NETSURE-NCU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
12
Rows
12
Columns
88
.1.3.6.1.4.1.6302.2.1.2.5.5 · 1 row entry · 6 columns
Battery Table.
psBatteryEntry entry .1.3.6.1.4.1.6302.2.1.2.5.5.1
Battery Measurement Table Entry.
Indexes
psBatteryIndex
Column Syntax OID
psBatteryIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.5.5.1.1
psBatteryCurrent
Battery current in mA.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.5.1.2
psBatteryName
Battery shunt name.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.5.5.1.3
psBatteryCapacity
Battery capacity in Ah.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.5.1.4
psBatteryCapacityPercent
Battery capacity in percent.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.5.1.5
psBatteryRatedCapacity
Battery capacity in Ah * 1000.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.5.1.6
.1.3.6.1.4.1.6302.2.1.2.5.20 · 1 row entry · 8 columns
BMS Table.
psBmsEntry entry .1.3.6.1.4.1.6302.2.1.2.5.20.1
BMS Measurement Table Entry.
Indexes
psBmsIndex
Column Syntax OID
psBmsIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.5.20.1.1
psBmsVoltage
BMS voltage in mV.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.2
psBmsCurrent
BMS Current in mA.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.3
psBmsRatedCapacity
BMS rated capacity.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.4
psBmsStateOfCharge
BMS State Of Charge in percent.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.5
psBmsCapacity
BMS capacity in Ah.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.6
psBmsAverageTemperature
BMS cell average temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.7
psBmsAmbientTemperature
BMS ambient temperature, stored as 0.001 Celsius degree.
The integer 2147483647 represents invalid value..
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.5.20.1.8
.1.3.6.1.4.1.6302.2.1.2.7.3 · 1 row entry · 6 columns
Temperature Measurement Table.
psTemperatureEntry entry .1.3.6.1.4.1.6302.2.1.2.7.3.1
Temperature Measurement Table Entry.
Indexes
psTemperatureIndex
Column Syntax OID
psTemperatureIndex
Temperature Probe Number
Integer32
Constraints:
range: 1-71
.1.3.6.1.4.1.6302.2.1.2.7.3.1.1
psTemperatureMeasurement
Temperature Value In degrees Centigrade * 1000.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.7.3.1.2
psTemperatureName
Configured Temperature Probe Name.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.7.3.1.3
psTemperatureType
Temperature Probe Type
Enumerationr/w
Enumerated Values:
0none
1ambient
2battery
.1.3.6.1.4.1.6302.2.1.2.7.3.1.4
psTemperatureAlarmStatus
Temperature Probe Alarm Status
Enumeration
Enumerated Values:
0high
1low
2fail
3none
.1.3.6.1.4.1.6302.2.1.2.7.3.1.5
psTemperatureMeasurementF
Temperature Value In degrees Fahrenheit * 1000.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.7.3.1.6
.1.3.6.1.4.1.6302.2.1.2.11.4 · 1 row entry · 8 columns
Table holding information about indivual rectifiers.
psRectifierEntry entry .1.3.6.1.4.1.6302.2.1.2.11.4.1
An entry (conceptual row) in the rectifierInfoTable.
Indexes
psRectifierIndex
Column Syntax OID
psRectifierIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.11.4.1.1
psRectifierProductNumber
Rectifier Product Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.11.4.1.2
psRectifierHWVersion
Rectifier Hardware Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.11.4.1.3
psRectifierSWVersion
Rectifier Software Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.11.4.1.4
psRectifierSerialNumber
Rectifier Serial Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.11.4.1.5
psRectifierCurrent
Rectifier Current.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.11.4.1.6
psRectifierIdent
Rectifier physical location identifier.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.11.4.1.7
psRectifierFail
The type of alarm change. One of
(1) activated
(2) deactivated
StatusChange
Textual Convention: StatusChange Enumeration
Type Values:
1activated
2deactivated
.1.3.6.1.4.1.6302.2.1.2.11.4.1.8
.1.3.6.1.4.1.6302.2.1.2.12.2 · 1 row entry · 3 columns
Distribution Table.
psDistributionLoadEntry entry .1.3.6.1.4.1.6302.2.1.2.12.2.1
Distribution Measurement Table Entry.
Indexes
psDistributionLoadIndex
Column Syntax OID
psDistributionLoadIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-268386303
.1.3.6.1.4.1.6302.2.1.2.12.2.1.1
psDistributionLoadCurrent
Distribution current in mA.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.12.2.1.2
psDistributionLoadName
Distribution name.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.12.2.1.3
.1.3.6.1.4.1.6302.2.1.2.12.3 · 1 row entry · 3 columns
Distribution Table.
psDistributionGeneralEntry entry .1.3.6.1.4.1.6302.2.1.2.12.3.1
Distribution Measurement Table Entry.
Indexes
psDistributionGeneralIndex
Column Syntax OID
psDistributionGeneralIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-268386303
.1.3.6.1.4.1.6302.2.1.2.12.3.1.1
psDistributionGeneralCurrent
Distribution current in mA.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.12.3.1.2
psDistributionGeneralName
Distribution name.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.12.3.1.3
.1.3.6.1.4.1.6302.2.1.2.13.6 · 1 row entry · 8 columns
Table holding information about indivual converters.
psConverterEntry entry .1.3.6.1.4.1.6302.2.1.2.13.6.1
An entry (conceptual row) in the ConverterInfoTable.
Indexes
psConverterIndex
Column Syntax OID
psConverterIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.6302.2.1.2.13.6.1.1
psConverterProductNumber
Converter Product Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.13.6.1.2
psConverterHWVersion
Converter Hardware Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.13.6.1.3
psConverterSWVersion
Converter Software Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.13.6.1.4
psConverterSerialNumber
Converter Serial Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.13.6.1.5
psConverterCurrent
Converter Current.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.13.6.1.6
psConverterIdent
Converter physical location identifier.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.13.6.1.7
psConverterFail
The type of alarm change. One of
(1) activated
(2) deactivated
StatusChange
Textual Convention: StatusChange Enumeration
Type Values:
1activated
2deactivated
.1.3.6.1.4.1.6302.2.1.2.13.6.1.8
.1.3.6.1.4.1.6302.2.1.2.15 · 1 row entry · 2 columns
Table of indexed equipment signal values.
equipmentSignalTableEntry entry .1.3.6.1.4.1.6302.2.1.2.15.1
An entry (conceptual row) in the psEquipment Signal Table.
Indexes
psEquipmentSignalTableEntryIndex
Column Syntax OID
psEquipmentSignalTableEntryIndex
The unique sequence number of this equipment signal.
Integer32
Constraints:
range: 1-268386303
.1.3.6.1.4.1.6302.2.1.2.15.1.1
psEquipmentSignalValue
Indexed equipment signal value.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.15.1.2
.1.3.6.1.4.1.6302.2.1.2.19.1 · 1 row entry · 13 columns
Table holding information about indivual FCU Plus equipment.
psFCUPlusEntry entry .1.3.6.1.4.1.6302.2.1.2.19.1.1
An entry (conceptual row) in the FCUPlus InfoTable.
Indexes
psFCUPlusIndex
Column Syntax OID
psFCUPlusIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.19.1.1.1
psFCUPlusTemperature1
FCUPlus Temperature1 stored as milli Celsius.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.19.1.1.2
psFCUPlusTemperature2
FCUPlus Temperature2 stored as milli Celsius.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.19.1.1.3
psFCUPlusTemperature3
FCUPlus Temperature3 stored as milli Celsius.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.19.1.1.4
psFCUPlusHumidity
FCUPlus Humidity percent.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.19.1.1.5
psFCUPlusFanType
FCUPlus fan type,
HeatChange(0),
ForcedVent(1)
Enumeration
Enumerated Values:
0heatChange
1forcedVent
.1.3.6.1.4.1.6302.2.1.2.19.1.1.6
psFCUPlusWithHeater
FCUPlus with heater,
no(0),
yes(1)
Enumeration
Enumerated Values:
0no
1yes
.1.3.6.1.4.1.6302.2.1.2.19.1.1.7
psFCUPlusFanGroup1State
FCUPlus fan group 1 state,
stop(0),
start(1)
Enumeration
Enumerated Values:
0stop
1start
.1.3.6.1.4.1.6302.2.1.2.19.1.1.8
psFCUPlusFanGroup2State
FCUPlus fan group 2 state,
stop(0),
start(1)
Enumeration
Enumerated Values:
0stop
1start
.1.3.6.1.4.1.6302.2.1.2.19.1.1.9
psFCUPlusFanGroup3State
FCUPlus fan group 3 state,
stop(0),
start(1)
Enumeration
Enumerated Values:
0stop
1start
.1.3.6.1.4.1.6302.2.1.2.19.1.1.10
psFCUPlusHeater1State
FCUPlus heater 1 state,
stop(0),
start(1)
Enumeration
Enumerated Values:
0stop
1start
.1.3.6.1.4.1.6302.2.1.2.19.1.1.11
psFCUPlusHeater2State
FCUPlus heater 2 state,
stop(0),
start(1)
Enumeration
Enumerated Values:
0stop
1start
.1.3.6.1.4.1.6302.2.1.2.19.1.1.12
psFCUPlusRunningMode
FCUPlus running mode,
Normal(0),
Test(1)
Enumeration
Enumerated Values:
0normal
1test
.1.3.6.1.4.1.6302.2.1.2.19.1.1.13
.1.3.6.1.4.1.6302.2.1.2.21.4 · 1 row entry · 9 columns
Table holding information about indivual rectifiers.
psInverterEntry entry .1.3.6.1.4.1.6302.2.1.2.21.4.1
An entry (conceptual row) in the rectifierInfoTable.
Indexes
psInverterIndex
Column Syntax OID
psInverterIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.21.4.1.1
psInverterProductNumber
Inverter Product Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.21.4.1.2
psInverterHWVersion
Inverter Hardware Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.21.4.1.3
psInverterSWVersion
Inverter Software Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.21.4.1.4
psInverterSerialNumber
Inverter Serial Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.21.4.1.5
psInverterVoltage
Inverter Output Voltage.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.21.4.1.6
psInverterCurrent
Inverter Output Current.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.21.4.1.7
psInverterIdent
Inverter physical location identifier.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.21.4.1.8
psInverterFrequency
Inverter Output Frequency
StatusChange
Textual Convention: StatusChange Enumeration
Type Values:
1activated
2deactivated
.1.3.6.1.4.1.6302.2.1.2.21.4.1.9
.1.3.6.1.4.1.6302.2.1.2.25.10 · 1 row entry · 16 columns
Table holding information about indivual solar converters.
psSolarEntry entry .1.3.6.1.4.1.6302.2.1.2.25.10.1
An entry (conceptual row) in the solar converter InfoTable.
Indexes
psSolarIndex
Column Syntax OID
psSolarIndex
Automatically generated index object.
Integer32
Constraints:
range: 1-16777215
.1.3.6.1.4.1.6302.2.1.2.25.10.1.1
psSolarProductNumber
Solar Converter Product Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.25.10.1.2
psSolarHWVersion
Solar Converter Hardware Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.25.10.1.3
psSolarSWVersion
Solar Converter Software Revision.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.25.10.1.4
psSolarSerialNumber
Solar Converter Serial Number.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.25.10.1.5
psSolarIdent
Solar Converter physical location identifier.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.2.25.10.1.6
psSolarRatedIoutAtMaxVout
Solar converter rated Iout milliamps at Max Vout.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.7
psSolarInputVoltage
Solar converter rated input voltage in millivolts.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.8
psSolarInputCurrent
Solar converter input current in milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.9
psSolarInputPower
Solar converter input power in W.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.10
psSolarOutputVoltage
Solar converter output voltage in millivolts.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.11
psSolarOutputCurrent
Solar converter output current in milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.12
psSolarOutputPower
Solar converter output power in W.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.13
psSolarUsedCapacity
Solar converter used capacity in percent.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.14
psSolarTotalRunningTime
Solar converter total running time in hours * 1000.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.2.25.10.1.15
psSolarFail
The type of alarm change. One of
(1) activated
(2) deactivated
StatusChange
Textual Convention: StatusChange Enumeration
Type Values:
1activated
2deactivated
.1.3.6.1.4.1.6302.2.1.2.25.10.1.16
.1.3.6.1.4.1.6302.2.1.4 · 1 row entry · 6 columns
Table holding information about the currently active alarms.
activeAlarmEntry entry .1.3.6.1.4.1.6302.2.1.4.1
An entry (conceptual row) in the alarmTrapTable.
Indexes
alarmIndex
Column Syntax OID
alarmIndex
The unique sequence number of this alarm trap.
SNMPv2-SMICounter32
Textual Convention: SNMPv2-SMICounter32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.6302.2.1.4.1.1
alarmTime
Date and time when event occured (local time), including
timezone if supported by controller.
SNMPv2-TCDateAndTime
Textual Convention: SNMPv2-TCDateAndTime OctetString
Type Constraints:
range: 8
range: 11
.1.3.6.1.4.1.6302.2.1.4.1.2
alarmStatusChange
The type of alarm change. One of
(1) activated
(2) deactivated
StatusChange
Textual Convention: StatusChange Enumeration
Type Values:
1activated
2deactivated
.1.3.6.1.4.1.6302.2.1.4.1.3
alarmSeverity
The severity of the alarm. One of
(3) warning - OA, lowest level of alarm severity
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of alarm severity
Status
Textual Convention: Status Enumeration
Type Values:
1unknown
2normal
3warning
4minor
5major
6critical
7unmanaged
8restricted
9testing
10disabled
.1.3.6.1.4.1.6302.2.1.4.1.4
alarmDescription
Free-text description of alarm.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.6302.2.1.4.1.5
alarmType
Alarm type, i.e. an integer specifying the type of alarm.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.6302.2.1.4.1.6