wtWebioEA2x2ERPAlarmOutputTrigger
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.2
Object
column
mandatory
r/w
OctetString
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
The first four OCTETS contain the mask which determines which of the outputs are to
be considered (corresponding bit = 1) and which outputs are to ignore
(corresponding bit = 0):
OCTET 1 : unused
OCTET 2 : unused
OCTET 3 : unused
OCTET 4, Bit 0-1: Mask for digital outputs 0-1
OCTETS 5-8 contain the level (1=HIGH, 0=LOW) which the outputs
should assume:
OCTET 5 : unused
OCTET 6 : unused
OCTET 7 : unused
OCTET 8, Bit 0-1: Level of digital outputs 0-1
OCTETS 9-12 contain the ANY bit (1=ON, 0=OFF). Outputs masked with the any bit trigger with any change
of the corresponding output bit. Settings in OCTET 5-9 are then unused:
OCTET 9: unused
OCTET 10: unused
OCTET 11: unused
OCTET 12, Bit 0-1: ANY bits of digital outputs 0-1
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.2- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioEA2x2ERPAlarmEntry
Syntax
OctetString
Values & Constraints
Object Constraints
range: 4-4