ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
9
Rows
9
Columns
62
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2 · 1 row entry · 17 columns
Table containing information about the individual
battery manager being monitored.
battManDeviceEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1
List of information about each battery manager being monitored.
Indexes
battManDeviceAddress
Column Syntax OID
battManDeviceAddress
Index into the battManDeviceTable.Address of this device on the RS-485 path
Integer32
Constraints:
range: 17-127
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.1
battManProtocolVersion
Version of the protocol implemented in the monitored equipment.
Integer32
Constraints:
range: 1-254
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.2
battManSoftwareVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the monitored device system software
version. Any printable ASCII characters can be included in this field.
NULL (0x00) c…
OctetString
Constraints:
range: 8-8
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.3
battManDeviceId
The content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information.
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.4
battManVendorIdentity
The content of this field is vendor specific. The intent is to provide
a text representation of the battery manager vendor identity. Any
printable ASCII characters can be included in this field. NULL (0x00)
characters …
OctetString
Constraints:
range: 10-10
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.5
battManStringVoltage
Current string voltage configuration.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.6
battManBatteries
Current number of batteries.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.7
battManBatteryStrings
Current number of strings.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.8
battManBatteriesPerStrings
Current number of batteries per string.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.9
battManVoltageSupport
Defines if the voltage measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.10
battManTemperatureSupport
Defines if the temperature measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.11
battManImpedanceSupport
Defines if the impedance measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.12
battManEqualPercentSupport
Defines if the equlization percent measurement is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.13
battManBatteryStatusSupport
Defines if the battery status monitoring is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.14
battManDiagSupport
Defines if the battery manager modules diagnostics monitoring is supported
1 = No support.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.15
battManEnvDataSupport
Defines if the battery manager environment data is supported
1 = No support.
2 = The Environment Data table is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.16
battManManualMeasurementSupport
Defines if the battery manager manualy triggered measurement is supported
1 = No support.
2 = The Manual Measurement table is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.17
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3 · 1 row entry · 4 columns
Table containing strings data
battManStringEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1
List of information about each string. Indexed by string number
Indexes
battManStringDeviceAddress battManString
Column Syntax OID
battManStringDeviceAddress
Index into the battManStringTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.1
battManString
Index into the battManStringTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.2
battManStringBatteries
number of batteries.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.3
battManStringTotalVoltage
Scaled representation of an individual string total voltage in 1/100 Volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4 · 1 row entry · 12 columns
Table containing batteries data
battManBatteryEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1
List of information about each battery. Indexed by battery number
Indexes
battManBatteryDeviceAddress battManBatteryStringID battManBattery
Column Syntax OID
battManBatteryDeviceAddress
Index into the battManBatteryTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.1
battManBattery
Index into the battManBatteryTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.2
battManBatteryStringID
id of the string that this battery belongs to.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.3
battManBatteryVersion
battery module version.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.4
battManBatteryHwVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system hardware version. Any printable
ASCII characters can be included in this field. NULL (0x00) characters …
OctetString .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.5
battManBatterySwVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system software version. Any printable
ASCII characters can be included in this field. NULL (0x00) characters …
OctetString .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.6
battManBatteryVoltage
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.7
battManBatteryTemperature
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.8
battManBatteryImpedance
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.9
battManBatteryEqualizationPercent
Reports the battery equalization percent with a range of 0 to 100%.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.10
battManBatteryStatus
Reports the status of the battery

1. ok
2. alarm

This item requires an entry in the discrete properties MIB.
Enumeration
Enumerated Values:
1ok
2alarm
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.11
battManBatteryDatasetID
The DatasetID of the measurement done for this battery.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.12
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5 · 1 row entry · 4 columns
Table containing battery diagnostic data
battManBatteryDiagEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1
List of diagnostic information about each battery. Indexed by battery number
Indexes
battManBatteryDiagDeviceAddress battManBatteryDiagModuleID
Column Syntax OID
battManBatteryDiagDeviceAddress
Index into the battManBatteryDiagTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.1
battManBatteryDiagModuleID
Index into the battManBatteryDiagTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.2
battManBatteryDiagPageNumber
the data page number.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.3
battManBatteryDiagPageData
The content of this field is vendor specific. The intent is to provide
a text representation of the particular information of the identified module.
when an invalid page number is requested, this field will be returned…
OctetString
Constraints:
range: 20-20
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6 · 1 row entry · 4 columns
Table containing battery managers control settings.
battManControlEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1
List of controls about each battery manager. Indexed by battManControlDeviceAddress
Indexes
battManControlDeviceAddress
Column Syntax OID
battManControlDeviceAddress
Index into the battManControlStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.1
battManControlEqualizationSetting
Represents the equalization status.

1 means equalization activated
2 means equalization deactivated
Enumerationr/w
Enumerated Values:
1activated
2deactivated
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.2
battManControlAutoInterval
Represents the period (in hours) used to take automated measurements
The value 0 deactivates the automated measurements
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.3
battManControlSensorsRestart
Restart the sensors. Reading the object returns false(2), and has no effect on the unit.
Enumerationr/w
Enumerated Values:
1true
2false
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7 · 1 row entry · 2 columns
Table containing battery managers status data.
battManStatusEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1
List of status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManStatusDeviceAddress
Column Syntax OID
battManStatusDeviceAddress
Index into the battManStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.1
battManStatusTimeToMeasurement
Indicates the remaining time (in seconds) before next automated measurement.
If the automated measurement is deactivated, then the return value is always 0.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.2
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8 · 1 row entry · 4 columns
Table containing battery manager's Environmental Status data.
battManEnvStatusEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1
List of Environmental Status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManEnvStatusDeviceAddress
Column Syntax OID
battManEnvStatusDeviceAddress
Index into the battManEnvStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.1
battManEnvStatusTemperature
Scaled representation of battery manager temperature in degrees C

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.2
battManEnvStatusHumidity
Scaled representation of battery manager humidity percent.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.3
battManEnvStatusDryContact
bit map that indicates the state of the dry contacts. bit set means the corresponding dry contact is closed
Bits Dry Contact
0 dry contact1
1 dry contact2
2 dry contact3
3 dry contact4
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.4
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9 · 1 row entry · 6 columns
Table containing battery manager's Manual Measurement trigger command and response data.
battManManualMeasEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1
List of ManualMeasurement Status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManManualMeasDeviceAddress
Column Syntax OID
battManManualMeasDeviceAddress
Index into the battManManualMeasStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.1
battManManualMeasStatusText
Short phrase describing the manual measurement status.
OctetString
Constraints:
range: 80-80
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.2
battManManualMeasStatusCode
0: Taking measurement now.
1: Equalizer on, the measurement will be ready in 5 minutes.
2: NACK, cannot take measurement now.
3: Waiting for controller information
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.3
battManManualMeasDatasetID
Dataset ID of this measurement (When Status code 0 and 1 was returned by the trigger command). Reset to negative value when not applicable.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.4
battManManualMeasTimeToMeasurement
(When Status code 2 was returned by the trigger command): remaining time in seconds before a measurement can be done. Reset to negative value when not applicable.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.5
battManManualMeasurementTrigger
Measurement manual trigger command. Then check the battManManualMeasTimeToMeasurement. When read always returns false(2).
Enumerationr/w
Enumerated Values:
1true
2false
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.6
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11 · 1 row entry · 9 columns
Table containing batteries data
battManBatteryLogEntry entry .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1
List of information about each battery. Indexed by battery number
Indexes
battManBattLogDeviceAddress battManBattLogDatasetID battManBattLogStringID battManBattLogBatteryID
Column Syntax OID
battManBattLogDeviceAddress
Index into the battManBatteryLog. Corresponds to battManDeviceAddress in battManDeviceTable
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.1
battManBattLogDatasetID
The DatasetID of the measurement done for this battery.
Unsigned32
Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.2
battManBattLogBatteryID
Index into the battManBatteryLog.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.3
battManBattLogStringID
id of the string that this battery belongs to.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.4
battManBattLogVoltage
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.5
battManBattLogTemperature
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C.

This item requires an entry in the properties MIB.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.6
battManBattLogImpedance
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm.

This item requires an entry in the properties MIB.
HundredthmOhm
Textual Convention: HundredthmOhm Integer32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.7
battManBattLogConductance
Scaled representation of an individual battery cell conductance in in 1/100 of Siemens
with a range of 6000 to 60000 Siemens (tbd)

This item requires an entry in the properties MIB.
HundredthkS
Textual Convention: HundredthkS Integer32
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.8
battManBattLogTimestamp
Date and time when the measurement was taken.

This item requires an entry in the discrete properties MIB.
SNMPv2-TCDateAndTime
Textual Convention: SNMPv2-TCDateAndTime OctetString
Type Constraints:
range: 8
range: 11
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.9