GUDEADS-PDU818X-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
3
Rows
3
Columns
11
pdu818XTrapIPTable
table.1.3.6.1.4.1.28507.35.1.1.1.2
·
1 row entry
·
2 columns
list of all Trap receiver
an entry containing management
informations regarding the list of trap
receivers
informations regarding the list of trap
receivers
Indexes
pdu818XTrapIPIndex
| Column | Syntax | OID |
|---|---|---|
|
pdu818XTrapIPIndex
A unique value, greater than zero, for each receiver slot.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.28507.35.1.1.1.2.1.1 |
|
pdu818XTrapAddr
DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty string disables this slot. |
OctetStringr/w Constraints: range: 0-99 |
.1.3.6.1.4.1.28507.35.1.1.1.2.1.2 |
pdu818XPowerTable
table.1.3.6.1.4.1.28507.35.1.5.1.2
·
1 row entry
·
6 columns
All available Channel Interfaces.
An entry containing management information
applicable to a particular Power Channel.
applicable to a particular Power Channel.
Indexes
pdu818XPowerIndex
| Column | Syntax | OID |
|---|---|---|
|
pdu818XPowerIndex
Index of Power Channel entries
|
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.1 |
|
pdu818XChanStatus
0 = data not active, 1 = data valid
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.2 |
|
pdu818XEnergyActive
Total accumulated Active Energy of Power Channel.
|
WhSNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.3 |
|
pdu818XPowerActive
Active Power
|
WSNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.4 |
|
pdu818XCurrent
Actual Curent on Power Channel.
|
mASNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.5 |
|
pdu818XVoltage
Actual Voltage on Power Channel
|
VSNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.28507.35.1.5.1.2.1.6 |
pdu818XSensorTable
table.1.3.6.1.4.1.28507.35.1.6.1
·
1 row entry
·
3 columns
Indexes
pdu818XSensorIndex
| Column | Syntax | OID |
|---|---|---|
| pdu818XSensorIndex | Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.28507.35.1.6.1.1.1 |
|
pdu818XTempSensor
actual temperature, a value of -9999 indicates
that data is not available |
10th of degree CelsiusSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.28507.35.1.6.1.1.2 |
|
pdu818XHygroSensor
actual humidity, a value of -9999 indicates
that data is not available |
10th of percentage humiditySNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.28507.35.1.6.1.1.3 |