wtWebCount6ReportInputTrigger
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.1
Object
column
mandatory
r/w
OctetString
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input.
Bit 0 corresponds to the LSB.
The first four OCTETS contain the mask which determines which of the inputs are to
be considered (corresponding bit = 1) and which inputs are to ignore
(corresponding bit = 0):
OCTET 1 : unused
OCTET 2 : unused
OCTET 3: unused
OCTET 4, Bit 0-5: Mask for digital inputs 0-5
Bit 6-7: unused
OCTETS 5-8 contain the level (1=HIGH, 0=LOW) which the inputs
should assume:
OCTET 5 : unused
OCTET 6 : unused
OCTET 7 : unused
OCTET 8, Bit 0-5: Level of digital inputs 0-5
Bit 6-7: unused
OCTETS 9-12 contain the counter bit (1=ON, 0=OFF). Inputs masked with the counter bit trigger an Report
when the corresponding counter reaching the wtWebCount6ReportMaxCounterValue. Settings in OCTET 5-9 are then unused:
OCTET 9 : unused
OCTET 10: unused
OCTET 11: unused
OCTET 12, Bit 0-5: Counter bits of digital inputs 0-5
Bit 6-7: unused.
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.1- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebCount6ReportEntry
Syntax
OctetString
Values & Constraints
Object Constraints
range: 1-65535