INFRATEC-RMS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
18
Rows
18
Columns
94

digitalInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.1 · 1 row entry · 5 columns
The digitalInTable contains all information about 
physical inputs Digital In 1-8.
digitalInEntry entry .1.3.6.1.4.1.1909.10.2.1.1
Each entry contains information for each input
Indexes
digitalInIndex
Column Syntax OID
digitalInIndex mandatory
Index of Digital Input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.1.1.1
digitalInDescr mandatory
Descriptive name of Digital Input
r/w .1.3.6.1.4.1.1909.10.2.1.1.2
digitalInState mandatory
Current state of Digital Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.1.1.3
digitalInLastChange mandatory
Timestamp of last change
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.1.1.4
digitalInChanges mandatory
How many times the input changed since system startup
RFC1155-SMICounter
Textual Convention: RFC1155-SMICounter Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.1.1.5

alertInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.2 · 1 row entry · 6 columns
The alertInTable contains all information about 
physical inputs Alert In 1-4.
alertInEntry entry .1.3.6.1.4.1.1909.10.2.2.1
Each entry contains the values for an alert input
Indexes
alertInIndex
Column Syntax OID
alertInIndex mandatory
Index of Alert Input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.2.1.1
alertInDescr mandatory
Descriptive name of Alert Input
r/w .1.3.6.1.4.1.1909.10.2.2.1.2
alertInState mandatory
Current state of Alert Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.2.1.3
alertInLastChange mandatory
Timestamp of last change
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.2.1.4
alertInChanges mandatory
How many times the input changed since system startup
RFC1155-SMICounter
Textual Convention: RFC1155-SMICounter Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.2.1.5
alertInReset mandatory
Reset an Alert In by writing 2 in here.
Most sensors use to store an alarm, which only can be
deleted by resetting the sensor respectively the whole
signalling line. This is achieved by powering-off this
signalling …
Enumerationr/w
Enumerated Values:
1default
2alertIn-reset
.1.3.6.1.4.1.1909.10.2.2.1.6

upsInTable

table mandatory
.1.3.6.1.4.1.1909.10.2.3 · 1 row entry · 5 columns
The upsInputTable contains all information about 
physical inputs UPS In 1-2.
upsInEntry entry .1.3.6.1.4.1.1909.10.2.3.1
Each entry contains the values for an UPS input
Indexes
upsInIndex
Column Syntax OID
upsInIndex mandatory
Index of UPS Input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.2.3.1.1
upsInDescr mandatory
Name of UPS Input
r/w .1.3.6.1.4.1.1909.10.2.3.1.2
upsInState mandatory
Current state of UPS Input
Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.2.3.1.3
upsInLastChange mandatory
Timestamp of last change
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.3.1.4
upsInChanges mandatory
How many times the input changed since system startup
RFC1155-SMICounter
Textual Convention: RFC1155-SMICounter Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.2.3.1.5

outputTable

table mandatory
.1.3.6.1.4.1.1909.10.3.1 · 1 row entry · 7 columns
The table used for describing the digital outputs
outputEntry entry .1.3.6.1.4.1.1909.10.3.1.1
Each entry contains the description of an digital output
Indexes
outputIndex
Column Syntax OID
outputIndex mandatory
Index of digital output
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.1.1.1
outputDescr mandatory
Descriptive Name of one digital output
r/w .1.3.6.1.4.1.1909.10.3.1.1.2
outputEffect mandatory
Determines the way the physical digital output is
influenced by one or more filter results.
For this the result of the logical output block can be
passed thru (thru) or inverted (invert).
Furthermore it is possible to…
Enumerationr/w
Enumerated Values:
1off
2on
3thru
4invert
.1.3.6.1.4.1.1909.10.3.1.1.3
outputLastChange mandatory
Timestamp of last change
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.3.1.1.4
outputChanges mandatory
How many times an output changed since system startup
RFC1155-SMICounter
Textual Convention: RFC1155-SMICounter Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.3.1.1.5
outputLogic mandatory
Each output can be controlled by a couple of filters, which
are combined in a boolean operation. The logic operation
(and/or) can be set up with this entry.
Enumerationr/w
Enumerated Values:
1and
2or
.1.3.6.1.4.1.1909.10.3.1.1.6
outputState mandatory
Current state of digital output
Enumeration
Enumerated Values:
1open
2short
.1.3.6.1.4.1.1909.10.3.1.1.7

outputLogicTable

table mandatory
.1.3.6.1.4.1.1909.10.3.2 · 1 row entry · 3 columns
The table used for describing the list of filters,
which effect an output.
outputLogicEntry entry .1.3.6.1.4.1.1909.10.3.2.1
Each entry contains the description of one logic and/or
element
Indexes
outputLogicOutputIndex outputLogicFilterIndex
Column Syntax OID
outputLogicOutputIndex mandatory
Index of the output
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.2.1.1
outputLogicFilterIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.3.2.1.2
outputLogicFilter mandatory
Determines, if this filter works on the logical and/or
element. Default is off.
Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.1909.10.3.2.1.3

tempTable

table mandatory
.1.3.6.1.4.1.1909.10.4.1 · 1 row entry · 3 columns
Table to hold the information about temperature inputs
tempEntry entry .1.3.6.1.4.1.1909.10.4.1.1
Each entry contains information about one temperature
input
Indexes
tempIndex
Column Syntax OID
tempIndex mandatory
Index of temperature input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.4.1.1.1
tempDescr mandatory
Descriptive name of temperature input
r/w .1.3.6.1.4.1.1909.10.4.1.1.2
tempValue mandatory
Current temperature in degree celsius.
If 655 no sensor is connected.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.4.1.1.3

humidTable

table mandatory
.1.3.6.1.4.1.1909.10.5.1 · 1 row entry · 3 columns
Table to hold the information about humidity inputs
humidEntry entry .1.3.6.1.4.1.1909.10.5.1.1
Each entry contains information about one humidity
input
Indexes
humidIndex
Column Syntax OID
humidIndex mandatory
Index of humidity input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.5.1.1.1
humidDescr mandatory
Descriptive name of the humidity input
r/w .1.3.6.1.4.1.1909.10.5.1.1.2
humidValue mandatory
Current humidity in percent rel. humidity.
If 255 no sensor is connected.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.5.1.1.3

mainsTable

table mandatory
.1.3.6.1.4.1.1909.10.6.1 · 1 row entry · 3 columns
Table to hold the information about the mains inputs
mainsEntry entry .1.3.6.1.4.1.1909.10.6.1.1
Each entry contains information about one mains input
Indexes
mainsIndex
Column Syntax OID
mainsIndex mandatory
Index of mains input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.6.1.1.1
mainsDescr mandatory
Descriptive name of the mains input
r/w .1.3.6.1.4.1.1909.10.6.1.1.2
mainsValue mandatory
Current voltage of mains input in volt.
If 13 or 255 no voltage is detected.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.6.1.1.3

filterTable

table mandatory
.1.3.6.1.4.1.1909.10.7.1 · 1 row entry · 11 columns
Table containing all information about the defined filters
filterEntry entry .1.3.6.1.4.1.1909.10.7.1.1
Each entry contains the description of one filter
Indexes
filterIndex
Column Syntax OID
filterIndex mandatory
Index of the filter entry
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.1.1.1
filterDescr mandatory
Descriptive name of filter
r/w .1.3.6.1.4.1.1909.10.7.1.1.2
filterResult mandatory
Current filter result, i.e. result of all 'or'ed inputs
- see block diagram
Enumeration
Enumerated Values:
1false
2true
.1.3.6.1.4.1.1909.10.7.1.1.3
filterEffect mandatory
Determines the way the filter is used for further operation
Can be switched off, passed thru or inverted.
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.1.1.4
filterTrap mandatory
Determines the way of trap notification to management
station(s) in case of filter events. Traps can be off,
sent once (when filter becomes true) or sent repeatedly
(as long as filter is true).
Enumerationr/w
Enumerated Values:
1no
2once
3repeat
.1.3.6.1.4.1.1909.10.7.1.1.5
filterLED mandatory
When set to yes(2) a filter event will be signalled
by the warning LED on front of RMS
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.1909.10.7.1.1.6
filterBuzzer mandatory
When set to yes(2) a filter event will be signalled
by the build-in buzzer
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.1909.10.7.1.1.7
filterMessagePriority mandatory
If set to priority-warning(2) or priority-critical(3),
a filter event will be logged in the message log an on
all defined log server(s) with the corresponding priority.
This priority has only informational character.
Enumerationr/w
Enumerated Values:
1no-message
2priority-warning
3priority-critical
.1.3.6.1.4.1.1909.10.7.1.1.8
filterConfirmation mandatory
If set to enabled(1), it is possible to confirme a true
filter. This can be done on front panel of RMS, via telnet
or via SNMP (see also variable filterConfirm).
Enumerationr/w
Enumerated Values:
1disabled
2enabled
.1.3.6.1.4.1.1909.10.7.1.1.9
filterReactivationTime mandatory
Time after which a confirmed filter will be reactivated
automatically
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.1.1.10
filterConfirm mandatory
A true filter can be confimed by writing confirmed(2)
in here (provided filter confirmation is enabled -
see variable filterConfirmation). By doing this the effect
of this filter will be suspended until the time speci…
Enumerationr/w
Enumerated Values:
1not-confirmed
2confirmed
.1.3.6.1.4.1.1909.10.7.1.1.11

filterDigitalInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.2 · 1 row entry · 3 columns
Table containing all information about the filter inputs 
Digital 1-8 of each filter
filterDigitalInEntry entry .1.3.6.1.4.1.1909.10.7.2.1
Each entry contains the description of one digital input
Indexes
filterDigitalInIndex filterDigitalInPort
Column Syntax OID
filterDigitalInIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.2.1.1
filterDigitalInPort mandatory
Index of the digital input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.2.1.2
filterDigitalInEffect mandatory
Determines the way the digital input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.2.1.3

filterAlertInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.3 · 1 row entry · 3 columns
Table containing all information about the filter inputs 
Alert In 1-4 of each filter
filterAlertInEntry entry .1.3.6.1.4.1.1909.10.7.3.1
Each entry contains information of one alert input
Indexes
filterAlertInIndex filterAlertInPort
Column Syntax OID
filterAlertInIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.3.1.1
filterAlertInPort mandatory
Index of the alert input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.3.1.2
filterAlertInEffect mandatory
Determines the way the alert input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.3.1.3

filterUPSInTable

table mandatory
.1.3.6.1.4.1.1909.10.7.4 · 1 row entry · 3 columns
Table containing all information about the filter inputs 
UPS In 1-2 of each filter
filterUPSInEntry entry .1.3.6.1.4.1.1909.10.7.4.1
Each entry contains the description of one ups input
Indexes
filterUPSInIndex filterUPSInPort
Column Syntax OID
filterUPSInIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.4.1.1
filterUPSInPort mandatory
Index of the UPS input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.4.1.2
filterUPSInEffect mandatory
Determines the way the UPS input effects the filter.
Can be switched off(1), inverted(3) or passed thru(2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.4.1.3

filterTempTable

table mandatory
.1.3.6.1.4.1.1909.10.7.5 · 1 row entry · 7 columns
Table containing information about temperature inputs of
each filter, i.e. thresholds and compare operations
filterTempEntry entry .1.3.6.1.4.1.1909.10.7.5.1
Each entry contains the description of one filter temp input
Indexes
filterTempIndex filterTempSensor
Column Syntax OID
filterTempIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.1
filterTempSensor mandatory
Index of the temp input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.2
filterTempEffect mandatory
Determines the way the result of temp input comparison
effects on the filter. Can be switched off(1), inverted (3)
or passed thru(3).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.5.1.3
filterTempAThres mandatory
Threshold of temp input part A
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.4
filterTempAMode mandatory
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.5.1.5
filterTempBThres mandatory
Threshold of temp input part B
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.5.1.6
filterTempBMode mandatory
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.5.1.7

filterHumidityTable

table mandatory
.1.3.6.1.4.1.1909.10.7.6 · 1 row entry · 7 columns
Table containing information about humidity inputs of
each filter, i.e. thresholds and compare operations
filterHumidityEntry entry .1.3.6.1.4.1.1909.10.7.6.1
Each entry contains the description of one filter
Indexes
filterHumidityIndex filterHumiditySensor
Column Syntax OID
filterHumidityIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.1
filterHumiditySensor mandatory
Index of the humidity input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.2
filterHumidityEffect mandatory
Determines the way the result of humidity input comparison
effects the filter. Can be switched off(1), inverted(3) or
passed thru(2), if not needed.
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.6.1.3
filterHumidityAThres mandatory
Threshold of humidity input part A
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.4
filterHumidityAMode mandatory
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.6.1.5
filterHumidityBThres mandatory
Threshold of humidity input part B
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.6.1.6
filterHumidityBMode mandatory
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.6.1.7

filterMainsTable

table mandatory
.1.3.6.1.4.1.1909.10.7.7 · 1 row entry · 7 columns
Table containing information about mains inputs of
each filter, i.e. thresholds and compare operations
filterMainsEntry entry .1.3.6.1.4.1.1909.10.7.7.1
Each entry contains the description of one filter
Indexes
filterMainsIndex filterMainsSensor
Column Syntax OID
filterMainsIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.1
filterMainsSensor mandatory
Index of the mains sensor
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.2
filterMainsEffect mandatory
Determines the way the result of mains input comparison
effects on the filter. Can be switched off(1), inverted(3)
or passed thru (2).
Enumerationr/w
Enumerated Values:
1off
2thru
3invert
.1.3.6.1.4.1.1909.10.7.7.1.3
filterMainsAThres mandatory
Threshold of mains input part B
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.4
filterMainsAMode mandatory
Determines the operating mode of comparison operation A.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.7.1.5
filterMainsBThres mandatory
Threshold of mains input part B
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.7.1.6
filterMainsBMode mandatory
Determines the operating mode of comparison operation B.
Can be set to greater(2) ' >', less(3) '<' or turned off(1),
if not needed
Enumerationr/w
Enumerated Values:
1off
2greater
3less
.1.3.6.1.4.1.1909.10.7.7.1.7

filterFeedbackTable

table mandatory
.1.3.6.1.4.1.1909.10.7.8 · 1 row entry · 7 columns
Table containing information about feedback inputs
filterFeedbackEntry entry .1.3.6.1.4.1.1909.10.7.8.1
Each entry contains the description of one filter
Indexes
filterFeedbackIndex filterFeedbackInput
Column Syntax OID
filterFeedbackIndex mandatory
Index of the filter
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.1
filterFeedbackInput mandatory
Index of the feedback input
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.2
filterFeedbackInFilter mandatory
Number of the filter which is connected
to this feedback input
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.3
filterFeedbackDelay mandatory
Delay time to wait until signal is forwarded
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.4
filterFeedbackPassCondition mandatory
Determines the way an incoming signal is forwarded to the
filter structure.
If set to thru(1), all incoming signals are straight
forwarded.
If set to conditional(2), an incoming signal only will be
forwarded, if aft…
Enumerationr/w
Enumerated Values:
1thru
2conditional
.1.3.6.1.4.1.1909.10.7.8.1.5
filterFeedbackHold mandatory
Determines the time the passed signal will be held up, after
the falling edge of the original trigger signal.
See timing diagram in manual for further details.
Integer32r/w
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.7.8.1.6
filterFeedbackEffect mandatory
Determines the way the result of feedback input effects
the filter. Can be switched off(1), inverted(3) or passed
thru (2).
Enumerationr/w
Enumerated Values:
1off
2on
3invert
.1.3.6.1.4.1.1909.10.7.8.1.7

messageTable

table mandatory
.1.3.6.1.4.1.1909.10.8.1 · 1 row entry · 6 columns
The message table contains the logged filter events
messageEntry entry .1.3.6.1.4.1.1909.10.8.1.1
Each entry contains information of one message
Indexes
messageIndex
Column Syntax OID
messageIndex mandatory
Index of message line
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.8.1.1.1
messageFilter mandatory
Number of filter which caused the message
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.8.1.1.2
messageFilterDescr mandatory
Name of the filter which caused the message
.1.3.6.1.4.1.1909.10.8.1.1.3
messageTime mandatory
Timestamp of event
RFC1155-SMITimeTicks
Textual Convention: RFC1155-SMITimeTicks Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.1909.10.8.1.1.4
messagePriority mandatory
Priority of the message. If set to no-priority(1) no message
will be logged. The Priority has only informational character
and doesn't affect the way it is handled
Enumeration
Enumerated Values:
1no-priority
2warning
3critical
.1.3.6.1.4.1.1909.10.8.1.1.5
messageAcknoledged mandatory
Displays, if event was acknoledged already. Has only
informational character for operator
Enumerationr/w
Enumerated Values:
1not-acknowledged
2acknowledged
.1.3.6.1.4.1.1909.10.8.1.1.6

userTable

table mandatory
.1.3.6.1.4.1.1909.10.9.1 · 1 row entry · 5 columns
Some infos about all registered users, e.g.
name, right and chipcard key (if reader installed)
userEntry entry .1.3.6.1.4.1.1909.10.9.1.1
Each entry contains information about one user
Indexes
userIndex
Column Syntax OID
userIndex mandatory
Index of user. Is dynamically filled from 1..n
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.1909.10.9.1.1.1
userName mandatory
name of one user
.1.3.6.1.4.1.1909.10.9.1.1.2
userRight mandatory
Access right of one user
Enumeration
Enumerated Values:
1readonly
2readwrite
.1.3.6.1.4.1.1909.10.9.1.1.3
userChipcardKey mandatory
Displays the chipcard key of this user -
only available, if optional chipcard reader installed.
.1.3.6.1.4.1.1909.10.9.1.1.4
userChipcardAccess mandatory
Holds the status of the last access try via
chipcard reader. In case of failure a rmsChipcardTrap
will be sent.
Enumeration
Enumerated Values:
1denied
2granted
.1.3.6.1.4.1.1909.10.9.1.1.5