dataLogMaxInletPoleVoltage

PDU-MIB · .1.3.6.1.4.1.13742.4.1.13.1.1.8

Object

column MilliVolts
The Maximum value for the measurement period:
The value of the voltage reported
in MilliVolts.
  For Single Phase: Input Line Voltage
  For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
  For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N

Context

MIB
PDU-MIB
OID
.1.3.6.1.4.1.13742.4.1.13.1.1.8
Type
column
Access
readonly
Status
current
Parent
dataLogInletPoleEntry
Groups
1

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PDU-MIB' -M '/opt/observium/mibs/raritan:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PDU-MIB::dataLogMaxInletPoleVoltage'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PDU-MIB' -M '/opt/observium/mibs/raritan:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PDU-MIB::dataLogMaxInletPoleVoltage.<dataLogIndex>.<dataLogInletIndex>.<dataLogInletPoleIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PDU-MIB' -M '/opt/observium/mibs/raritan:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PDU-MIB::dataLogMaxInletPoleVoltage'

Syntax

Source
MilliVolts
Base type
Unsigned32

Values & Constraints

No enumerated values or constraints recorded.

Conformance