lmsBinaryChannelTable

table mandatory
.1.3.6.1.4.1.885.2.3.1 · 1 row entry · 5 columns
The table listing for the Binary channel information
lmsBinaryChannelEntry entry .1.3.6.1.4.1.885.2.3.1.1
An entry containing information about a individual Binary channel.
Indexes
binaryChannelIndex
Column Syntax OID
binaryChannelIndex mandatory
The Binary channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.1.1.1
binaryChannelName mandatory
The Binary channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.1.1.2
binaryChannelStatus mandatory
The Binary channel state (CC=voltage applied)
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.1.1.3
binaryChannelAlarmStatus mandatory
The Binary channel alarm status
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.1.1.4
binaryChannelAlarmClass mandatory
The Binary channel alarm class
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.1.1.5

lmsAnalogChannelTable

table mandatory
.1.3.6.1.4.1.885.2.3.2 · 1 row entry · 9 columns
The table listing for the Analog channel information
lmsAnalogChannelEntry entry .1.3.6.1.4.1.885.2.3.2.1
An entry containing information about an individual Analog channel.
Indexes
analogChannelIndex
Column Syntax OID
analogChannelIndex mandatory
The Analog channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.2.1.1
analogChannelName mandatory
The Analog channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.2.1.2
analogChannelValue mandatory
The Analog channel reading
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.885.2.3.2.1.3
analogChannelUnits mandatory
The Analog channel reading units of measurement
OctetString
Constraints:
range: 0-4
.1.3.6.1.4.1.885.2.3.2.1.4
analogChannelLimit1 mandatory
The Analog channel limit number one value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.2.1.5
analogChannelLimit2 mandatory
The Analog channel limit number two value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.2.1.6
analogChannelLimit3 mandatory
The Analog channel limit number three value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.2.1.7
analogChannelLimit4 mandatory
The Analog channel limit number four value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.2.1.8
analogChannelAlarm mandatory
The Analog channel alarm status
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.3.2.1.9

lmsRelayChannelTable

table mandatory
.1.3.6.1.4.1.885.2.3.3 · 1 row entry · 5 columns
The table listing for the Relay channel information
lmsRelayChannelEntry entry .1.3.6.1.4.1.885.2.3.3.1
An entry containing information about an individual Relay channel.
Indexes
relayChannelIndex
Column Syntax OID
relayChannelIndex mandatory
The Relay channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.3.1.1
relayChannelName mandatory
The Relay channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.3.1.2
relayChannelStatus mandatory
The Relay channel status (On, Forced, Programmed)
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.3.1.3
relayChannelAlarmStatus mandatory
The Relay channel alarm status
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.3.1.4
relayChannelAlarmClass mandatory
The Relay channel alarm class
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.3.1.5

lmsLEDChannelTable

table mandatory
.1.3.6.1.4.1.885.2.3.4 · 1 row entry · 5 columns
The table listing for the LED channel information
lmsLEDChannelEntry entry .1.3.6.1.4.1.885.2.3.4.1
An entry containing information about an individual LED channel.
Indexes
ledChannelIndex
Column Syntax OID
ledChannelIndex mandatory
The LED channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.4.1.1
ledChannelName mandatory
The LED channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.4.1.2
ledChannelStatus mandatory
The LED channel status (On, Forced, Programmed)
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.4.1.3
ledChannelAlarmStatus mandatory
The LED channel alarm status
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.4.1.4
ledChannelAlarmClass mandatory
The LED channel alarm class
OctetStringr/w
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.4.1.5

lmsEnergyChannelTable

table mandatory
.1.3.6.1.4.1.885.2.3.5 · 1 row entry · 6 columns
The table listing for the Energy Management channel information
lmsEnergyChannelEntry entry .1.3.6.1.4.1.885.2.3.5.1
An entry containing information about an individual Energy Management channel.
Indexes
energyChannelIndex
Column Syntax OID
energyChannelIndex mandatory
The Energy Management channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.5.1.1
energyChannelName mandatory
The Energy Management channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.5.1.2
energyCapacity mandatory
The rated capacity of the rectifier associated with the Energy Management channel
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.5.1.3
energyShunt mandatory
The current load on the rectifier associated with the Energy Management channel
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.5.1.4
energyRFA mandatory
The current operational status of the rectifier associated with the Energy Management channel
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.3.5.1.5
energyTR mandatory
The current control status of the rectifier associated with the Energy Management channel
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.3.5.1.6
.1.3.6.1.4.1.885.2.3.6 · 1 row entry · 9 columns
The table entry for a Function channel Alarm
lmsFunctionChannelEntry entry .1.3.6.1.4.1.885.2.3.6.1
An entry containing the information returned by a Function channel Trap
Indexes
functionChannelIndex
Column Syntax OID
functionChannelIndex mandatory
The Function channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.3.6.1.1
functionChannelName mandatory
The Function channel name
OctetStringr/w
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.3.6.1.2
functionChannelValue mandatory
The Function channel reading
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.6.1.3
functionChannelUnits mandatory
The Function channel reading units of measurement
OctetString
Constraints:
range: 0-4
.1.3.6.1.4.1.885.2.3.6.1.4
functionChannelLimit1 mandatory
The Function channel limit number one value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.6.1.5
functionChannelLimit2 mandatory
The Function channel limit number two value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.6.1.6
functionChannelLimit3 mandatory
The Function channel limit number three value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.6.1.7
functionChannelLimit4 mandatory
The Function channel limit number four value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.3.6.1.8
functionChannelAlarm mandatory
The Function channel alarm status
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.3.6.1.9

lmsLedAlarmTable

table mandatory
.1.3.6.1.4.1.885.2.5.1 · 1 row entry · 7 columns
The table entry for a Led Alarm
lmsLedAlarmEntry entry .1.3.6.1.4.1.885.2.5.1.1
An entry containing the information returned by a LED Trap
Indexes
ledAlarmIndex
Column Syntax OID
ledAlarmIndex mandatory
The LED channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.1.1.1
ledAlarmName mandatory
The LED channel name
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.5.1.1.2
ledAlarmStatus mandatory
The LED channel status (On, Forced, Programmed)
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.1.1.3
ledAlarmAlarmStatus mandatory
The LED channel alarm status
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.1.1.4
ledAlarmClass mandatory
The LED channel alarm class
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.1.1.5
ledAlarmReportType mandatory
The LED channel alarm condition
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.1.1.6
ledAlarmDuration mandatory
The length of time the LED alarm has been active
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.1.1.7

lmsAnalogAlarmTable

table mandatory
.1.3.6.1.4.1.885.2.5.10 · 1 row entry · 10 columns
The table entry for an Analog channel Alarm
lmsAnalogAlarmEntry entry .1.3.6.1.4.1.885.2.5.10.1
An entry containing the information returned by an Analog channel Trap
Indexes
analogAlarmIndex
Column Syntax OID
analogAlarmIndex mandatory
The Analog channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.10.1.1
analogAlarmName mandatory
The Analog channel name
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.5.10.1.2
analogAlarmValue mandatory
The Analog channel reading
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.10.1.3
analogAlarmUnits mandatory
The Analog channel reading units of measurement
OctetString
Constraints:
range: 0-4
.1.3.6.1.4.1.885.2.5.10.1.4
analogAlarmLimitValue mandatory
The Analog channel limit value
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.10.1.5
analogAlarmLimitType mandatory
The Analog channel limit type
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.5.10.1.6
analogAlarmLimitName mandatory
The Analog channel limit name
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.10.1.7
analogAlarmLimitClass mandatory
The Analog channel limit condition
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.10.1.8
analogAlarmReportType mandatory
The Analog channel limit condition
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.10.1.9
analogAlarmDuration mandatory
The length of time the Analog limit has been active
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.10.1.10

lmsBinaryAlarmTable

table mandatory
.1.3.6.1.4.1.885.2.5.11 · 1 row entry · 7 columns
The table entry for a Binary Alarm
lmsBinaryAlarmEntry entry .1.3.6.1.4.1.885.2.5.11.1
An entry containing the information returned by a Binary Trap
Indexes
binaryAlarmIndex
Column Syntax OID
binaryAlarmIndex mandatory
The Binary channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.11.1.1
binaryAlarmName mandatory
The Binary channel name
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.5.11.1.2
binaryAlarmStatus mandatory
The Binary channel state (CC=voltage applied)
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.11.1.3
binaryAlarmAlarmStatus mandatory
The Binary channel alarm status
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.11.1.4
binaryAlarmClass mandatory
The Binary channel alarm class
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.11.1.5
binaryAlarmReportType mandatory
The Binary channel alarm condition
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.11.1.6
binaryAlarmDuration mandatory
The length of time the Binary alarm has been active
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.11.1.7

lmsFunctionAlarmTable

table mandatory
.1.3.6.1.4.1.885.2.5.12 · 1 row entry · 10 columns
The table entry for a Function channel Alarm
lmsFunctionAlarmEntry entry .1.3.6.1.4.1.885.2.5.12.1
An entry containing the information returned by a Function channel Trap
Indexes
functionAlarmIndex
Column Syntax OID
functionAlarmIndex mandatory
The Function channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.12.1.1
functionAlarmName mandatory
The Function channel name
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.5.12.1.2
functionAlarmValue mandatory
The Function channel reading
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.12.1.3
functionAlarmUnits mandatory
The Function channel reading units of measurement
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.12.1.4
functionAlarmLimitValue mandatory
The Function channel limit value
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.885.2.5.12.1.5
functionAlarmLimitType mandatory
The Function channel limit value
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.885.2.5.12.1.6
functionAlarmLimitName mandatory
The Function channel limit name
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.885.2.5.12.1.7
functionAlarmLimitClass mandatory
The Function channel alarm class
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.12.1.8
functionAlarmReportType mandatory
The Function channel limit condition
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.12.1.9
functionAlarmDuration mandatory
The length of time the Function limit has been active
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.12.1.10

lmsRelayAlarmTable

table mandatory
.1.3.6.1.4.1.885.2.5.13 · 1 row entry · 7 columns
The table entry for a Relay Alarm
lmsRelayAlarmEntry entry .1.3.6.1.4.1.885.2.5.13.1
An entry containing the information returned by a Relay Trap
Indexes
relayAlarmIndex
Column Syntax OID
relayAlarmIndex mandatory
The Relay channel number
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.13.1.1
relayAlarmName mandatory
The Relay channel name
OctetString
Constraints:
range: 0-30
.1.3.6.1.4.1.885.2.5.13.1.2
relayAlarmStatus mandatory
The Relay channel status (On, Forced, Programmed)
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.13.1.3
relayAlarmAlarmStatus mandatory
The Relay channel alarm status
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.13.1.4
relayAlarmClass mandatory
The Relay channel alarm class
OctetString
Constraints:
range: 0-5
.1.3.6.1.4.1.885.2.5.13.1.5
relayAlarmReportType mandatory
The Relay channel alarm condition
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.885.2.5.13.1.6
relayAlarmDuration mandatory
The length of time the Relay alarm has been active
OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.885.2.5.13.1.7