GEIST-IMD-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
12
Rows
12
Columns
109
pduMainTable
table.1.3.6.1.4.1.21239.5.2.3.1
·
1 row entry
·
12 columns
PDU general information
Entry in the pduMainTable table: each entry contains an index and other sensor details
Indexes
pduMainIndex
| Column | Syntax | OID |
|---|---|---|
|
pduMainIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.1.1.1 |
|
pduMainSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.1.1.2 |
|
pduMainName
Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.1.1.3 |
|
pduMainLabel
Label
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.1.1.4 |
|
pduMainAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.5 |
|
pduMeterType
Current meter type. 0 = Wye, 1 = Delta
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.21239.5.2.3.1.1.6 |
|
pduTotalName
Total Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.1.1.7 |
|
pduTotalLabel
Total Label
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.1.1.8 |
|
pduTotalRealPower
PDU Total Real Power
|
wattsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.9 |
|
pduTotalApparentPower
PDU Total Apparent Power
|
volt-ampsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.10 |
|
pduTotalPowerFactor
PDU Total Power Factor
|
%SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.11 |
|
pduTotalEnergy
PDU Total Accumulated Energy
|
watt-hoursSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.12 |
pduPhaseTable
table.1.3.6.1.4.1.21239.5.2.3.2
·
1 row entry
·
15 columns
PDU phases information
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
Indexes
pduPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
pduPhaseIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.1 |
|
pduPhaseName
PDU Phase Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.2.1.2 |
|
pduPhaseLabel
PDU Phase Label
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.2.1.3 |
|
pduPhaseVoltage
PDU Phase Voltage in tenths of a volt
|
decivolts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.4 |
|
pduPhaseVoltageMax
PDU Phase Voltage (Max) in tenths of a volt
|
decivolts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.5 |
|
pduPhaseVoltageMin
PDU Phase Voltage (Min) in tenths of a volt
|
decivolts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.6 |
|
pduPhaseVoltagePeak
PDU Phase Voltage (Peak) in tenths of a volt
|
decivoltsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.7 |
|
pduPhaseCurrent
PDU Phase Current reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.8 |
|
pduPhaseCurrentMax
PDU Phase Current (Max) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.9 |
|
pduPhaseCurrentMin
PDU Phase Current (Min) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.10 |
|
pduPhaseCurrentPeak
PDU Phase Current (Peak) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.11 |
|
pduPhaseRealPower
PDU Phase Real Power
|
wattsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.12 |
|
pduPhaseApparentPower
PDU Phase Apparent Power
|
volt-ampsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.13 |
|
pduPhasePowerFactor
PDU Phase Power Factor
|
%SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.14 |
|
pduPhaseEnergy
PDU Phase Accumulated Energy
|
watt-hoursSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.2.1.15 |
pduBreakerTable
table.1.3.6.1.4.1.21239.5.2.3.3
·
1 row entry
·
7 columns
PDU information
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
Indexes
pduBreakerIndex
| Column | Syntax | OID |
|---|---|---|
|
pduBreakerIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.3.1.1 |
|
pduBreakerName
PDU Breaker Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.3.1.2 |
|
pduBreakerLabel
PDU Breaker Label
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.3.1.3 |
|
pduBreakerCurrent
PDU Breaker Current reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.3.1.4 |
|
pduBreakerCurrentMax
PDU Breaker Current (Max) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.3.1.5 |
|
pduBreakerCurrentMin
PDU Breaker Current (Min) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.3.1.6 |
|
pduBreakerCurrentPeak
PDU Breaker Current (Peak) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.3.1.7 |
pduLineTable
table.1.3.6.1.4.1.21239.5.2.3.4
·
1 row entry
·
7 columns
PDU line current information
Entry in the pduLineTable table: each entry contains an index and other sensor details
Indexes
pduLineIndex
| Column | Syntax | OID |
|---|---|---|
|
pduLineIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.4.1.1 |
|
pduLineName
PDU Line Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.4.1.2 |
|
pduLineLabel
PDU Line Label
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.3.4.1.3 |
|
pduLineCurrent
PDU Line Current reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.4.1.4 |
|
pduLineCurrentMax
PDU Line Current (Max) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.4.1.5 |
|
pduLineCurrentMin
PDU Line Current (Min) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.4.1.6 |
|
pduLineCurrentPeak
PDU Line Current (Peak) reading in hundreths of an amp
|
centiamps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.4.1.7 |
tempSensorTable
table.1.3.6.1.4.1.21239.5.2.4
·
1 row entry
·
5 columns
Remote Temperature Sensor
Entry in the tempSensorTable table: each entry contains an index and other sensor details
Indexes
tempSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
tempSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.4.1.1 |
|
tempSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.4.1.2 |
|
tempSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.4.1.3 |
|
tempSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.4.1.4 |
|
tempSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.4.1.5 |
airFlowSensorTable
table.1.3.6.1.4.1.21239.5.2.5
·
1 row entry
·
8 columns
Remote Airflow, Humidity, Temperature and Dewpoint Sensor
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
Indexes
airFlowSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
airFlowSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.5.1.1 |
|
airFlowSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.5.1.2 |
|
airFlowSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.5.1.3 |
|
airFlowSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.5.1.4 |
|
airFlowSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.5.1.5 |
|
airFlowSensorFlow
AFHT3 Airflow reading
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.5.1.6 |
|
airFlowSensorHumidity
AFHT3 Humidity reading
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.5.1.7 |
|
airFlowSensorDewPoint
Current reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.5.1.8 |
dewPointSensorTable
table.1.3.6.1.4.1.21239.5.2.6
·
1 row entry
·
7 columns
Remote Dew Point sensor
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
Indexes
dewPointSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
dewPointSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.6.1.1 |
|
dewPointSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.6.1.2 |
|
dewPointSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.6.1.3 |
|
dewPointSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.6.1.4 |
|
dewPointSensorTemp
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.6.1.5 |
|
dewPointSensorHumidity
Humidity reading
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.6.1.6 |
|
dewPointSensorDewPoint
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.6.1.7 |
ccatSensorTable
table.1.3.6.1.4.1.21239.5.2.7
·
1 row entry
·
7 columns
Remote CCAT sensor
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
Indexes
ccatSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
ccatSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.7.1.1 |
|
ccatSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.7.1.2 |
|
ccatSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.7.1.3 |
|
ccatSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.7.1.4 |
|
ccatSensorValue
CCAT sensor reading
|
Integer32 Constraints: range: -100-5000 |
.1.3.6.1.4.1.21239.5.2.7.1.5 |
|
ccatSensorType
CCAT sensor type
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.7.1.6 |
|
ccatSensorDescription
CCAT sensor value description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.7.1.7 |
t3hdSensorTable
table.1.3.6.1.4.1.21239.5.2.8
·
1 row entry
·
14 columns
Remote Temperature x 3, Humidity and Dewpoint Sensor
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
Indexes
t3hdSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
t3hdSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.8.1.1 |
|
t3hdSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.8.1.2 |
|
t3hdSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.8.1.3 |
|
t3hdSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.4 |
|
t3hdSensorIntName
T3HD Sensor Internal Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.8.1.5 |
|
t3hdSensorIntTemp
Current reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.8.1.6 |
|
t3hdSensorIntHumidity
T3HD Sensor Internal Humidity
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.8.1.7 |
|
t3hdSensorIntDewPoint
Current reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.8.1.8 |
|
t3hdSensorExtAAvail
T3HD External A status: 0 = Unavailable, 1 = Available
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.9 |
|
t3hdSensorExtAName
T3HD External A Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.8.1.10 |
|
t3hdSensorExtATemp
Current reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.8.1.11 |
|
t3hdSensorExtBAvail
T3HD External B status: 0 = Unavailable, 1 = Available
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.12 |
|
t3hdSensorExtBName
T3HD External B Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.8.1.13 |
|
t3hdSensorExtBTemp
Current reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.8.1.14 |
thdSensorTable
table.1.3.6.1.4.1.21239.5.2.9
·
1 row entry
·
7 columns
Remote Temperature, Humidity and Dewpoint Sensor
Entry in the thdSensorTable table: each entry contains an index and other sensor details
Indexes
thdSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
thdSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.9.1.1 |
|
thdSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.9.1.2 |
|
thdSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.9.1.3 |
|
thdSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.9.1.4 |
|
thdSensorTemp
Current reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.9.1.5 |
|
thdSensorHumidity
THD Sensor Humidity
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.9.1.6 |
|
thdSensorDewPoint
Current reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo
|
0.1 DegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.9.1.7 |
rpmSensorTable
table.1.3.6.1.4.1.21239.5.2.10
·
1 row entry
·
15 columns
Remote Power Manager Sensor
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
Indexes
rpmSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
rpmSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.10.1.1 |
|
rpmSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.10.1.2 |
|
rpmSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.10.1.3 |
|
rpmSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.4 |
|
rpmSensorEnergy
RPM Sensor Accumulated Energy
|
kWhSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.5 |
|
rpmSensorVoltage
RPM Sensor Voltage
|
Volts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.6 |
|
rpmSensorVoltageMax
RPM Sensor Voltage (Max)
|
Volts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.7 |
|
rpmSensorVoltageMin
RPM Sensor Voltage (Min)
|
Volts (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.8 |
|
rpmSensorVoltagePeak
RPM Sensor Voltage (Peak)
|
VoltsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.9 |
|
rpmSensorCurrent
RPM Sensor Current reading in deciAmps
|
0.1 Amps (rms)SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.10 |
|
rpmSensorRealPower
RPM Sensor Real Power
|
WattsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.11 |
|
rpmSensorApparentPower
RPM Sensor Apparent Power
|
Volt-AmpsSNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.12 |
|
rpmSensorPowerFactor
RPM Sensor Power Factor
|
%SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.13 |
|
rpmSensorOutlet1
RPM Sensor Outlet 1 State: 0 = off, 1 = on
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.14 |
|
rpmSensorOutlet2
RPM Sensor Outlet 2 State: 0 = off, 1 = on
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.15 |
a2dSensorTable
table.1.3.6.1.4.1.21239.5.2.11
·
1 row entry
·
5 columns
Analog Measurement Sensor (Voltage, Current, or Dry Contact)
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Indexes
a2dSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
a2dSensorIndex
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.11.1.1 |
|
a2dSensorSerial
Serial Number
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.11.1.2 |
|
a2dSensorName
Friendly Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.21239.5.2.11.1.3 |
|
a2dSensorAvail
Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable
|
SNMPv2-SMIGauge32 Textual Convention: SNMPv2-SMIGauge32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.11.1.4 |
|
a2dSensorValue
Current analog measurement reading within either a user defined or preset range depending on device mode.
|
Integer32 Constraints: range: -1000000-1000000 |
.1.3.6.1.4.1.21239.5.2.11.1.5 |