.3.6.1.4.1.21796.3.3.99.1.2.1
An entry containing setup information
for a particular sensor.
Indexes
sensSetupIndex
Column Syntax OID
sensSetupIndex mandatory
The sensor setup table index.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.21796.3.3.99.1.2.1.1
sensSetupName mandatory
The sensor name.
SensorNamer/w
Textual Convention: SensorName OctetString
Type Constraints:
range: 0..15
.1.3.6.1.4.1.21796.3.3.99.1.2.1.2
sensFlags mandatory
The behaviour of sensor
- 0x01: range or level detection
- 0x02: enable trap sending
-- 0x04: output set (thermostat)
- 0x08: sensor enabled
- 0x10: enable SMS sending
- 0x20: enable email sending.
SensorFlagsr/w
Textual Convention: SensorFlags Integer32
.1.3.6.1.4.1.21796.3.3.99.1.2.1.5
sensLimitMin mandatory
The sensor low limit.
SensorValuer/w
Textual Convention: SensorValue Integer32
.1.3.6.1.4.1.21796.3.3.99.1.2.1.6
sensLimitMax mandatory
The sensor high limit.
SensorValuer/w
Textual Convention: SensorValue Integer32
.1.3.6.1.4.1.21796.3.3.99.1.2.1.7
sensHysteresis mandatory
The sensor hysteresis.
SensorValuer/w
Textual Convention: SensorValue Integer32
.1.3.6.1.4.1.21796.3.3.99.1.2.1.8