wtWebioEA12x12LCShutDownView
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.4.3.1.5.5
Object
scalar
mandatory
r/w
OctetString
Here the result of the automatic load control shut down can be read. All outputs remain switched of,
until a zero is written into this variable. But previously all loads should be inspected.
High current (short circuit), a broken supply line or a defect load (i.e. lamp) may be a shut down reason.
If no load is detected, the load control unit suspend automaticly the control of the corresponding output pair.
All controlled output could be identified reading the variable wtWebioEA12x12LoadControlEnable.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 4-7: unused
Bit 0-3: outputs 8-11
Octet 4:
Bit 0-7: outputs 0-7.
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.4.3.1.5.5- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebioEA12x12Alarm
Syntax
OctetString
Values & Constraints
Object Constraints
range: 1-12