ELECTROLINE-DHT-BATTERIES-CONTROLLER-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
9
Rows
9
Columns
62
battManDeviceTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2
·
1 row entry
·
17 columns
Table containing information about the individual battery manager being monitored.
List of information about each battery manager being monitored.
Indexes
battManDeviceAddress
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
battManDeviceAddress
Index into the battManDeviceTable.Address of this device on the RS-485 path
|
Integer32 Constraints: range: 17-127 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.1 |
||||
|
battManProtocolVersion
Version of the protocol implemented in the monitored equipment.
|
Integer32 Constraints: range: 1-254 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.2 |
||||
|
battManSoftwareVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the monitored device system software version. Any printable ASCII characters can be included in this field. NULL (0x00) c… |
OctetString Constraints: range: 8-8 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.3 |
||||
|
battManDeviceId
The content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information. |
OctetString Constraints: range: 32-32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.4 |
||||
|
battManVendorIdentity
The content of this field is vendor specific. The intent is to provide
a text representation of the battery manager vendor identity. Any printable ASCII characters can be included in this field. NULL (0x00) characters … |
OctetString Constraints: range: 10-10 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.5 |
||||
|
battManStringVoltage
Current string voltage configuration.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.6 |
||||
|
battManBatteries
Current number of batteries.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.7 |
||||
|
battManBatteryStrings
Current number of strings.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.8 |
||||
|
battManBatteriesPerStrings
Current number of batteries per string.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.9 |
||||
|
battManVoltageSupport
Defines if the voltage measurement is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.10 |
||||
|
battManTemperatureSupport
Defines if the temperature measurement is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.11 |
||||
|
battManImpedanceSupport
Defines if the impedance measurement is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.12 |
||||
|
battManEqualPercentSupport
Defines if the equlization percent measurement is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.13 |
||||
|
battManBatteryStatusSupport
Defines if the battery status monitoring is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.14 |
||||
|
battManDiagSupport
Defines if the battery manager modules diagnostics monitoring is supported
1 = No support. 2 = Field is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.15 |
||||
|
battManEnvDataSupport
Defines if the battery manager environment data is supported
1 = No support. 2 = The Environment Data table is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.16 |
||||
|
battManManualMeasurementSupport
Defines if the battery manager manualy triggered measurement is supported
1 = No support. 2 = The Manual Measurement table is supported in this installation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.2.1.17 |
battManStringTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3
·
1 row entry
·
4 columns
Table containing strings data
List of information about each string. Indexed by string number
Indexes
battManStringDeviceAddress battManString
| Column | Syntax | OID |
|---|---|---|
|
battManStringDeviceAddress
Index into the battManStringTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.1 |
|
battManString
Index into the battManStringTable.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.2 |
|
battManStringBatteries
number of batteries.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.3 |
|
battManStringTotalVoltage
Scaled representation of an individual string total voltage in 1/100 Volts
This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.3.1.4 |
battManBatteryTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4
·
1 row entry
·
12 columns
Table containing batteries data
List of information about each battery. Indexed by battery number
Indexes
battManBatteryDeviceAddress battManBatteryStringID battManBattery
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
battManBatteryDeviceAddress
Index into the battManBatteryTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.1 |
||||
|
battManBattery
Index into the battManBatteryTable.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.2 |
||||
|
battManBatteryStringID
id of the string that this battery belongs to.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.3 |
||||
|
battManBatteryVersion
battery module version.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.4 |
||||
|
battManBatteryHwVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system hardware version. Any printable ASCII characters can be included in this field. NULL (0x00) characters … |
OctetString | .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.5 |
||||
|
battManBatterySwVersion
The content of this field is vendor specific. The intent is to provide
a text representation of the battery system software version. Any printable ASCII characters can be included in this field. NULL (0x00) characters … |
OctetString | .1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.6 |
||||
|
battManBatteryVoltage
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.7 |
||||
|
battManBatteryTemperature
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C. This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.8 |
||||
|
battManBatteryImpedance
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm. This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.9 |
||||
|
battManBatteryEqualizationPercent
Reports the battery equalization percent with a range of 0 to 100%.
This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.10 |
||||
|
battManBatteryStatus
Reports the status of the battery
1. ok 2. alarm This item requires an entry in the discrete properties MIB. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.11 |
||||
|
battManBatteryDatasetID
The DatasetID of the measurement done for this battery.
|
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.4.1.12 |
battManBatteryDiagTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5
·
1 row entry
·
4 columns
Table containing battery diagnostic data
List of diagnostic information about each battery. Indexed by battery number
Indexes
battManBatteryDiagDeviceAddress battManBatteryDiagModuleID
| Column | Syntax | OID |
|---|---|---|
|
battManBatteryDiagDeviceAddress
Index into the battManBatteryDiagTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.1 |
|
battManBatteryDiagModuleID
Index into the battManBatteryDiagTable.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.2 |
|
battManBatteryDiagPageNumber
the data page number.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.3 |
|
battManBatteryDiagPageData
The content of this field is vendor specific. The intent is to provide
a text representation of the particular information of the identified module. when an invalid page number is requested, this field will be returned… |
OctetString Constraints: range: 20-20 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.5.1.4 |
battManControlTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6
·
1 row entry
·
4 columns
Table containing battery managers control settings.
List of controls about each battery manager. Indexed by battManControlDeviceAddress
Indexes
battManControlDeviceAddress
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
battManControlDeviceAddress
Index into the battManControlStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.1 |
||||
|
battManControlEqualizationSetting
Represents the equalization status.
1 means equalization activated 2 means equalization deactivated |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.2 |
||||
|
battManControlAutoInterval
Represents the period (in hours) used to take automated measurements
The value 0 deactivates the automated measurements |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.3 |
||||
|
battManControlSensorsRestart
Restart the sensors. Reading the object returns false(2), and has no effect on the unit.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.6.1.4 |
battManStatusTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7
·
1 row entry
·
2 columns
Table containing battery managers status data.
List of status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManStatusDeviceAddress
| Column | Syntax | OID |
|---|---|---|
|
battManStatusDeviceAddress
Index into the battManStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.1 |
|
battManStatusTimeToMeasurement
Indicates the remaining time (in seconds) before next automated measurement.
If the automated measurement is deactivated, then the return value is always 0. |
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.7.1.2 |
battManEnvStatusTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8
·
1 row entry
·
4 columns
Table containing battery manager's Environmental Status data.
List of Environmental Status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManEnvStatusDeviceAddress
| Column | Syntax | OID |
|---|---|---|
|
battManEnvStatusDeviceAddress
Index into the battManEnvStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.1 |
|
battManEnvStatusTemperature
Scaled representation of battery manager temperature in degrees C
This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.2 |
|
battManEnvStatusHumidity
Scaled representation of battery manager humidity percent.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.3 |
|
battManEnvStatusDryContact
bit map that indicates the state of the dry contacts. bit set means the corresponding dry contact is closed
Bits Dry Contact 0 dry contact1 1 dry contact2 2 dry contact3 3 dry contact4 |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.8.1.4 |
battManManualMeasTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9
·
1 row entry
·
6 columns
Table containing battery manager's Manual Measurement trigger command and response data.
List of ManualMeasurement Status information about each battery manager. Indexed by battManEnvDeviceAddress
Indexes
battManManualMeasDeviceAddress
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
battManManualMeasDeviceAddress
Index into the battManManualMeasStatusTable. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.1 |
||||
|
battManManualMeasStatusText
Short phrase describing the manual measurement status.
|
OctetString Constraints: range: 80-80 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.2 |
||||
|
battManManualMeasStatusCode
0: Taking measurement now.
1: Equalizer on, the measurement will be ready in 5 minutes. 2: NACK, cannot take measurement now. 3: Waiting for controller information |
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.3 |
||||
|
battManManualMeasDatasetID
Dataset ID of this measurement (When Status code 0 and 1 was returned by the trigger command). Reset to negative value when not applicable.
|
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.4 |
||||
|
battManManualMeasTimeToMeasurement
(When Status code 2 was returned by the trigger command): remaining time in seconds before a measurement can be done. Reset to negative value when not applicable.
|
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.5 |
||||
|
battManManualMeasurementTrigger
Measurement manual trigger command. Then check the battManManualMeasTimeToMeasurement. When read always returns false(2).
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.9.1.6 |
battManBatteryLogTable
table.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11
·
1 row entry
·
9 columns
Table containing batteries data
List of information about each battery. Indexed by battery number
Indexes
battManBattLogDeviceAddress battManBattLogDatasetID battManBattLogStringID battManBattLogBatteryID
| Column | Syntax | OID |
|---|---|---|
|
battManBattLogDeviceAddress
Index into the battManBatteryLog. Corresponds to battManDeviceAddress in battManDeviceTable
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.1 |
|
battManBattLogDatasetID
The DatasetID of the measurement done for this battery.
|
Unsigned32 Textual Convention: CISCO-ATM-SWITCH-CUG-MIBUnsigned32 Unsigned32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.2 |
|
battManBattLogBatteryID
Index into the battManBatteryLog.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.3 |
|
battManBattLogStringID
id of the string that this battery belongs to.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.4 |
|
battManBattLogVoltage
Scaled representation of an individual battery voltage in 1/100 Volts
with a range of 0 to 16.000 volts This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.5 |
|
battManBattLogTemperature
Scaled representation of temperature in degrees C
with a range of -40 to + 80 degrees C. This item requires an entry in the properties MIB. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.6 |
|
battManBattLogImpedance
Scaled representation of an individual battery impedance in 1/100 mOhm
with a range of 0 to 99.99 mOhm. This item requires an entry in the properties MIB. |
HundredthmOhm Textual Convention: HundredthmOhm Integer32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.7 |
|
battManBattLogConductance
Scaled representation of an individual battery cell conductance in in 1/100 of Siemens
with a range of 6000 to 60000 Siemens (tbd) This item requires an entry in the properties MIB. |
HundredthkS Textual Convention: HundredthkS Integer32 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.8 |
|
battManBattLogTimestamp
Date and time when the measurement was taken.
This item requires an entry in the discrete properties MIB. |
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.5802.1.3.1.2.5.1.16.1.11.1.9 |