Object
column
Integer32
The part of the point index that refers to an
EventSensor.
The point index is a string of 3 numbers separated
by periods. It contains all the information
necessary for getting a piece of data off an event
sensor; namely, which EventSensor, point class,
and which-sensor-of-that-class (a.k.a. point).
This object's allowable values are 1 through 16,
and 200. 200 always refers to the EventSensor
inside the unit. 1 through 16 refer to additional
attached EventSensors.
The number corresponding to an EventSensor is
determined by the user at the initial configuration
time. If there is an internal sensor in the unit,
it will always be the first item in the Sensor
Events setup menu.
For example, if a new EventSensor is configured as
the 2nd entry AFTER the internal EventSensor (if
one exists) in the Sensor Events Setup Menu, then
that EventSensor will be known from then on as
EventSensor 2. All point indeces with esIndexES=2
will now refer to that particular EventSensor.
Context
- MIB
- SITEBOSS-550-STD-MIB
- OID
.1.3.6.1.4.1.3052.10.1.1.1.1.1- Type
- column
- Access
- readonly
- Status
- current
- Parent
- esPointEntry
Syntax
Integer32
Values & Constraints
Object Constraints
range: 1-200