wtWebio577xxEA12x12OutputValue

Webio-Digital-MIB-US · .1.3.6.1.4.1.5040.1.2.49.1.6

Object

scalar mandatory r/w Integer32
This variable is used to read and write the outputs of the digital I/O port. 
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. 
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: Bit 0-3: Digital outputs 8-11
OCTET 4, Bit 0-7: Digital outputs 0-7

Context

MIB
Webio-Digital-MIB-US
OID
.1.3.6.1.4.1.5040.1.2.49.1.6
Type
scalar
Access
readwrite
Status
mandatory
Parent
wtWebio577xxEA12x12InOut

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'Webio-Digital-MIB-US' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Webio-Digital-MIB-US::wtWebio577xxEA12x12OutputValue.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'Webio-Digital-MIB-US' -M '/opt/observium/mibs/webgraph:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'Webio-Digital-MIB-US::wtWebio577xxEA12x12OutputValue'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647