esPointValueStr

SL81-STD-MIB · .1.3.6.1.4.1.3052.5.1.1.1.1.7

Object

column mandatory SNMPv2-TCDisplayString
A string referring to the value of a point on an
EventSensor.
              
For contact closures and relays this object is
either 'Open' or 'Closed'.
              
For temperature and humidity point classes, this
object is the string representation of the
esPointValueInt object.  For temperature, 'C' or
'F' is including in the string to indicate scale.
              
For analog inputs, this object is the string
representation of the plus/minus input in the
configured units appended with the unit name.

Context

MIB
SL81-STD-MIB
OID
.1.3.6.1.4.1.3052.5.1.1.1.1.7
Type
column
Access
readonly
Status
mandatory
Parent
esPointEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SL81-STD-MIB' -M '/opt/observium/mibs/asentria:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SL81-STD-MIB::esPointValueStr'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'SL81-STD-MIB' -M '/opt/observium/mibs/asentria:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SL81-STD-MIB::esPointValueStr.<esIndexES>.<esIndexPC>.<esIndexPoint>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'SL81-STD-MIB' -M '/opt/observium/mibs/asentria:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'SL81-STD-MIB::esPointValueStr'

Syntax

Source
SNMPv2-TCDisplayString
Base type
OctetString
Display format
255a
Type Description
Represents textual information taken from the NVT ASCII
          
character set, as defined in pages 4, 10-11 of RFC 854.
          
To summarize RFC 854, the NVT ASCII repertoire specifies:
          
  - the use of character codes 0-127 (decimal)
          
  - the graphics characters (32-126) are interpreted as
    US ASCII
          
  - NUL, LF, CR, BEL, BS, HT, VT and FF have the special
    meanings specified in RFC 854
          
  - the other 25 codes have no standard interpretation
          
  - the sequence 'CR LF' means newline
          
  - the sequence 'CR NUL' means carriage-return
          
  - an 'LF' not preceded by a 'CR' means moving to the
    same column on the next line.
          
  - the sequence 'CR x' for any x other than LF or NUL is
    illegal.  (Note that this also means that a string may
    end with either 'CR LF' or 'CR NUL', but not with CR.)
          
Any object defined using this syntax may not exceed 255
characters in length.

Values & Constraints

Type Constraints
range: 0..255