wtWebioEA12x12PortInputMode
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.3
Object
column
mandatory
r/w
OctetString
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables
interrupt support for counting. Only positive edges are accepted as trigger
source. The maximum counting frequenz equals 2000 Hz.
This mode is available for inputs 0-3 only.
Selecting counter clear on read by setting the corresponding bit to 1 enables
the corresponding counter to be cleared automatically every time it is read,
except HTTP reading with user rights.
The OCTETS are interpreted bit-by-bit, with each set of octets corresponding to an input.
Bit 0 corresponds to the LSB.
Selection for input 0-3:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 3-7: unused
Bit 2 : Counter clear on read
Bit 1 : Change detection enable (default)
Bit 0 : Short Pulse detection enable
Selection for inputs 4-11:
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4, Bit 2-7: unused
Bit 1 : Counter clear on read
Bit 0 : Change detection enable (default)
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioEA12x12InputPortEntry
Syntax
OctetString
Values & Constraints
Object Constraints
range: 4-4