transferSwitchTransferToInlet
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.4.3.1.1.2
Object
column
r/w
Integer32
Select the active inlet. The written value must be between 1 and the value of inletCount. If the selected inlet is available it will become both active and preferred, otherwise an inconsistentValue error will be returned. By default the switching operation will fail if the phase difference between the inlets is too large. In this case the switch can be forced by writing transferSwitchAlarmOverride as True in the same request. This variable will always read as 0.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.4.3.1.1.2- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- transferSwitchControlEntry
Syntax
Integer32
Values & Constraints
Object Constraints
range: 0-64