upsRebootDuration
TRIPPUPS1-MIB ·
.1.3.6.1.4.1.850.1.1.9.4
Object
scalar
mandatory
r/w
Integer32
Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of the upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall depend on the value of upsAutoRestart at that time. UNITS seconds
Context
- MIB
- TRIPPUPS1-MIB
- OID
.1.3.6.1.4.1.850.1.1.9.4- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsControl
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-100