batteryTerminalVoltage
OBS ✓
TRISTAR-MPPT ·
.1.3.6.1.4.1.33333.2.38
Object
scalar SNMPv2-SMIInteger32
Battery Terminal Voltage - Description: Battery Terminal Voltage - Scaling Factor: 0.0054931640625 - Units: V - Range: [-10, 180] - Modbus address: 0x0019
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in:
Sensors
Explore Observium network monitoring
Context
- MIB
- TRISTAR-MPPT
- OID
.1.3.6.1.4.1.33333.2.38- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- tristarmppt
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'TRISTAR-MPPT' -M '/opt/observium/mibs/morningstar:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'TRISTAR-MPPT::batteryTerminalVoltage.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'TRISTAR-MPPT' -M '/opt/observium/mibs/morningstar:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'TRISTAR-MPPT::batteryTerminalVoltage'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647