ENVIROMUX16D Table View
Table-centric layout grouping table, row, and column objects.
Tables
20
Rows
20
Columns
167
intSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.3.1
·
1 row entry
·
13 columns
Table of internal Sensors entries
An internal sensor entry
Indexes
intSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
intSensorIndex
The index of the internal sensor entry 1..3
|
Integer32 Constraints: range: 0-1range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.1 |
|
intSensorType
Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.3.1.1.2 |
|
intSensorDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.3 |
|
intSensorGroupNb
Sensor's Group
|
Integer32 Constraints: range: 100-25500range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.4 |
|
intSensorGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.5 |
|
intSensorValue
The value of the internal sensor reading. For temperature, voltage, current or low voltage, it is presented in tenths of degrees/volts
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.3.1.1.6 |
|
intSensorUnit
The measuremnet unit for this sensor in numeric format. It is important only for temperature
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.7 |
|
intSensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.8 |
|
intSensorStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.3.1.1.9 |
|
intSensorMinThreshold
The value of the sensor lower threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.10 |
|
intSensorMaxThreshold
The value of the sensor upper threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.11 |
|
intSensorMinWarnThreshold
The value of the sensor lower warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.12 |
|
intSensorMaxWarnThreshold
The value of the sensor upper warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.3.1.1.13 |
auxSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.4.1
·
1 row entry
·
14 columns
Table of auxiliary sensors entries
An auxiliary sensor entry
Indexes
auxSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
auxSensorIndex
The index of the auxiliary sensor entry 1..4
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.1 |
|
auxSensorType
Auxiliary Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.4.1.1.2 |
|
auxSensorDescription
Auxiliary Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.3 |
|
auxSensorConnector
Connector where the auxiliary sensor is attached
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.4 |
|
auxSensorGroupNb
Auxiliary Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.5 |
|
auxSensorGroup
Auxiliary Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.6 |
|
auxSensorValue
The value of the auxiliary sensor reading. It is presented in tenths of degrees
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.7 |
|
auxSensorUnit
The measuremnet unit for this sensor. Can be Celsius or Fahrenheit
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.8 |
|
auxSensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.9 |
|
auxSensorStatus
The status of the auxiliary sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.4.1.1.10 |
|
auxSensorMinThreshold
The value of the sensor lower threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.11 |
|
auxSensorMaxThreshold
The value of the sensor upper threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.12 |
|
auxSensorMinWarnThreshold
The value of the sensor lower warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.13 |
|
auxSensorMaxWarnThreshold
The value of the sensor upper warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.4.1.1.14 |
extSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.5.1
·
1 row entry
·
14 columns
Table of external Sensors entries
An external sensor entry
Indexes
extSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
extSensorIndex
The index of the external sensor entry 1..32
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.1 |
|
extSensorType
Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.5.1.1.2 |
|
extSensorDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.3 |
|
extSensorConnector
Connector where the sensor is attached
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.4 |
|
extSensorGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.5 |
|
extSensorGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.6 |
|
extSensorValue
The value of the external sensor reading. For temperature, voltage, current or low voltage, it is presented in tenths of degrees/volts
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.5.1.1.7 |
|
extSensorUnit
The measuremnet unit for this sensor. It is important only for temperature
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.8 |
|
extSensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.9 |
|
extSensorStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.5.1.1.10 |
|
extSensorMinThreshold
The value of the sensor lower threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.11 |
|
extSensorMaxThreshold
The value of the sensor upper threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.12 |
|
extSensorMinWarnThreshold
The value of the sensor lower warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.13 |
|
extSensorMaxWarnThreshold
The value of the sensor upper warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.1.1.14 |
extSensorAclmTable
table.1.3.6.1.4.1.3699.1.1.11.1.5.2
·
1 row entry
·
10 columns
Table of external Sensors entries
An external sensor entry
Indexes
extSensorAclmIndex
| Column | Syntax | OID |
|---|---|---|
|
extSensorAclmIndex
Index of the sensor in the list
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.1 |
|
extSensorPeakValue
The peak value of the ACLM sensor presensted in tenths of volts/watts
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.2 |
|
extSensorFrequency
Frequency measured by the ACLM sensor presensted in tenths of Hz
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.3 |
|
extSensorCurrent
Current measured by the ACLM sensor presensted in tenths of A(mpers)
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.4 |
|
extSensorSpikes
Number of spikes read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.5 |
|
extSensorSwells
Number of swells read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.6 |
|
extSensorSags
Number of sags read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.7 |
|
extSensorRelay
Relay status
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.5.2.1.8 |
|
extSensorAclmMinThreshold
Minimum Threshold
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.9 |
|
extSensorAclmMaxThreshold
Maximum Threshold
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.5.2.1.10 |
digInputTable
table.1.3.6.1.4.1.3699.1.1.11.1.6.1
·
1 row entry
·
9 columns
Table of external Sensors entries
A dry contact entry
Indexes
digInputIndex
| Column | Syntax | OID |
|---|---|---|
|
digInputIndex
The index of the external sensor entry 1..4
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.6.1.1.1 |
|
digInputType
Sensor Type. Only dry contact type will be used
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.6.1.1.2 |
|
digInputDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.6.1.1.3 |
|
digInputConnector
Connector where the sensor is attached
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.6.1.1.4 |
|
digInputGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.6.1.1.5 |
|
digInputGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.6.1.1.6 |
|
digInputValue
The value of the dry contact reading.
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.6.1.1.7 |
|
digInputStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.6.1.1.8 |
|
digInputNormalValue
The normal value of the dry contact reading
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.6.1.1.9 |
ipDeviceTable
table.1.3.6.1.4.1.3699.1.1.11.1.7.1
·
1 row entry
·
9 columns
Table of IP Devices entries
An IP Device entry
Indexes
ipDeviceIndex
| Column | Syntax | OID |
|---|---|---|
|
ipDeviceIndex
The index of the IP Device entry 1..8
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.1 |
|
ipDeviceAddress
IP Device URL
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.2 |
|
ipDeviceDescription
IP Device Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.3 |
|
ipDeviceGroupNb
Index of the group the IP Device belongs to
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.4 |
|
ipDeviceGroup
Name of the group the IP Device belongs to
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.5 |
|
ipDeviceTimeout
IP Device ping timeout (in seconds)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.6 |
|
ipDeviceRetries
Number of ping retries to the IP device, until responding
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.7.1.1.7 |
|
ipDeviceValue
Responding status
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.7.1.1.8 |
|
ipDeviceStatus
Alarm status of the IP Device
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.7.1.1.9 |
outRelayTable
table.1.3.6.1.4.1.3699.1.1.11.1.8.1
·
1 row entry
·
3 columns
Table of output relays
An output relay entry
Indexes
outRelayIndex
| Column | Syntax | OID |
|---|---|---|
|
outRelayIndex
The index of relay
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.8.1.1.1 |
|
outRelayDescription
Desciption/name associated with the output relay
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.8.1.1.2 |
|
outRelayStatus
The status of the output relay
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.8.1.1.3 |
pwrSupplyTable
table.1.3.6.1.4.1.3699.1.1.11.1.9.1
·
1 row entry
·
2 columns
Table of power supplies
An output relay entry
Indexes
pwrSupplyIndex
| Column | Syntax | OID |
|---|---|---|
|
pwrSupplyIndex
The index of power supply
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.9.1.1.1 |
|
pwrSupplyStatus
The status of the output relay
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.9.1.1.2 |
eventTable
table.1.3.6.1.4.1.3699.1.1.11.1.10.1
·
1 row entry
·
4 columns
Table of events
An event entry
Indexes
eventIndex
| Column | Syntax | OID |
|---|---|---|
|
eventIndex
The index of the event
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.10.1.1.1 |
|
eventDescription
Desciption/name associated with the event
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.10.1.1.2 |
|
eventStatus
The status of the event
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.10.1.1.3 |
|
eventValue
The value of the sensor event reading. For temperature, voltage, current or low voltage, it is presented in tenths of degrees/volts
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.10.1.1.4 |
smartAlertTable
table.1.3.6.1.4.1.3699.1.1.11.1.11.1
·
1 row entry
·
3 columns
Table of smartAlerts
A smartAlert entry
Indexes
smartAlertIndex
| Column | Syntax | OID |
|---|---|---|
|
smartAlertIndex
The index of the smartAlert
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.11.1.1.1 |
|
smartAlertDescription
Desciption/name associated with the smartAlert
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.11.1.1.2 |
|
smartAlertStatus
The status of the smartAlert
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.11.1.1.3 |
remoteInputTable
table.1.3.6.1.4.1.3699.1.1.11.1.12.1
·
1 row entry
·
9 columns
Table of Remote Inputs entries
A remote input entry
Indexes
remoteInputIndex
| Column | Syntax | OID |
|---|---|---|
|
remoteInputIndex
The index of the remote input entry 1..256
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.12.1.1.1 |
|
remoteInputType
Sensor Type. Remote input contact type will be used
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.12.1.1.2 |
|
remoteInputDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.12.1.1.3 |
|
remoteInputConnector
Connector where the sensor is attached
|
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.3699.1.1.11.1.12.1.1.4 |
|
remoteInputGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.12.1.1.5 |
|
remoteInputGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.12.1.1.6 |
|
remoteInputValue
The value of the remote input reading.
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.12.1.1.7 |
|
remoteInputStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.12.1.1.8 |
|
remoteInputNormalValue
The normal value of the remote input reading
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.12.1.1.9 |
remoteRelayTable
table.1.3.6.1.4.1.3699.1.1.11.1.13.1
·
1 row entry
·
3 columns
Table of remote relays
An output relay entry
Indexes
remoteRelayIndex
| Column | Syntax | OID |
|---|---|---|
|
remoteRelayIndex
The index of relay
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.13.1.1.1 |
|
remoteRelayDescription
Desciption/name associated with the remote relay
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.13.1.1.2 |
|
remoteRelayStatus
The status of the remote relay
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.13.1.1.3 |
smokeDetectorTable
table.1.3.6.1.4.1.3699.1.1.11.1.14.1
·
1 row entry
·
5 columns
Table of Smoke Detectors entries
A smoke detector entry
Indexes
smokeDetectorIndex
| Column | Syntax | OID |
|---|---|---|
|
smokeDetectorIndex
The index of the smoke detector entry 1..8
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.14.1.1.1 |
|
smokeDetectorDescription
Smoke Detector Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.14.1.1.2 |
|
smokeDetectorGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.14.1.1.3 |
|
smokeDetectorValue
The value of the smoke detector reading.
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.14.1.1.4 |
|
smokeDetectorStatus
The status of the smoke detector
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.14.1.1.5 |
tacSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.15.1
·
1 row entry
·
14 columns
Table of Tac sensors entries
A tac sensor entry
Indexes
tacSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
tacSensorIndex
The index of the Tac sensor entry 1..4
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.1 |
|
tacSensorType
Tac Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.15.1.1.2 |
|
tacSensorDescription
Tac Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.3 |
|
tacSensorConnector
Connector where the Tac sensor is attached
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.4 |
|
tacSensorGroupNb
Tac Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.5 |
|
tacSensorGroup
Tac Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.6 |
|
tacSensorValue
The value of the Tac sensor reading.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.7 |
|
tacSensorUnit
The measuremnet unit for this sensor. Can be Celsius or Fahrenheit
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.8 |
|
tacSensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.9 |
|
tacSensorStatus
The status of the Tac sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.15.1.1.10 |
|
tacSensorMinThreshold
The value of the sensor lower threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.11 |
|
tacSensorMaxThreshold
The value of the sensor upper threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.12 |
|
tacSensorMinWarnThreshold
The value of the sensor lower warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.13 |
|
tacSensorMaxWarnThreshold
The value of the sensor upper warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.15.1.1.14 |
ipSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.16.1
·
1 row entry
·
13 columns
Table of IP Sensors entries
An IP sensor entry
Indexes
ipSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
ipSensorIndex
The index of the external sensor entry 1..88
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.1 |
|
ipSensorMicroUnit
The index of the Enviromux-Micro unit the sensor belongs to (1..8)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.2 |
|
ipSensorType
Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.16.1.1.3 |
|
ipSensorDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.4 |
|
ipSensorConnector
Connector where the sensor is attached on the Enviromux-Micro unit, -1 if internal
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.5 |
|
ipSensorGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.6 |
|
ipSensorGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.7 |
|
ipSensorValue
The value of the external sensor reading. For temperature, voltage, current or low voltage, it is presented in tenths of degrees/volts
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.16.1.1.8 |
|
ipSensorUnit
The measuremnet unit for this sensor. It is important only for temperature
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.9 |
|
ipSensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.10 |
|
ipSensorStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.16.1.1.11 |
|
ipSensorMinThreshold
The value of the sensor lower threshold
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.12 |
|
ipSensorMaxThreshold
The value of the sensor upper threshold
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.16.1.1.13 |
aux2SensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.17.1
·
1 row entry
·
14 columns
Table of auxiliary sensors entries
An auxiliary 2 sensor entry
Indexes
aux2SensorIndex
| Column | Syntax | OID |
|---|---|---|
|
aux2SensorIndex
The index of the auxiliary 2 sensor entry 1..96
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.1 |
|
aux2SensorType
Auxiliary 2 Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.17.1.1.2 |
|
aux2SensorDescription
Auxiliary 2 Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.3 |
|
aux2SensorConnector
Connector where the auxiliary 2 sensor is attached
|
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.4 |
|
aux2SensorGroupNb
Auxiliary 2 Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.5 |
|
aux2SensorGroup
Auxiliary 2 Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.6 |
|
aux2SensorValue
The value of the auxiliary 2 sensor reading. It is presented in tenths of degrees
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.7 |
|
aux2SensorUnit
The measuremnet unit for this sensor. Can be Celsius or Fahrenheit
|
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.8 |
|
aux2SensorUnitName
The measuremnet unit for this sensor in readable format
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.9 |
|
aux2SensorStatus
The status of the auxiliary 2 sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.17.1.1.10 |
|
aux2SensorMinThreshold
The value of the sensor lower threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.11 |
|
aux2SensorMaxThreshold
The value of the sensor upper threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.12 |
|
aux2SensorMinWarnThreshold
The value of the sensor lower warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.13 |
|
aux2SensorMaxWarnThreshold
The value of the sensor upper warning threshold
|
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.17.1.1.14 |
msgRegistersTable
table.1.3.6.1.4.1.3699.1.1.11.1.18.1
·
1 row entry
·
3 columns
Table of message registers
An input message entry
Indexes
msgRegistersIndex
| Column | Syntax | OID |
|---|---|---|
|
msgRegistersIndex
The index of message register
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.3699.1.1.11.1.18.1.1.1 |
|
msgRegistersDescription
The content of the message
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.18.1.1.2 |
|
msgRegistersStatus
The status of the message register
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.18.1.1.3 |
sirenBeaconsTable
table.1.3.6.1.4.1.3699.1.1.11.1.19.1
·
1 row entry
·
2 columns
Table of sirenBeacons registers
An input message entry
Indexes
sirenBeaconsIndex
| Column | Syntax | OID |
|---|---|---|
|
sirenBeaconsIndex
The index of sirenBeacons register
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.3699.1.1.11.1.19.1.1.1 |
|
sirenBeaconsStatus
The status of the sirenBeacons register
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.19.1.1.2 |
allExternalSensorTable
table.1.3.6.1.4.1.3699.1.1.11.1.21.1
·
1 row entry
·
13 columns
Table of external Sensors entries
An external sensor entry
Indexes
allExternalSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
allExternalSensorIndex
The index of external Sensor entry 1..750
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.1 |
|
allExternalSensorUID
Sensor UID
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.2 |
|
allExternalSensorType
Sensor Type
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.21.1.1.3 |
|
allExternalSensorDescription
Sensor Description
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.4 |
|
allExternalSensorConnector
Connector where the sensor is attached
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.5 |
|
allExternalSensorGroupNb
Sensor's Group
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.6 |
|
allExternalSensorGroup
Sensor's Group Name
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.7 |
|
allExternalSensorValue
Value of external sensor with unit separated by space. Value is writable if sensor is Remote Output relay
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.8 |
|
allExternalSensorStatus
The status of the sensor
|
Enumerationr/w | .1.3.6.1.4.1.3699.1.1.11.1.21.1.1.9 |
|
allExternalSensorMinThreshold
The value of the sensor lower threshold with unit
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.10 |
|
allExternalSensorMaxThreshold
The value of the sensor upper threshold with unit
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.11 |
|
allExternalSensorMinWarnThreshold
The value of the sensor lower warning threshold with unit
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.12 |
|
allExternalSensorMaxWarnThreshold
The value of the sensor upper warning threshold with unit
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.1.1.13 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2
·
1 row entry
·
10 columns
Table of external Sensors entries
An external sensor entry
Indexes
allExternalSensorAclmIndex
| Column | Syntax | OID |
|---|---|---|
|
allExternalSensorAclmIndex
Index of the sensor in the list
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.1 |
|
allExternalSensorPeakValue
The peak value of the ACLM sensor and unit separated by space
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.2 |
|
allExternalSensorFrequency
Frequency measured by the ACLM sensor and unit separated by space
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.3 |
|
allExternalSensorCurrent
Current measured by the ACLM sensor and unit separated by space
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.4 |
|
allExternalSensorSpikes
Number of spikes read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.5 |
|
allExternalSensorSwells
Number of swells read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.6 |
|
allExternalSensorSags
Number of sags read
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.7 |
|
allExternalSensorRelay
Relay status
|
Enumeration | .1.3.6.1.4.1.3699.1.1.11.1.21.2.1.8 |
|
allExternalSensorAclmMinThreshold
Minimum Threshold
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.9 |
|
allExternalSensorAclmMaxThreshold
Maximum Threshold
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.3699.1.1.11.1.21.2.1.10 |