objDCSystemError
UPC4 ·
.1.3.6.1.4.1.16460.5.1.1.61.1.61
Object
column 1Enumeration
It is the current Error state for the DC-system: Event# DC-system 1 = (30XX) Event# DC-system 2 = (32XX) Event# DC-system 3 = (34XX) Event# DC-system 4 = (36XX) 1 : (3000) Vload < Vmin 2 : (3001) Vload > Vmax 3 : (3002) Vload < Vmin_INV 4 : (3003) Vload < Vmin_DCC 5 : (3010) REC#1 Error 6 : (3011) REC#1 No CAN 7 : (3012) REC#1 Redundancy 8 : (3013) REC#1 Load 9 : (3014) REC#1 Load distribution 10 : (3020) REC#2 Error 11 : (3021) REC#2 No CAN 12 : (3022) REC#2 Redundancy 13 : (3023) REC#2 Load 14 : (3024) REC#2 Load distribution 15 : (3030) Limit Load current 16 : (3035) DCC Error 17 : (3036) DCC No CAN 18 : (3037) DCC Redundancy 19 : (3040) INV Error 20 : (3041) INV No CAN 21 : (3042) INV Redundancy 22 : (3075) STS Error state 23 : (3076) STS No CAN 24 : (3077) STS Error source 1 25 : (3078) STS Error source 2 26 : (3079) STS Synchronization error 27 : (3080) STS Inverter error 28 : (3081) STS Temperature Heat sink 29 : (3082) STS Current high 30 : (3083) STS DC voltage low 31 : (3084) STS DC voltage high 32 : (3085) STS DC voltage low (Warning threshold) 33 : (3086) STS DC voltage high (Warning threshold) 34 : (3087) STS Mains priority 35 : (3088) STS Relay active 36 : (3089) STS Load on INV 37 : (3090) STS Collective alarm 38 : (3091) STS _not used_ 39 : (3092) STS _not used_ 40 : (3043) Equalize charge 41 : (3044) Equalize charge Timeout 42 : (3045) Boost charge 43 : (3046) Boost charge Timeout 44 : (3047) Fan (boost charge) 45 : (3051) Isolation error Plus 46 : (3052) Isolation error Minus 47 : (3053) Isolation measurement runs 48 : (3056) Battery test 49 : (3057) Battery test error 50 : (3060) Drop diode 1 51 : (3061) Drop diode 2 52 : (3064) Difference Ah 53 : (3067) Capacity low A 54 : (3068) Capacity low B 55 : (3070) Tsensor limit Battery 56 : (3073) Diesel operation
Context
- MIB
- UPC4
- OID
.1.3.6.1.4.1.16460.5.1.1.61.1.61- Type
- column
- Access
- readonly
- Status
- current
- Units
- 1
- Parent
- upc4DCSystemErrorEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'UPC4' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'UPC4::objDCSystemError'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'UPC4' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'UPC4::objDCSystemError.<objDCSystemError>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'UPC4' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'UPC4::objDCSystemError'
Syntax
1Enumeration
Values & Constraints
Enumerated Values
0 | inactive |
1 | active |