wtWebioEA2x2ERPPortInputMode
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.25.3.2.1.1.3
Object
column
mandatory
r/w
OctetString
Binary coded modes: Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequenz equals 2000 Hz. This mode is available for inputs 0-3 only. Selecting counter clear on read by setting the corresponding bit to 1 enables the corresponding counter to be cleared automatically every time it is read, except HTTP reading with user rights. The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. Selection for input 0-1: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Bidirectional counter enable Bit 2 : Counter clear on read Bit 1 : Change detection enable (default) Bit 0 : Short Pulse detection enable
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.25.3.2.1.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioEA2x2ERPInputPortEntry
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.