wtWebioEA24oemLoadControlView
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.14.3.1.5.4
Object
scalar mandatory
OctetString
Here the result of automatic load control can be read. All output were tested in pairs (0-1, 2-3, 4-5, 6-7, 8-9, 10-11). If an error occours at one output, both output of an pair will be switched of. For a properly function of the load control each output of a pair have to has a load. If there is no existing load, a pull down resistor can be used. Outputs with no load are automaticly detected and not part of the control function. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. Octet 1: unused OCTET 2: Bit 0-7 : outputs 16 - 23 OCTET 3: Bit 0-7 : outputs 8 - 15 OCTET 4: Bit 0-7 : outputs 0 - 7
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.14.3.1.5.4- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- wtWebioEA24oemAlarm
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'Webio-Digital-MIB-US' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Webio-Digital-MIB-US::wtWebioEA24oemLoadControlView.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'Webio-Digital-MIB-US' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'Webio-Digital-MIB-US::wtWebioEA24oemLoadControlView'
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.