CYCLADES-ACS-PM-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
21
.1.3.6.1.4.1.2925.4.5.2 · 1 row entry · 7 columns
Allows to read information about each connected PM
cyPMEntry entry .1.3.6.1.4.1.2925.4.5.2.1
Information about the connected PM
Indexes
cyPMSerialPortNumber
Column Syntax OID
cyPMSerialPortNumber
The number of the serial port when the PM is connected.
IF-MIBInterfaceIndex
Textual Convention: IF-MIBInterfaceIndex Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.2925.4.5.2.1.1
cyPMNumberOutlets
Number of outlets.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.2.1.2
cyPMNumberUnits
Total number of PM unists that are accessed by this
serial port.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.2.1.3
cyPMCurrent
Current reading for the PM.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2925.4.5.2.1.4
cyPMVersion
The software version of the PM.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2925.4.5.2.1.5
cyPMTemperature
The PM temperature.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2925.4.5.2.1.6
cyPMCommand
A character string for the user to send commands to
PM. He can use it to does the save command.
Or to list the outlets that need to be turned off,
or turned on , or cycled or locked or unlocked as a
group. The command…
OctetStringr/w
Constraints:
range: 1-100
.1.3.6.1.4.1.2925.4.5.2.1.7
.1.3.6.1.4.1.2925.4.5.3 · 1 row entry · 8 columns
Allow operations on specific PM unit connected
cyPMUnitEntry entry .1.3.6.1.4.1.2925.4.5.3.1
Allow operations on outlet
Indexes
cyPMSerialPortNumber cyPMUnitNumber
Column Syntax OID
cyPMUnitNumber
The number of the PM unit in the daisy-chained mode.
IF-MIBInterfaceIndex
Textual Convention: IF-MIBInterfaceIndex Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.1
cyPMUnitVersion
The software version of this PM unit.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2925.4.5.3.1.2
cyPMUnitOutlets
Number of outlets of this PM unit.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.3
cyPMUnitFirstOutlet
Number of the first outlet of this PM unit.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.4
cyPMUnitCurrent
Current of this PM unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.5
cyPMUnitMaxCurrent
Maximum current of this PM unit in AMP.
The value of this object is the maximum current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the maximum current is 0.5 AMP.)
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.6
cyPMUnitTemperature
Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the …
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.7
cyPMUnitMaxTemperature
Maximum temperature value of this PM unit in Celsius
degrees. The value of this object is the maximum
temperature in degrees C * 10. You need to translate
the readed value(Ex. : value is 240, the maximum
temperature …
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.3.1.8
.1.3.6.1.4.1.2925.4.5.4 · 1 row entry · 6 columns
Allow operations on outlet
cyOutletEntry entry .1.3.6.1.4.1.2925.4.5.4.1
Allow operations on outlet
Indexes
cyPMSerialPortNumber cyOutletNumber
Column Syntax OID
cyOutletNumber
The outlet number on the PM. Zero is ALL outlets.
IF-MIBInterfaceIndexOrZero
Textual Convention: IF-MIBInterfaceIndexOrZero Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.2925.4.5.4.1.1
cyOutletName
The name given to a particular outlet Maximum size is 8 characters.
OctetStringr/w
Constraints:
range: 1-8
.1.3.6.1.4.1.2925.4.5.4.1.2
cyOutletServer
Alias of the Server connected to this outlet .
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2925.4.5.4.1.3
cyOutletPower
Getting this object will return the power state of
the outlet. Valid return states are UNKNOW, OFF and
ON. Setting this object will change the power state
of the outlet.
Enumerationr/w
Enumerated Values:
0off
1on
2cycle
3unknow
.1.3.6.1.4.1.2925.4.5.4.1.4
cyOutletLock
Getting this object will return the lock state of
the outlet. Setting this object will change the
lock state of the outlet.
Enumerationr/w
Enumerated Values:
0unlock
1lock
2unknow
.1.3.6.1.4.1.2925.4.5.4.1.5
cyOutletPUInterval
The power unit interval of this outlet in seconds.
The value of this object is the actual interval in
seconds * 10. You need to translate the readed value
(Ex. : value is 5, the interval is 0.5 seconds.)
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2925.4.5.4.1.6