es1DcSys1CfgBatAutonomyPeukertNumber
SITE-MONITORING-MIB ·
.1.3.6.1.4.1.12551.20.1.20.1.20.1.15.3.106
Object
The Peukert number relates to the internal resistance of a battery and provides an indication of the expected capacity. The ideal number is 1. This value can be calculated with the formula: (ln(t2)-ln(t1))/(ln(i1)-ln(i2)) where tx is the autonomy in hours at a constant discharge current of ix Amps. Often, we use t1 = 1h and t2 = 10h
Context
- MIB
- SITE-MONITORING-MIB
- OID
.1.3.6.1.4.1.12551.20.1.20.1.20.1.15.3.106- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- es1DcSys1ConfigList
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'SITE-MONITORING-MIB' -M '/opt/observium/mibs/cet-power:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SITE-MONITORING-MIB::es1DcSys1CfgBatAutonomyPeukertNumber.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'SITE-MONITORING-MIB' -M '/opt/observium/mibs/cet-power:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'SITE-MONITORING-MIB::es1DcSys1CfgBatAutonomyPeukertNumber'
Syntax
- Source
- SNMPv2-TCDisplayString
- Base type
OctetString- Display format
255a
Type Description
Represents textual information taken from the NVT ASCII
character set, as defined in pages 4, 10-11 of RFC 854.
To summarize RFC 854, the NVT ASCII repertoire specifies:
- the use of character codes 0-127 (decimal)
- the graphics characters (32-126) are interpreted as
US ASCII
- NUL, LF, CR, BEL, BS, HT, VT and FF have the special
meanings specified in RFC 854
- the other 25 codes have no standard interpretation
- the sequence 'CR LF' means newline
- the sequence 'CR NUL' means carriage-return
- an 'LF' not preceded by a 'CR' means moving to the
same column on the next line.
- the sequence 'CR x' for any x other than LF or NUL is
illegal. (Note that this also means that a string may
end with either 'CR LF' or 'CR NUL', but not with CR.)
Any object defined using this syntax may not exceed 255
characters in length.
Values & Constraints
Type Constraints
range: 0..255
Conformance
Member of