PDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
2
Rows
2
Columns
25
.1.3.6.1.4.1.13742.2.1.2.2 · 1 row entry · 12 columns
A list of outlet entries. The number of
entries is given by the value of ifNumber.
outletEntry entry .1.3.6.1.4.1.13742.2.1.2.2.1
An outlet entry containing objects at the
for a particular outlet.
Indexes
outletIndex
Column Syntax OID
outletIndex
A unique value for each outlet. Its value
ranges between 1 and the value of outletNumber.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.1
outletLabel
A textual string containing information
about the outlet.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.13742.2.1.2.2.1.2
outletOperationalState
A value for each outlet which describes the
operational state of the outlet. It is also
used to set the operational state of the outlet
Enumerationr/w
Enumerated Values:
-1error
0off
1on
2cycling
.1.3.6.1.4.1.13742.2.1.2.2.1.3
outletSensorNumberRMSCurrent
A unique value for the RMS current sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.4
outletSensorNumberRMSPhase
A unique value for the RMS phase sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.5
outletSensorNumberMaxRMSCurrent
A unique value for the max. RMS current sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.6
outletSensorNumberTrueRMSPower
A unique value for the true RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.7
outletSensorNumberApparentRMSPower
A unique value for the apparent RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.8
outletSensorNumberMaxTrueRMSPower
A unique value for the max. true RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.9
outletSensorNumberAverageRealRMSPower
A unique value for the average real RMS power sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.10
outletSensorNumberRMSVoltage
A unique value for the RMS voltage sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.11
outletSensorNumberFrequency
A unique value for the frequency sensor
attached to the outlet. This is also an index
into the sensors table sensorTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.2.2.1.12
.1.3.6.1.4.1.13742.2.1.3.2 · 1 row entry · 13 columns
A list of sensors of the pdu. The number of
entries is given by the value of sensorNumber.
sensorEntry entry .1.3.6.1.4.1.13742.2.1.3.2.1
An sensor entry containing objects at the
for a particular sensor.
Indexes
sensorIndex
Column Syntax OID
sensorIndex
A unique value for each sensor. Its value
ranges between 1 and may exceed the value
of sensorNumber.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.3.2.1.1
sensorLabel
A textual string containing information
about the sensor.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.13742.2.1.3.2.1.2
sensorType
The type of the sensor.
Enumeration
Enumerated Values:
0receptacle-rms-current
1receptacle-rms-phase
2receptacle-max-rms-current
3receptacle-true-rms-power
4receptacle-apparent-rms-power
5receptacle-max-true-rms-power
6receptacle-average-real-rms-power
192power-branch-rms-voltage
193power-branch-frequency
194power-branch-temperature
195power-branch-rms-current
197environmental-temp-3
198environmental-temp-2
199environmental-temp-1
206environmental-humidity-2
207environmental-humidity-1
240unit-circuit-break-0
241unit-circuit-break-1
242unit-rms-current
243unit-max-rms-current
244unit-temp
245unit-true-power
246unit-apparent-power
247unit-rms-voltage
.1.3.6.1.4.1.13742.2.1.3.2.1.3
sensorValue
The value the sensor delivers. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned
SNMPv2-SMIOpaque
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.4
sensorUnit
A string that containes the unit of the value.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.13742.2.1.3.2.1.5
sensorState
To state of the sensor.
Enumeration
Enumerated Values:
-1unavailable
0ok
1below-lower-non-critical
2above-upper-non-critical
3below-lower-critical
4above-upper-critical
5below-lower-non-recoverable
6above-upper-non-recoverable
.1.3.6.1.4.1.13742.2.1.3.2.1.6
sensorAssociatedOutlet
A unique value for the outlet the sensor
is associated to, if any. This is also an
index into the outlets table outletTable.
An value of 0 indicates no associated outlet.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.13742.2.1.3.2.1.7
sensorLowerNonCriticalThreshold
The value for the lower non-critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.8
sensorUpperNonCriticalThreshold
The value for the upper non-critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.9
sensorLowerCriticalThreshold
The value for the lower critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_OCTE…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.10
sensorUpperCriticalThreshold
The value for the upper critical
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, ASN_OCTE…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.11
sensorLowerNonRecoverableThreshold
The value for the lower non-recoverable
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, A…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.12
sensorUpperNonRecoverableThreshold
The value for the upper non-recoverable
threshold of the sensor. This value is
provided as ASN_OPAQUE_FLOAT type. In case of
an error or unavailability NaN is returned.
Setting this value is possible via:
ASN_INTEGER, A…
SNMPv2-SMIOpaquer/w
Textual Convention: SNMPv2-SMIOpaque OctetString
.1.3.6.1.4.1.13742.2.1.3.2.1.13