rcIrigbTimeCode
RUGGEDCOM-IRIGB-MIB ·
.1.3.6.1.4.1.15004.4.10.1.3
Object
scalar
r/w
Enumeration
This device uses the following convention to decode the IRIGB time code: letter [B] represents IRIG-B format, [xx] represents [00] for PWM/TTL mode of operation and [12] for AM operation. For example, Bxx7 represents B007 for PWM/TTL operation and B127 for AM operation. Please note that only Bxx0, Bxx1, Bxx4 and Bxx5 time codes support IRIGB extensions.
Context
- MIB
- RUGGEDCOM-IRIGB-MIB
- OID
.1.3.6.1.4.1.15004.4.10.1.3- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- rcIrigbBase
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | bxx0 |
2 | bxx1 |
3 | bxx2 |
4 | bxx3 |
5 | bxx4 |
6 | bxx5 |
7 | bxx6 |
8 | bxx7 |