lgpCondId6228RemoteSensorAverageHighHumidity
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB ·
.1.3.6.1.4.1.476.1.42.3.2.7.1.6228
Object
node
The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold.
Context
- MIB
- LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.2.7.1.6228- Type
- node
- Status
- current
- Parent
- lgpFlexConditionsWellKnown
- Siblings
- 1279
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpCondId4122SystemInputPowerProblem The input is not qualified to provide power to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4122 |
| lgpCondId4132BypassOverloadPhaseA An overload exists on output phase A while operating on the bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4132 |
| lgpCondId4133BypassOverloadPhaseB An overload exists on output phase B while operating on the bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4133 |
| lgpCondId4134BypassOverloadPhaseC An overload exists on output phase C while operating on the bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4134 |
| lgpCondId4135BypassNotAvailable A problem associated with the bypass has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4135 |
| lgpCondId4137BypassAutoRetransferPrimed Automatic retransfer from bypass to inverter is possible. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4137 |
| lgpCondId4138BypassAutoRetransferFailed After performing a recoverable transfer to bypass, an attempt to
auto retransfer from bypass to inverter failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4138 |
| lgpCondId4139BypassExcessAutoRetransfers The number of auto retransfers, from bypass to inverter, has
exceeded the maximum for a specified time interval. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4139 |
| lgpCondId4140BypassRestartInhibitExternal Restart of the bypass is inhibited by the state of an external
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4140 |
| lgpCondId4141BypassBreakerClosed The bypass breaker is closed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4141 |
| lgpCondId4142BypassStaticSwitchOverload Bypass off due to static switch overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4142 |
| lgpCondId4143BypassStaticSwitchUnavailable The static bypass is unavailable to support the critical load. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4143 |
| lgpCondId4144BypassExcessivePulseParallel The system has performed too many pulse parallel operations within
a specified time interval. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4144 |
| lgpCondId4145BypassAutoTransferFailed An automatic transfer to static bypass failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4145 |
| lgpCondId4146SystemInputPhsRotationError The power conductors on the input line are not wired to the UPS in
the sequence preferred for the rectifier (A-B-C). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4146 |
| lgpCondId4147SystemInputCurrentLimit The RMS input current has reached the input current limit
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4147 |
| lgpCondId4162BatteryLow The calculated battery time remaining has reached the low battery
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4162 |
| lgpCondId4163OutputOffEndofDischarge Output turned off due to battery reaching end-of-discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4163 |
| lgpCondId4164BatteryChargingError The battery is not charging properly. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4164 |
| lgpCondId4165BatteryChargingReducedExtrnl Using a reduced battery charging algorithm due to an external
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4165 |
| lgpCondId4166BatteryCapacityLow Battery capacity is low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4166 |
| lgpCondId4167OutputOff Output is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4167 |
| lgpCondId4168BatteryDischarging The battery is discharging. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4168 |
| lgpCondId4169BatteryTemperatureImbalance Excessive temperature differences between battery sensors detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4169 |
| lgpCondId4170BatteryEqualize The rectifier output voltage is increased to equalize the battery
voltage level. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4170 |
| lgpCondId4171BatteryManualTestInProgress Manual battery test is in progress. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4171 |
| lgpCondId4172BatteryAutoTestInProgress Automatic battery test is in progress. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4172 |
| lgpCondId4173MainBatteryDisconnectOpen Main battery disconnect is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4173 |
| lgpCondId4174BatteryTemperatureSensorFault A battery temperature sensor fault has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4174 |
| lgpCondId4175BypassFrequencyError The bypass frequency is outside the inverter synchronization
limits. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4175 |
| lgpCondId4176BatteryCircuitBreaker1Open Battery circuit breaker 1 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4176 |
| lgpCondId4177BatteryBreaker1OpenFailure Battery circuit breaker 1 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4177 |
| lgpCondId4178BatteryBreaker1CloseFailure Battery circuit breaker 1 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4178 |
| lgpCondId4179BatteryCircuitBreaker2Open Battery circuit breaker 2 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4179 |
| lgpCondId4180BatteryBreaker2OpenFailure Battery circuit breaker 2 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4180 |
| lgpCondId4181BatteryBreaker2CloseFailure Battery circuit breaker 2 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4181 |
| lgpCondId4182BatteryCircuitBreaker3Open Battery circuit breaker 3 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4182 |
| lgpCondId4183BatteryBreaker3OpenFailure Battery circuit breaker 3 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4183 |
| lgpCondId4184BatteryBreaker3CloseFailure Battery circuit breaker 3 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4184 |
| lgpCondId4185BatteryCircuitBreaker4Open Battery circuit breaker 4 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4185 |
| lgpCondId4186BatteryBreaker4OpenFailure Battery circuit breaker 4 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4186 |
| lgpCondId4187BatteryBreaker4CloseFailure Battery circuit breaker 4 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4187 |
| lgpCondId4188BatteryCircuitBreaker5Open Battery circuit breaker 5 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4188 |
| lgpCondId4189BatteryBreaker5OpenFailure Battery circuit breaker 5 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4189 |
| lgpCondId4190BatteryBreaker5CloseFailure Battery circuit breaker 5 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4190 |
| lgpCondId4191BatteryCircuitBreaker6Open Battery circuit breaker 6 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4191 |
| lgpCondId4192BatteryBreaker6OpenFailure Battery circuit breaker 6 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4192 |
| lgpCondId4193BatteryBreaker6CloseFailure Battery circuit breaker 6 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4193 |
| lgpCondId4194BatteryCircuitBreaker7Open Battery circuit breaker 7 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4194 |
| lgpCondId4195BatteryBreaker7OpenFailure Battery circuit breaker 7 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4195 |
| lgpCondId4196BatteryBreaker7CloseFailure Battery circuit breaker 7 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4196 |
| lgpCondId4197BatteryCircuitBreaker8Open Battery circuit breaker 8 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4197 |
| lgpCondId4198BatteryBreaker8OpenFailure Battery circuit breaker 8 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4198 |
| lgpCondId4199BatteryBreaker8CloseFailure Battery circuit breaker 8 failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4199 |
| lgpCondId4200BatteryChargingInhibited Battery charging is inhibited due to an external inhibit signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4200 |
| lgpCondId4213SystemShutdownEPO System shutdown due to Emergency Power Off (EPO). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4213 |
| lgpCondId4214SystemShutdownREPO System shutdown due to Remote Emergency Power Off (REPO). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4214 |
| lgpCondId4215SystemOutputOff The system output is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4215 |
| lgpCondId4216BypassBackfeedDetected The system detected a voltage on the bypass when none was expected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4216 |
| lgpCondId4217BypassManualXfrInhibited Manual transfer from inverter to bypass is inhibited - bypass not
qualified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4217 |
| lgpCondId4218BypassManualRexfrInhibited Manual transfer from bypass to inverter is inhibited - inverter
output not qualified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4218 |
| lgpCondId4219BatteryOverTemperature A battery temperature sensor is reporting a value above a
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4219 |
| lgpCondId4220BatteryExternalMonitor1 External battery monitor 1 - battery maintenance required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4220 |
| lgpCondId4221BatteryExternalMonitor2 External battery monitor 2 - battery maintenance required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4221 |
| lgpCondId4222BatteryGroundFault Battery system ground fault amperage exceeds the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4222 |
| lgpCondId4229EmergencyPowerOffLatched System output is off - 'Emergency Power Off (EPO) - latched'
requires manual reset. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4229 |
| lgpCondId4230SystemOutputLowPowerFactor The system output power factor is low, resulting in reduced output
capacity. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4230 |
| lgpCondId4231OutputCurrentExceedsThreshold Output current for one or more phases exceeds a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4231 |
| lgpCondId4233InverterFailure Inverter failure - inverter output is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4233 |
| lgpCondId4234InverterOverloadPhaseA Inverter is operating with an overload on phase A. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4234 |
| lgpCondId4235InverterOverloadPhaseB Inverter is operating with an overload on phase B. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4235 |
| lgpCondId4236InverterOverloadPhaseC Inverter is operating with an overload on phase C. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4236 |
| lgpCondId4237InverterInhibitExternal Restart of the inverter is inhibited by an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4237 |
| lgpCondId4238InverterOutBreakerOpenFail Inverter output breaker failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4238 |
| lgpCondId4239InverterOutBreakerCloseFail Inverter output breaker failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4239 |
| lgpCondId4270InputContact01 The external input contact 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4270 |
| lgpCondId4271InputContact02 The external input contact 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4271 |
| lgpCondId4272InputContact03 The external input contact 3. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4272 |
| lgpCondId4273InputContact04 The external input contact 4. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4273 |
| lgpCondId4274InputContact05 The external input contact 5. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4274 |
| lgpCondId4275InputContact06 The external input contact 6. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4275 |
| lgpCondId4276InputContact07 The external input contact 7. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4276 |
| lgpCondId4277InputContact08 The external input contact 8. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4277 |
| lgpCondId4278InputContact09 The external input contact 9. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4278 |
| lgpCondId4279InputContact10 The external input contact 10. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4279 |
| lgpCondId4280InputContact11 The external input contact 11. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4280 |
| lgpCondId4281InputContact12 The external input contact 12. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4281 |
| lgpCondId4282InputContact13 The external input contact 13. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4282 |
| lgpCondId4283InputContact14 The external input contact 14. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4283 |
| lgpCondId4284InputContact15 The external input contact 15. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4284 |
| lgpCondId4285InputContact16 The external input contact 16. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4285 |
| lgpCondId4286OutputAmpOverUserLimitPhsA The phase A output has exceeded the user amperage threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4286 |
| lgpCondId4287OutputAmpOverUserLimitPhsB The phase B output has exceeded the user amperage threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4287 |
| lgpCondId4288OutputAmpOverUserLimitPhsC The phase C output has exceeded the user amperage threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4288 |
| lgpCondId4289InverterTransferInhibitExt Transfer of critical bus source to inverter is inhibited by an
external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4289 |
| lgpCondId4290InverterShutdownOverload The inverter has shutdown due to a sustained overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4290 |
| lgpCondId4294InletAirOverTemperature The inlet air exceeds the maximum temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4294 |
| lgpCondId4295RectifierFailure Rectifier failure - rectifier is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4295 |
| lgpCondId4296RectifierOperationInhibitExt The operation of the rectifier is inhibited by an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4296 |
| lgpCondId4297UPSOutputonInverter The output power is supplied by the inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4297 |
| lgpCondId4298UPSOutputonBypass The output power is supplied by the bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4298 |
| lgpCondId4299OutputLoadonMaintBypass The output power is supplied by the maintenance bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4299 |
| lgpCondId4300InternalCommunicationsFailure The control has detected a communication failure of a component on
the internal communication bus. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4300 |
| lgpCondId4308DCBusGroundFaultPositive A ground fault has been detected on the positive DC Bus link. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4308 |
| lgpCondId4309DCBusGroundFaultNegative A ground fault has been detected on the negative DC Bus link. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4309 |
| lgpCondId4310EquipmentOverTemperature Equipment over temperature summary event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4310 |
| lgpCondId4311SystemFanFailure System fan failure - one or more fans have failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4311 |
| lgpCondId4313PasswordChanged Password changed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4313 |
| lgpCondId4314PowerSupplyFailure Power supply failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4314 |
| lgpCondId4315OnGenerator A generator is supplying the power to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4315 |
| lgpCondId4316AutoRestartInProgress Auto restart is in progress. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4316 |
| lgpCondId4317AutoRestartInhibitedExt Auto restart inhibited due to an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4317 |
| lgpCondId4320InitiatedTransfertoBypass User initiated manual transfer to bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4320 |
| lgpCondId4321InitiatedTransfertoInverter User initiated manual transfer to inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4321 |
| lgpCondId4322BatteryTestPassed Battery test passed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4322 |
| lgpCondId4323BatteryTestFailed Battery test failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4323 |
| lgpCondId4324BatteryTestManuallyStopped The battery test was manually stopped prior to completion. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4324 |
| lgpCondId4325BackfeedBreakerOpen The backfeed breaker is in the open position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4325 |
| lgpCondId4341VelocityAuthenticationFailure Notification of a message rejected by Velocity due to an
authentication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4341 |
| lgpCondId4360ReceptacleOverCurrent The system has detected a receptacle over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4360 |
| lgpCondId4361ReceptacleUnderCurrent The system has detected a receptacle under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4361 |
| lgpCondId4382SystemInputCurrentImbalance System Input Currents are Imbalanced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4382 |
| lgpCondId4383BypassStaticSwitchOffExtrnl Bypass static switch is off due to the state of an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4383 |
| lgpCondId4384BatteryEoDDisconnect Battery disconnect due to end-of-discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4384 |
| lgpCondId4389SystemOutputFault A fault has been detected in the system output. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4389 |
| lgpCondId4390InverterOffExternal Inverter is off (operation is inhibited) due to external signal
state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4390 |
| lgpCondId4391InverterStaticSwitchSCRShort The system has detected a short across one or more inverter static
switch Silicon Controlled Rectifiers (SCR). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4391 |
| lgpCondId4392TemperatureSensorError One or more temperature sensors cannot provide a valid temperature
reading (i.e. sensor failure, wiring failure, sense circuit
failure, etc). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4392 |
| lgpCondId4406BranchOverCurrent The system has detected a module over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4406 |
| lgpCondId4407BranchUnderCurrent The system has detected a module under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4407 |
| lgpCondId4416BranchOverCurrent The system has detected a module over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4416 |
| lgpCondId4417BranchUnderCurrent The system has detected a module under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4417 |
| lgpCondId4421BranchFailure One or more conditions indicate a Branch Receptacle Module failure
, service is required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4421 |
| lgpCondId4436PDUOverCurrent The system has detected a module over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4436 |
| lgpCondId4437PDUUnderCurrent The system has detected a module under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4437 |
| lgpCondId4438SystemInternalTemperatureRise Excessive temperature rise internal to the system (i.e. difference
between the output versus input temperature is too large). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4438 |
| lgpCondId4439AutomaticRestartFailed Automatic restart failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4439 |
| lgpCondId4440FuseFailure A summary event indicating one or more fuse failures. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4440 |
| lgpCondId4441SystemControllerError System controller internal error. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4441 |
| lgpCondId4442SystemBreakersOpenFailure One or more breakers in the system failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4442 |
| lgpCondId4448PDUOverCurrent The system has detected a module over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4448 |
| lgpCondId4449PDUUnderCurrent The system has detected a module under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4449 |
| lgpCondId4468PDUOverCurrentL1 The system has detected a module over current condition on line 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4468 |
| lgpCondId4469PDUOverCurrentL2 The system has detected a module over current condition on line 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4469 |
| lgpCondId4470PDUOverCurrentL3 The system has detected a module over current condition on line 3. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4470 |
| lgpCondId4471PDUUnderCurrentL1 The system has detected a module under current condition on line 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4471 |
| lgpCondId4472PDUUnderCurrentL2 The system has detected a module under current condition on line 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4472 |
| lgpCondId4473PDUUnderCurrentL3 The system has detected a module under current condition on line 3. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4473 |
| lgpCondId4492ReceptaclePowerStateOn The receptacle power state changed to the ON state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4492 |
| lgpCondId4493ReceptaclePowerStateOff The receptacle power state changed to the OFF state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4493 |
| lgpCondId4494BranchBreakerOpen The Branch Receptacle Module's input breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4494 |
| lgpCondId4495DeviceConfigurationChange Device Configuration Change. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4495 |
| lgpCondId4496BasicDisplayModuleRemoved Basic Display Module Removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4496 |
| lgpCondId4497BasicDisplayModuleDiscovered Basic Display Module Discovered. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4497 |
| lgpCondId4500PDUOverCurrent The system has detected a power module over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4500 |
| lgpCondId4501PDUUnderCurrent The system has detected a power module under current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4501 |
| lgpCondId4502PDUFailure One or more conditions indicate a power module failure, service is
required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4502 |
| lgpCondId4503PDUCommunicationFail Internal communications failure with the Power Module. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4503 |
| lgpCondId4504BranchRemoved Branch Receptacle Module Removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4504 |
| lgpCondId4505BranchDiscovered Branch Receptacle Module Discovered. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4505 |
| lgpCondId4506BranchOverCurrent The system has detected a Branch Receptacle Module over current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4506 |
| lgpCondId4507BranchCurrent The system has detected a Branch Receptacle Module under current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4507 |
| lgpCondId4508ReceptacleLoadRemoved The receptacle's load stopped drawing power. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4508 |
| lgpCondId4509ReceptacleLoadAdded The receptacle's load started to draw power. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4509 |
| lgpCondId4523ModuleRemoved Module Removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4523 |
| lgpCondId4524ModuleAdded Module Added. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4524 |
| lgpCondId4550FirmwareUpdateRequired Module compatibility error requires a system firmware update to
resolve. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4550 |
| lgpCondId4551GenericTestEvent A generic test event designed to evaluate system handling of
events. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4551 |
| lgpCondId4580OverTemperature An over temperature condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4580 |
| lgpCondId4581UnderTemperature An under temperature condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4581 |
| lgpCondId4588OverRelativeHumidity An over relative humidity condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4588 |
| lgpCondId4589UnderRelativeHumidity An under relative humidity condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4589 |
| lgpCondId4601ExternalAirSensorAOverTemperature [Ext Air Sensor A Temperature] has exceeded [External Air Over
Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4601 |
| lgpCondId4604ExternalAirSensorBOverTemperature [Ext Air Sensor B Temperature] has exceeded [External Air Over
Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4604 |
| lgpCondId4608ExtAirSensorAUnderTemperature [Ext Air Sensor A Temperature] has dropped below [Ext Air Under
Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4608 |
| lgpCondId4611ExtAirSensorBUnderTemperature [Ext Air Sensor B Temperature] has dropped below [Ext Air Under
Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4611 |
| lgpCondId4615ExtDewPointOverTemperature At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
[Ext Dew Point Over Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4615 |
| lgpCondId4618ExternalAirSensorAIssue The external air sensor A is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4618 |
| lgpCondId4621ExternalAirSensorBIssue The external air sensor B is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4621 |
| lgpCondId4626SupplyChilledWaterOverTemp [Supply Fluid Temperature] has exceeded [High Supply Fluid
Temperature Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4626 |
| lgpCondId4629SupplyChilledWaterTempSensorIssue The supply chilled water temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4629 |
| lgpCondId4634SupplyRefrigerantOverTemp Event that is activated when [Supply Refrigerant Temperature]
exceeds [Supply Refrig Over Temp Threshold]. The event is
deactivated when the temperature drops below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4634 |
| lgpCondId4637SupplyRefrigerantUnderTemp [Supply Refrigerant Temperature] has dropped below a specified
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4637 |
| lgpCondId4640SupplyRefrigerantTempSensorIssue The supply refrigeramt temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4640 |
| lgpCondId4645SupplyFluidOverTemp [Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4645 |
| lgpCondId4648SupplyFluidUnderTemp [Supply Fluid Temperature] has dropped below a specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4648 |
| lgpCondId4651SupplyFluidTempSensorIssue The supply fluid temperature sensor is disconnected or the signal
is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4651 |
| lgpCondId4656Pump1LossofFlow Loss of flow is detected in pump 1. The loss of flow condition
occurs when no differential pressure is detected across the pump. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4656 |
| lgpCondId4659Pump2LossofFlow Loss of flow is detected in pump 2. The loss of flow condition
occurs when no differential pressure is detected across the pump. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4659 |
| lgpCondId4662PumpShortCycle Pumps have short cycled. A short cycle is defined as turning on
and off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4662 |
| lgpCondId4669Compressor1AHighHeadPressure Compressor 1A high head pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4669 |
| lgpCondId4672Compressor1BHighHeadPressure Compressor 1B high head pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4672 |
| lgpCondId4675Compressor2AHighHeadPressure Compressor 2A high head pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4675 |
| lgpCondId4678Compressor2BHighHeadPressure Compressor 2B high head pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4678 |
| lgpCondId4681Compressor1AShortCycle Compressor 1A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4681 |
| lgpCondId4684Compressor1BShortCycle Compressor 1B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4684 |
| lgpCondId4687Compressor2AShortCycle Compressor 2A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4687 |
| lgpCondId4690Compressor2BShortCycle Compressor 2B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4690 |
| lgpCondId4693Tandem1LowSuctionPressure 'Tandem compressors' 1 low suction pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4693 |
| lgpCondId4696Tandem2LowSuctionPressure 'Tandem compressors' 2 low suction pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4696 |
| lgpCondId4703ChilledWaterControlValvePosition Chilled water valve out of position. Chilled water control valve
position does not match expected value. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4703 |
| lgpCondId4711SystemCondensationDetected System condensation detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4711 |
| lgpCondId4714ShutdownLossOfPower System lost power. This event becomes active when the unit is
powered on following an unexpected loss of power. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4714 |
| lgpCondId4720SmokeDetected Smoke detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4720 |
| lgpCondId4723WaterUnderFloor Water under the floor is detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4723 |
| lgpCondId4726ServiceRequired Unit requires servicing. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4726 |
| lgpCondId4729FanIssue One or more fans are not operating within their operational
parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4729 |
| lgpCondId4732ReceptacleLoadDropped The receptacle's load is not drawing power. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4732 |
| lgpCondId4740BatteryAutomaticTestInhibited Automatic (scheduled) battery tests are inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4740 |
| lgpCondId4741BatterySelfTest Battery self test is in progress. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4741 |
| lgpCondId4742BatteryLowShutdown Battery disconnect due to end-of-discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4742 |
| lgpCondId4747EquipmentTemperatureSensorFail One or more temperature sensors report a temperature outside of
the range of expected operation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4747 |
| lgpCondId4749SystemFanFailureRedundant Redundant system fan failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4749 |
| lgpCondId4750MultipleFanFailure Multiple fan failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4750 |
| lgpCondId4753MainControllerFault A Main Controller fault has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4753 |
| lgpCondId4754SystemBreakersCloseFailure One or more breakers in the system failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4754 |
| lgpCondId4755InputFilterCycleLock The input filter disconnect is open due to exceeding the maximum
number of cycles. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4755 |
| lgpCondId4756ServiceCodeActive Service code is running. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4756 |
| lgpCondId4757LBSActive The Load Bus Sync option is active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4757 |
| lgpCondId4758LBSInhibited The system has detected that conditions to perform Load Bus Sync
are not satisfied. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4758 |
| lgpCondId4759LeadingPowerFactor The leading output Power Factor has fallen below a specified value. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4759 |
| lgpCondId4760ControlsResetRequired A controls reset is required due to one or more critical settings
changing. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4760 |
| lgpCondId4823ParallelCommWarning Parallel communication bus warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4823 |
| lgpCondId4824SystemCommFail Failure of a device on the multi-module system communication bus. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4824 |
| lgpCondId4825LossofRedundancy The multi-module collection doesn't have enough modules to satisfy
the redundancy configuration. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4825 |
| lgpCondId4826BPSSStartupInhibit The Bypass Static Switch startup is inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4826 |
| lgpCondId4827MMSTransferInhibit The critical load can not be manually transferred from inverter to
bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4827 |
| lgpCondId4828MMSRetransferInhibit The critical load can not be manually retransferred from bypass to
inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4828 |
| lgpCondId4830MMSLossofSyncPulse Multi-module system loss of sync pulse. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4830 |
| lgpCondId4831MMSOverload Multi-module system overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4831 |
| lgpCondId4834MMSOnBattery The multi-module system is on battery. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4834 |
| lgpCondId4835MMSLowBatteryWarning Multi-module system low battery warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4835 |
| lgpCondId4906LowAmbientTemperature The system has detected a low ambient temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4906 |
| lgpCondId4907HighAmbientTemperature The system has detected a high ambient temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4907 |
| lgpCondId4908LowOverallVoltage The system has detected a low battery string overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4908 |
| lgpCondId4909HighOverallVoltage The system has detected a high battery string overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4909 |
| lgpCondId4910HighBatteryStringCurrent The system has detected a high battery string current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4910 |
| lgpCondId4911LowBatteryStringFloatCurrent The system has detected a low battery string float current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4911 |
| lgpCondId4912HighBatteryStringFloatCurrent The system has detected a high battery string float current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4912 |
| lgpCondId4913HighBatteryStringRippleCurrent The system has detected a high battery string ripple current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4913 |
| lgpCondId4914BatteryStringDischargeDetected The system has detected a battery string discharge condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4914 |
| lgpCondId4915MaximumDischargeTimeExceeded The system has detected an excessive discharge time condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4915 |
| lgpCondId4916DischargeLowOverallVoltage The system has detected a low battery string overall voltage
condition during a discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4916 |
| lgpCondId4917DischargeLowCellVoltage The system has detected a low cell voltage condition during a
discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4917 |
| lgpCondId4918DischargeHighBatteryStringCurrent The system has detected a high battery string current condition
during a discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4918 |
| lgpCondId4919ExcessiveCelltoCellTemperatureDeviation The system has detected an excessive cell to cell temperature
deviation condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4919 |
| lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation The system has detected an excessive cell to ambient temperature
deviation condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4920 |
| lgpCondId4964LowCellVoltage The system has detected a low cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4964 |
| lgpCondId4965HighCellVoltage The system has detected a high cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4965 |
| lgpCondId4966LowCellTemperature The system has detected a low cell temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4966 |
| lgpCondId4967HighCellTemperature The system has detected a high cell temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4967 |
| lgpCondId4968LowInternalResistance The system has detected a low internal resistance condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4968 |
| lgpCondId4969HighInternalResistance The system has detected a high internal resistance condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4969 |
| lgpCondId4970HighIntercellResistance The system has detected a high intercell resistance condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4970 |
| lgpCondId4978IntertierResistanceHigh The system has detected a high intertier resistance condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4978 |
| lgpCondId4980SupplyChilledWaterLossofFlow Supply chilled water or glycol flow is too low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4980 |
| lgpCondId4983SupplyRefrigOverTempBand1 [Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 1]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4983 |
| lgpCondId4986SupplyRefrigUnderTempBand1 [Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 1]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4986 |
| lgpCondId4990SupplyRefrigOverTempBand2 [Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 2]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4990 |
| lgpCondId4993SupplyRefrigUnderTempBand2 [Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 2]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4993 |
| lgpCondId4996Inverter1ShortCycle Inverter for pump 1 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a numbe… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4996 |
| lgpCondId4999Inverter2ShortCycle Inverter for pump 2 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a numbe… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.4999 |
| lgpCondId5015SupplyAirOverTemperature [Supply Air Temperature] has exceeded [High Supply Air Temperature
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5015 |
| lgpCondId5019SupplyAirUnderTemperature [Supply Air Temperature] has dropped below [Low Supply Air
Temperature Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5019 |
| lgpCondId5023ReturnAirOverTemperature [Return Air Temperature] has exceeded [High Return Air Temperature
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5023 |
| lgpCondId5026SupplyAirSensorIssue The air sensor at the outlet of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5026 |
| lgpCondId5034HighReturnHumidity [Return Humidity] has exceeded [High Return Humidity Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5034 |
| lgpCondId5036LowReturnHumidity [Return Humidity] has dropped below [Low Return Humidity
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5036 |
| lgpCondId5037HumidifierHoursExceeded Operating hours for the humidifier have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5037 |
| lgpCondId5038DehumidifierHoursExceeded Operating hours for the dehumidifier have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5038 |
| lgpCondId5039HumidifierUnderCurrent The electrical current to the humidifier has dropped below its
lower threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5039 |
| lgpCondId5040HumidifierOverCurrent The electrical current to the humidifier has exceeded its upper
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5040 |
| lgpCondId5041HumidifierLowWater The water level in the humidifier has dropped below its threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5041 |
| lgpCondId5042HumidifierCylinderWorn Humidifier cylinder is not operating properly and needs to be
replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5042 |
| lgpCondId5043HumidifierIssue Humidifier issue detected, causing it to be locked out. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5043 |
| lgpCondId5044ExtHumidifierLockout The humidifier is shut down and disabled by an external input
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5044 |
| lgpCondId5045HumidifierControlBoardNotDetected Humidifier control board is required to be connected, but no
signal is detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5045 |
| lgpCondId5046ReturnHumidityOutOfProportionalBand [Return Humidity] has exceeded the upper limit of
[Dehumidification Proportional Band], or has dropped below the
lower limit of [Humidification Proportional Band] ], for an
extend… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5046 |
| lgpCondId5053LossofAirFlow No air flow through the unit due to failure of all fans. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5053 |
| lgpCondId5054FanHoursExceeded Operating hours for the unit blower fan have exceeded the
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5054 |
| lgpCondId5055TopFanIssue The top fan is not operating within its normal parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5055 |
| lgpCondId5056BottomFanIssue The bottom fan is not operating within its normal parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5056 |
| lgpCondId5060RemoteSensorIssue Remote sensor is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5060 |
| lgpCondId5062Compressor1LowSuctionPressure Compressor 1 low suction pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5062 |
| lgpCondId5063Compressor1HoursExceeded Operating hours for compressor 1 have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5063 |
| lgpCondId5064DigScrollComp1TempSensorIssue Digital scroll compressor 1 temperature sensor is disconnected or
the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5064 |
| lgpCondId5065DigScrollComp1OverTemp Digital scroll compressor 1 shut off because its head temperature
has exceeded the upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5065 |
| lgpCondId5066Compressor1LowPressureTransducerIssue Compressor 1 low pressure transducer is disconnected or the signal
is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5066 |
| lgpCondId5067ExtCompressorLockout The compressor is shut down and disabled by an external input
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5067 |
| lgpCondId5068ReheaterOverTemperature The temperature of the reheater has exceeded its threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5068 |
| lgpCondId5069ElectricReheater1HoursExceeded Operating hours for electric reheater 1 have exceeded the
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5069 |
| lgpCondId5070ExtReheatLockout The reheater is shut down and disabled by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5070 |
| lgpCondId5071Condenser1Issue Condenser 1 is not operating within its normal parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5071 |
| lgpCondId5072CondenserVFDIssue The condenser fan Variable Frequency Drive is offline. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5072 |
| lgpCondId5073CondenserTVSSIssue The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5073 |
| lgpCondId5104ExtOverTemperature A temperature has exceeded its threshold, as indicated by an
external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5104 |
| lgpCondId5105ExtLossofFlow Loss of flow is detected, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5105 |
| lgpCondId5106ExtCondenserPumpHighWater High water is detected in the condensate pump by the auxiliary
float, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5106 |
| lgpCondId5107ExtStandbyGlycolPumpOn The standby glycol pump is on, as indicated by an external input
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5107 |
| lgpCondId5108ExternalFireDetected Fire detected, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5108 |
| lgpCondId5109UnitOn Unit was turned on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5109 |
| lgpCondId5110UnitOff Unit was turned off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5110 |
| lgpCondId5111UnitStandby Unit was placed in standby mode. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5111 |
| lgpCondId5112UnitPartialShutdown An event has occurred requiring some system components to be
shutdown and disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5112 |
| lgpCondId5113UnitShutdown An event has occurred requiring the unit to be shutdown and
disabled to prevent damage to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5113 |
| lgpCondId5114WaterLeakageDetectorSensorIssue The water leakage detector sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5114 |
| lgpCondId5115BMSCommunicationsTimeout Building Management System (or external monitoring system) has not
communicated with the system within the expected timeframe. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5115 |
| lgpCondId5116MaintenanceDue The calculated maintenance date has been reached. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5116 |
| lgpCondId5117MaintenanceCompleted Maintenance has been completed on the unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5117 |
| lgpCondId5118CloggedAirFilter Air filter is dirty and needs to be (cleaned or) replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5118 |
| lgpCondId5119RAMBatteryIssue RAM or RAM backup battery is not operating correctly. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5119 |
| lgpCondId5120MasterUnitCommunicationLost Communication with master unit has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5120 |
| lgpCondId5121HighPowerShutdown Supply to high power components has been shutdown. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5121 |
| lgpCondId5126DigScrollComp2OverTemp Digital scroll compressor 2 shut off because its head temperature
has exceeded the upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5126 |
| lgpCondId5144OutputOfUf The output frequency has exceeded a specified range for a
specified period of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5144 |
| lgpCondId5145MMSModuleAlarmActive Active alarm or fault of any module in a multi-module system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5145 |
| lgpCondId5146CompressorPumpDownIssue Unable to pump down suction-side pressure during compressor
shutdown. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5146 |
| lgpCondId5147ReturnAirSensorIssue The air sensor at the inlet of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5147 |
| lgpCondId5148CompressorHighPressureTransducerIssue Compressor high pressure transducer is disconnected or the signal
is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5148 |
| lgpCondId5149BatteryNotQualified The UPS battery voltage is not qualified. This event will be
detected even in the absence of battery disconnect or when it is
open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5149 |
| lgpCondId5150BatteryTerminalsReversed The measured battery voltage is a negative value due to reverse
battery terminal connections. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5150 |
| lgpCondId5151BatteryConverterFailure Battery converter failure. This is a summary event caused by one
or more power sub-modules in a UPS module. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5151 |
| lgpCondId5152InverterSCROpen The system has detected an open across one or more inverter static
switch Silicon Controlled Rectifiers. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5152 |
| lgpCondId5153LoadSharingFault Difference between any phase inverter current of unit and the
relevant average output current of parallel system is more than a
specific percent of nominal current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5153 |
| lgpCondId5154DCBusAbnormal The system has detected an abnormal DC Bus Voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5154 |
| lgpCondId5155MainsInputNeutralLost Loss of neutral in the input source is detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5155 |
| lgpCondId5156LoadImpactTransfer On bypass as result of load impact. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5156 |
| lgpCondId5157UserOperationInvalid User attempted an invalid operation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5157 |
| lgpCondId5158PowerSubModuleFault One or more failures detected in power module, inverter or
rectifier. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5158 |
| lgpCondId5178OutputOvervoltage One or more of the output phase voltages has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5178 |
| lgpCondId5179OutputUndervoltage One or more of the output phase voltages has dropped below the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5179 |
| lgpCondId5180OutputOvercurrent One or more of the phase currents has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5180 |
| lgpCondId5181NeutralOvercurrent The system's neutral current has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5181 |
| lgpCondId5182GroundOvercurrent System ground current has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5182 |
| lgpCondId5183OutputVoltageTHD The Total Harmonic Distortion of the voltage on one or more of the
output phases has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5183 |
| lgpCondId5184OutputFrequencyError The output frequency is outside a specified range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5184 |
| lgpCondId5185TransformerOvertemperature Indicates a unit transformer overtemperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5185 |
| lgpCondId5212PanelSummaryStatus The status for the panel. Detects and annunciates upon occurrence
of any branch or panelboard main breaker active event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5212 |
| lgpCondId5213PanelOvervoltage One or more of the phase voltages of this panel has exceeded the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5213 |
| lgpCondId5214PanelUndervoltage One or more of the phase voltages of this panel is less than the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5214 |
| lgpCondId5215PanelOvercurrent One or more of the phase currents of this panel has exceeded the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5215 |
| lgpCondId5216PanelNeutralOvercurrent The Neutral current of this panel has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5216 |
| lgpCondId5217PanelGroundOvercurrent The Ground current of this panel has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5217 |
| lgpCondId5226BranchOvercurrent The current in one or more phases of this branch exceeds the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5226 |
| lgpCondId5227BranchUndercurrent The current in one or more phases of this branch is less than the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5227 |
| lgpCondId5245SubfeedPhaseOvercurrent One or more of the phase currents in this subfeed has exceeded the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5245 |
| lgpCondId5246SubfeedNeutralOvercurrent The Neutral current in this subfeed has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5246 |
| lgpCondId5247SubfeedGroundOvercurrent The Ground current of this subfeed has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5247 |
| lgpCondId5249EventState The present state of this digital event input. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5249 |
| lgpCondId5263CompressorNotStopping Compressor commanded to stop, but continues to run. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5263 |
| lgpCondId5269CompressorHoursExceeded [Compressor Hours] has exceeded [Compressor Hours Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5269 |
| lgpCondId5270CompressorHighHeadPressure Compressor is shut down due to high head pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5270 |
| lgpCondId5271CompressorLowSuctionPressure Compressor is shut down due to low suction pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5271 |
| lgpCondId5272CompressorThermalOverload Compressor is shut down due to thermal overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5272 |
| lgpCondId5273CompressorLowOilPressure Compressor low oil pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5273 |
| lgpCondId5274CompressorHeadPressureOverThreshold Compressor head pressure has exceeded an upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5274 |
| lgpCondId5275CompressorLossofDifferentialPressure Compressor is shut down due to low differential pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5275 |
| lgpCondId5277CondenserFanIssue Condenser fan is not operating within its operational parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5277 |
| lgpCondId5278LowCondenserRefrigerantPressure Refrigerant pressure in condenser coil is too low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5278 |
| lgpCondId5280LowFluidPressure [Fluid Pressure] has dropped below a specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5280 |
| lgpCondId5293ReturnFluidOverTemp [Return Fluid Temperature] has exceeded a specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5293 |
| lgpCondId5294ReturnFluidUnderTemp [Return Fluid Temperature] has dropped below a specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5294 |
| lgpCondId5295ReturnFluidTempSensorIssue The return fluid temperature sensor is disconnected or the signal
is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5295 |
| lgpCondId5296TeamworkReturnFluidTempSensorIssue The return fluid temperature sensors for all Teamwork units are
disconnected or the signals are out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5296 |
| lgpCondId5297AllPumpsLossofFlow System is shut down due to loss of flow in all available pumps. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5297 |
| lgpCondId5300PumpHoursExceeded [Pump Hours] has exceeded [Pump Hours Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5300 |
| lgpCondId5306FreeCoolingValveHoursExceeded [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5306 |
| lgpCondId5308EvaporatorInletTempSensorIssue The evaporator inlet temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5308 |
| lgpCondId5309TeamworkEvaporatorInletTempSensorIssue The evaporator inlet temperature sensors for all Teamwork units
are disconnected or the signals are out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5309 |
| lgpCondId5310EvaporatorFluidFreezeAutoReset Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down, but will restart when
the temperature rises above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5310 |
| lgpCondId5311EvaporatorFluidFreezeManualResetRequired Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down and requires a manual
reset. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5311 |
| lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss While subgroup unit communication was lost, an event occurred on
the subgroup unit. Please check subgroup unit event log. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5315 |
| lgpCondId5335ReturnAirUnderTemperature [Return Air Temperature] has dropped below [Low Return Air
Temperature Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5335 |
| lgpCondId5349ExtAirSensorAHighHumidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
Humidity Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5349 |
| lgpCondId5351ExtAirSensorALowHumidity [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
Low Humidity Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5351 |
| lgpCondId5352CompressorShortCycle Compressor short cycle. A short cycle is defined as turning on and
off a number of times over a set time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5352 |
| lgpCondId5354DigScrollCompDischargeTempSensorIssue Digital scroll compressor discharge temperature sensor is
disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5354 |
| lgpCondId5355DigScrollCompOverTemp Digital scroll compressor is shut down due to head temperature
exceeding an upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5355 |
| lgpCondId5361ExtFreeCoolingLockout Free cooling is disabled by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5361 |
| lgpCondId5362FreeCoolingTempSensorIssue The free cooling fluid temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5362 |
| lgpCondId5365HotWaterHotGasValveHoursExceeded [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
Gas Valve Hours Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5365 |
| lgpCondId5368ElectricReheaterHoursExceeded [Electric Reheater Hours] has exceeded [Electric Reheaters Hours
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5368 |
| lgpCondId5376MainFanOverload Main fan is shut down due to thermal overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5376 |
| lgpCondId5377Condenser Condenser is not operating within its operational parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5377 |
| lgpCondId5415ExtLossofAirBlower Loss of air blower is detected, as indicated by an external input
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5415 |
| lgpCondId5416ExtStandbyUnitOn Standby unit is on, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5416 |
| lgpCondId5417DigitalOutputBoardNotDetected Digital output board is required to be connected, but no signal is
detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5417 |
| lgpCondId5418UnitCodeMissing Unit code has not been entered and saved. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5418 |
| lgpCondId5419UnitCommunicationLost Master has lost communication with one or more networked units. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5419 |
| lgpCondId5422OvertemperaturePowerOff Power turned off because equipment over temperature limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5422 |
| lgpCondId5423TooManySensors The number of sensors connected to the PDU exceeds the allowable
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5423 |
| lgpCondId5432TransformerOvertemperaturePowerOff Output power shutdown due to high transformer temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5432 |
| lgpCondId5433TransformerOvertemperature Transformer temperature has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5433 |
| lgpCondId5434TransformerTemperatureSensorFail Transformer temperature sensor has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5434 |
| lgpCondId5436LowAmbientTemperatureProbeTwo The system has detected a low ambient temperature condition on
temperature probe 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5436 |
| lgpCondId5437HighAmbientTemperatureProbeTwo The system has detected a high ambient temperature condition on
temperature probe 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5437 |
| lgpCondId5438ThermalRunawayDetected The system has detected a thermal runaway condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5438 |
| lgpCondId5439BatteryStringEqualize The system has detected a battery string equalize condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5439 |
| lgpCondId5440BatteryStringOffline The system has detected the battery string is offline. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5440 |
| lgpCondId5442DischargeLowCellVoltage The system has detected a low cell voltage condition during a
discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5442 |
| lgpCondId5447MMSPowerSharing A module is not sharing power with the other modules in a multi
-module system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5447 |
| lgpCondId5453ModuleInStandbyIntelligentParalleling Module is placed into standby operation per Intelligent
Paralleling. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5453 |
| lgpCondId5456ECOModeActive Conditions for Activation or Automatic Reactivation have been
satisfied. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5456 |
| lgpCondId5457ECOModeSuspended ECO Mode session is suspended. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5457 |
| lgpCondId5458ExcessECOSuspends Number of automatic suspensions has exceeded the ECO Mode -
Maximum Auto Suspensions setting. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5458 |
| lgpCondId5471DoorOpen An open door was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5471 |
| lgpCondId5472DoorSensorDisconnected Door sensor disconnect detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5472 |
| lgpCondId5479ContactClosureOpen An open circuit was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5479 |
| lgpCondId5480ContactClosureClosed A closed circuit was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5480 |
| lgpCondId5492ExtSystemCondensationDetected External system condensation detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5492 |
| lgpCondId5495ExtFanIssue One or more fans are not operating within their operational
parameters. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5495 |
| lgpCondId5500ExtRemoteShutdown Unit is shut down by a remote signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5500 |
| lgpCondId5505HotAisleTempOutofRange The air temperature in the Hot aisle is either above [Hot Aisle
Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5505 |
| lgpCondId5508ColdAisleTempOutofRange The air temperature in the cold aisle is either above [Cold Aisle
Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5508 |
| lgpCondId5512RemoteShutdown Unit is shut down by a remote signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5512 |
| lgpCondId5513CompressorCapacityReduced Compressor capacity has been reduced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5513 |
| lgpCondId5514CompressorLowPressureTransducerIssue Compressor low pressure transducer is disconnected or the signal
is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5514 |
| lgpCondId5524PDUNeutralOverCurrent The system has detected a neutral over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5524 |
| lgpCondId5531CondenserCommunicationLost Communication with condenser unit has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5531 |
| lgpCondId5535CondenserOutsideAirTempSensorIssue Condenser outside air temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5535 |
| lgpCondId5536CondenserOutsideAirTempOutofOperatingRange [Condenser Outside Air Temperature] is either above an upper
threshold or below a lower threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5536 |
| lgpCondId5537CondenserControlBoardIssue The condenser control board is reporting an issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5537 |
| lgpCondId5539CondenserRefrigerantPressureOverThreshold Condenser refrigerant pressure has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5539 |
| lgpCondId5540CondenserRefrigerantPressureUnderThreshold Condenser refrigerant pressure has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5540 |
| lgpCondId5541CondenserRefrigerantPressureSensorIssue Condenser refrigerant pressure sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5541 |
| lgpCondId5542CondenserSupplyRefrigerantOverTemp Condenser supply refrigerant temperature has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5542 |
| lgpCondId5543CondenserSupplyRefrigerantUnderTemp Condenser supply refrigerant temperature has dropped below a
specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5543 |
| lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue Condenser supply refrigerant temperature sensor is disconnected or
the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5544 |
| lgpCondId5545CondenserMaxFanSpeedOverride Fan speed exceeding the maximum set point in order to alleviate a
high temperature or pressure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5545 |
| lgpCondId5559EvaporatorReturnFluidOverTemp [Evaporator Return Fluid Temperature] has exceeded a threshold.
The event is deactivated when the temperature drops below the
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5559 |
| lgpCondId5560EvaporatorReturnFluidUnderTemp [Evaporator Return Fluid Temperature] has dropped below a
threshold. The event is deactivated when the temperature rises
above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5560 |
| lgpCondId5561LBSActiveMaster This UPS system has been selected as the functional Master Load
Bus Synchronization (LBS) system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5561 |
| lgpCondId5562LBSActiveSlave This UPS system is synchronized to the output bus of the UPS
system that has been selected as the Master Load Bus
Synchronization (LBS) system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5562 |
| lgpCondId5563DCBusLowFault The DC Bus voltage has reached a critical low level. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5563 |
| lgpCondId5564FanContactorOpen The fan contactor is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5564 |
| lgpCondId5565FanContactorOpenFail The fan contactor failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5565 |
| lgpCondId5566FanContactorCloseFail The fan contactor failed to close. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5566 |
| lgpCondId5567IPInhibit The intelligent paralleling operation is inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5567 |
| lgpCondId5568InputUndervoltage One or more of the input phase voltages has dropped below the
limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5568 |
| lgpCondId5569InputOvervoltage One or more of the input phase voltages has exceeded the limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5569 |
| lgpCondId5573AmbientAirSensorIssue Ambient air sensor is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5573 |
| lgpCondId5577ExtDewPointUnderTemperature At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
below [Ext Dew Point Under Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5577 |
| lgpCondId5578DewPointOverTemperature Dew point temperature reading has exceeded the upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5578 |
| lgpCondId5579DewPointUnderTemperature Dew point temperature reading has dropped below the lower
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5579 |
| lgpCondId5588UnspecifiedGeneralEvent One or more unspecified events active. See local unit display for
further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5588 |
| lgpCondId5593RemoteSensorAverageOverTemperature [Remote Sensor Average Temperature] has exceeded [Remote Sensor
Over Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5593 |
| lgpCondId5594RemoteSensorAverageUnderTemperature [Remote Sensor Average Temperature] has dropped below [Remote
Sensor Under Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5594 |
| lgpCondId5595RemoteSensorSystemAverageOverTemperature [Remote Sensor System Average Temperature] has exceeded [Remote
Sensor Over Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5595 |
| lgpCondId5596RemoteSensorSystemAverageUnderTemperature [Remote Sensor System Average Temperature] has dropped below
[Remote Sensor Under Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5596 |
| lgpCondId5597RemoteSensorOverTemperature [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5597 |
| lgpCondId5598RemoteSensorUnderTemperature [Remote Sensor Temperature] has dropped below [Remote Sensor Under
Temp Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5598 |
| lgpCondId5600AirEconomizerEmergencyOverride Indoor room temperature has exceeded its upper threshold and the
outdoor air damper has been opened for emergency cooling. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5600 |
| lgpCondId5601AirEconomizerReducedAirflow Air economizer filter is dirty and needs to be cleaned or replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5601 |
| lgpCondId5604CompressorSuperheatOverThreshold Compressor discharge refrigerant superheat temperature has
exceeded an upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5604 |
| lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent The delta temperature between a cell temperature and the ambient
temperature has exceeded the thermal runaway cell to ambient
temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5609 |
| lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent The delta temperature between two cells has exceeded the thermal
runaway cell to cell temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5610 |
| lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent The Battery-String charger current has exceeded the thermal
runaway charger current level one threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5611 |
| lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent The Battery-String charger current has exceeded the thermal
runaway charger current level two threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5612 |
| lgpCondId5617TemperatureControlSensorIssue The air sensor selected for cooling control is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5617 |
| lgpCondId5621EEVSuperheatBelowThreshold Electronic expansion valve refrigerant low superheat event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5621 |
| lgpCondId5622EEVDischargeTempAboveThreshold Electronic expansion valve refrigerant high discharge temperature
event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5622 |
| lgpCondId5623EEVBatteryIssue Electronic expansion valve battery cannot be recharged and needs
to be replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5623 |
| lgpCondId5624EEVPowerIssue Electronic expansion valve lost power and is running on battery
backup. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5624 |
| lgpCondId5625EEVUnspecifiedGeneralEvent One or more unspecified electronic expansion valve events active.
See local unit display for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5625 |
| lgpCondId5629StaticPressureSensorIssue The static pressure sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5629 |
| lgpCondId5630HighStaticPressure High static pressure event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5630 |
| lgpCondId5631LowStaticPressure Low static pressure event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5631 |
| lgpCondId5636PumpUnspecifiedGeneralEvent One or more unspecified pump events active. See local unit display
for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5636 |
| lgpCondId5637CondenserUnitUnspecifiedGeneralEvent One or more unspecified condenser unit events active. See local
unit display for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5637 |
| lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent One or more unspecified condenser circuit events active. See local
unit display for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5638 |
| lgpCondId5642SFAReservedEvent1 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5642 |
| lgpCondId5643SFAReservedEvent2 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5643 |
| lgpCondId5644SFAReservedEvent3 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5644 |
| lgpCondId5645SFAReservedEvent4 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5645 |
| lgpCondId5646SFAReservedEvent5 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5646 |
| lgpCondId5647SFAReservedEvent6 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5647 |
| lgpCondId5648SFAReservedEvent7 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5648 |
| lgpCondId5649SFAReservedEvent8 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5649 |
| lgpCondId5650SFAReservedEvent9 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5650 |
| lgpCondId5651SFAReservedEvent10 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5651 |
| lgpCondId5652SFAReservedEvent11 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5652 |
| lgpCondId5653SFAReservedEvent12 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5653 |
| lgpCondId5654SFAReservedEvent13 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5654 |
| lgpCondId5655SFAReservedEvent14 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5655 |
| lgpCondId5656SFAReservedEvent15 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5656 |
| lgpCondId5657SFAReservedEvent16 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5657 |
| lgpCondId5658SFAReservedEvent17 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5658 |
| lgpCondId5659SFAReservedEvent18 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5659 |
| lgpCondId5660SFAReservedEvent19 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5660 |
| lgpCondId5661SFAReservedEvent20 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5661 |
| lgpCondId5662SFAReservedEvent21 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5662 |
| lgpCondId5663SFAReservedEvent22 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5663 |
| lgpCondId5664SFAReservedEvent23 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5664 |
| lgpCondId5665SFAReservedEvent24 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5665 |
| lgpCondId5666SFAReservedEvent25 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5666 |
| lgpCondId5768OutletAirOvertemperatureLimit The difference between the outlet air temperature and inlet air
temperature exceeds a specified maximum temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5768 |
| lgpCondId5769EMOShutdown An Emergency Module Off command has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5769 |
| lgpCondId5770TopOutletFanFault Top outlet fan fault - one or more top outlet fans have failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5770 |
| lgpCondId5771MMSOverCapacity The multi-module system load is larger than the apparent power
limit setting. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5771 |
| lgpCondId5773CompressorCapacityNormal Compressor has returned to normal load capacity. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5773 |
| lgpCondId5774CompressorContactorIssue Compressor contactor is not closing during compressor startup or
is not opening during compressor shutdown. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5774 |
| lgpCondId5775UnitShutdownUnspecifiedGeneralEvent One or more unspecified unit shutdown events active. See local
unit display for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5775 |
| lgpCondId5776PDULowVoltageLN The system has detected a module under voltage condition (LN). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5776 |
| lgpCondId5777PDULowVoltageLL The system has detected a module under voltage condition (LL). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5777 |
| lgpCondId5778PDULowVoltageL1L2 The system has detected a line-to-line under voltage condition (L1
-L2). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5778 |
| lgpCondId5779PDULowVoltageL2L3 The system has detected a line-to-line under voltage condition (L2
-L3). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5779 |
| lgpCondId5780PDULowVoltageL3L1 The system has detected a line-to-line under voltage condition (L3
-L1). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5780 |
| lgpCondId5781PDULowVoltageL1N The system has detected a line to neutral under voltage condition
(L1-N). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5781 |
| lgpCondId5782PDULowVoltageL2N The system has detected a line to neutral under voltage condition
(L2-N). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5782 |
| lgpCondId5783PDULowVoltageL3N The system has detected a line to neutral under voltage condition
(L3-N). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5783 |
| lgpCondId5784BranchLowVoltageLN The system has detected a module under voltage condition (LN). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5784 |
| lgpCondId5785BranchLowVoltageLL The system has detected a module under voltage condition (LL). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5785 |
| lgpCondId5786BranchLowVoltage The system has detected a module under voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5786 |
| lgpCondId5788ContTieActive Continuous Power Tie Active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5788 |
| lgpCondId5792UserkWhReset The user kWh accumulator was reset to zero by the operator. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5792 |
| lgpCondId5796PeakkWReset The Peak kW was reset. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5796 |
| lgpCondId5798BypassOverload Bypass overloaded, reduce load immediately. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5798 |
| lgpCondId5801LowBatteryShutdownImminent If active and guaranteed shutdown is enabled, a low battery
reserve condition exists that will shutdown the UPS. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5801 |
| lgpCondId5806OutputOverload An overload exists on the output. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5806 |
| lgpCondId5807OutputOffPending Output off pending - shutdown imminent. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5807 |
| lgpCondId5808SystemShutdownOutputShort Shutdown was due to a short on the output. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5808 |
| lgpCondId5809SystemShutdownLowBattery Shutdown was due to a low battery condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5809 |
| lgpCondId5810SystemShutdownRemoteShutdown Shutdown was due to a remote communications shutdown command. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5810 |
| lgpCondId5811SystemShutdownHardwareFault Shutdown was due to an externally applied hardware control signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5811 |
| lgpCondId5817LossofRedundancy The system has an insufficient number of power modules to provide
redundancy. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5817 |
| lgpCondId5818PowerModuleFailure One or more conditions indicate a power module failure, service is
required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5818 |
| lgpCondId5819PowerModuleWarning One or more power modules is reporting a warning condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5819 |
| lgpCondId5838PowerModuleFanFault The Power Module has detected a fan fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5838 |
| lgpCondId5839PowerModuleOverTemperature The Power Module has detected an over temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5839 |
| lgpCondId5840PowerModuleShutdownOverTemperature Power Module has shutdown due to over temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5840 |
| lgpCondId5842ChargerModuleFanFault The Charger Module has detected a fan fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5842 |
| lgpCondId5847BatteryModuleTemperatureSensorFault A Battery Module temperature sensor fault has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5847 |
| lgpCondId5848BatteryModuleOverTemperature The Battery Module has detected an over temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5848 |
| lgpCondId5849ReplaceBatteryModule The Battery Module needs to be replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5849 |
| lgpCondId5850SystemShutdownTransformerOverTemperature System shutdown due to transformer over temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5850 |
| lgpCondId5851MaximumLoadAlarm Maximum load alarm indicating load setting has been exceeded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5851 |
| lgpCondId5856BatteryModuleFault One or more battery modules are reporting a fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5856 |
| lgpCondId5857BatteryModuleWarning One or more battery modules are reporting a warning condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5857 |
| lgpCondId5862CheckAirFilter Please check air filter, it may need to be cleaned or replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5862 |
| lgpCondId5863TransformerFanFault The transformer fan has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5863 |
| lgpCondId5865NoLoadWarning Indicates the UPS has output voltage but the output current is
below a set threshold [No Load Warning Current Threshold] for a
set period of time [No Load Warning Delay]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5865 |
| lgpCondId5871BatteryOverTemperatureLimit A battery temperature sensor is reporting a value above a
predetermined limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5871 |
| lgpCondId5873UnexpectedMainBatteryDisconnectClosure The main battery disconnect has closed unexpectedly. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5873 |
| lgpCondId5874BatteryOverVoltage The system has detected that the battery voltage has exceeded a
predetermined limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5874 |
| lgpCondId5875BatteryFuseFault One or more battery fuse faults has occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5875 |
| lgpCondId5878MainBatteryDisconnectForcedToUnlock The main battery disconnect is forced to the unlocked state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5878 |
| lgpCondId5879VdcBackfeed The voltage between battery and DC bus measurements is out of
tolerance. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5879 |
| lgpCondId5880RectifierConfigurationChangeRequest This event indicates that the battery is not configured and PFC is
not enabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5880 |
| lgpCondId5881RegenerationActive Regeneration operation is active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5881 |
| lgpCondId5882RegenerationOperationTerminated Regeneration operation is not active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5882 |
| lgpCondId5883RegenerationOperationFailure Regeneration operation has been terminated due to bypass source
instability or unit misoperation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5883 |
| lgpCondId5884ProgramInputContact01 When the signal from [Program Input Contact 01] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5884 |
| lgpCondId5885ProgramInputContact02 When the signal from [Program Input Contact 02] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5885 |
| lgpCondId5886ProgramInputContact03 When the signal from [Program Input Contact 03] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5886 |
| lgpCondId5887ProgramInputContact04 When the signal from [Program Input Contact 04] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5887 |
| lgpCondId5888ProgramInputContact05 When the signal from [Program Input Contact 05] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5888 |
| lgpCondId5889ProgramInputContact06 When the signal from [Program Input Contact 06] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5889 |
| lgpCondId5890ProgramInputContact07 When the signal from [Program Input Contact 07] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5890 |
| lgpCondId5891ProgramInputContact08 When the signal from [Program Input Contact 08] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5891 |
| lgpCondId5892ProgramInputContact09 When the signal from [Program Input Contact 09] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5892 |
| lgpCondId5893ProgramInputContact10 When the signal from [Program Input Contact 10] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5893 |
| lgpCondId5894ProgramInputContact11 When the signal from [Program Input Contact 11] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5894 |
| lgpCondId5895ProgramInputContact12 When the signal from [Program Input Contact 12] is active the
function assigned to this contact is executed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5895 |
| lgpCondId5896GroundFaultDetected The system has detected a ground fault on a Battery-String. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5896 |
| lgpCondId5902ReturnHumiditySensorIssue The humidity sensor at the inlet of the unit is disconnected or
the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5902 |
| lgpCondId5903CompressorLowDifferentialPressureLockout Compressor exceeded maximum startup attempts due to low
differential pressure. Compressor is shutdown and has been
disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5903 |
| lgpCondId5906AirflowSensorIssue Airflow sensor is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5906 |
| lgpCondId5907ExtAirDamperPositionIssue Air damper position does not match expected value, as indicated by
an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5907 |
| lgpCondId5908ExtPowerSourceAFailure Unit main power source A failure, as indicated by an external
input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5908 |
| lgpCondId5909ExtPowerSourceBFailure Unit main power source B failure, as indicated by an external
input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5909 |
| lgpCondId5910StaticPressureSensorOutofRange Static pressure sensor signal is out of its configured range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5910 |
| lgpCondId5911FluidTemperatureSensorIssue The fluid temperature sensor is disconnected or the signal is out
of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5911 |
| lgpCondId5912FluidFlowSensorIssue The fluid flow sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5912 |
| lgpCondId5914OverDifferentialPressure An over differential pressure condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5914 |
| lgpCondId5915UnderDifferentialPressure An under differential pressure condition was detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5915 |
| lgpCondId5924MixedModeLockout Mixed mode has been entered too many times over a rolling time
period and has been temporarily disabled. Mixed mode is defined
as the use of a compressor on one refrigeration cir… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5924 |
| lgpCondId5928UnbalancedLoadCondition The system has detected a line-to-line unbalanced load condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5928 |
| lgpCondId5939BranchOverCurrentProtection The Branch Receptacle Module's over current protection is
triggered. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5939 |
| lgpCondId5948BranchLowVoltageLL The system has detected a module under voltage condition (LL). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5948 |
| lgpCondId5957BypassInputVoltageFault The system has detected the bypass voltage is unqualified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5957 |
| lgpCondId5958BatteryTemperatureOutofRange Battery temperature is outside of acceptable range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5958 |
| lgpCondId5960InverterOverload Inverter in overload fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5960 |
| lgpCondId5966AuxAirTempDeviceCommunicationLost Communication with external auxiliary device providing an air
temperature value has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5966 |
| lgpCondId5967ModbusPowerMeterCommunicationLost Communication with Modbus power meter has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5967 |
| lgpCondId5968InverterDesaturation Inverter Desaturation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5968 |
| lgpCondId5969GenericDICFault The control board reports a fault - Service required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5969 |
| lgpCondId5970GroundFault An AC phase to ground fault or three phase fault to ground exists
on the output of the UPS. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5970 |
| lgpCondId5973InputBreakerOpen The main input breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5973 |
| lgpCondId5974NeutralBreakerOpen The neutral breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5974 |
| lgpCondId5975OutputBreakerOpen The output breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5975 |
| lgpCondId5976MaintenanceBypassBreakerClosed The maintenance bypass breaker is closed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5976 |
| lgpCondId5977BatteryBreakerOpen The battery circuit is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5977 |
| lgpCondId5978RectifierIsolationBreakerRFBOpen The rectifier isolation breaker (RFB) indicates that it is in the
open position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5978 |
| lgpCondId5982BypassBreakerSBBOpen The bypass circuit breaker (SBB) indicates that it is in the open
position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5982 |
| lgpCondId5983BypassIsolationBreakerBIBOpen The bypass isolation breaker (BIB) indicates that it is in the
open position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5983 |
| lgpCondId5984BypassUndervoltageWarning The voltage on one or more bypass phases is less than a specified
percentage of the nominal voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5984 |
| lgpCondId5985BypassStaticSwitchBPSSOn The Bypass Static Switch has been turned on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5985 |
| lgpCondId5998BattOvtempWarning A battery temperature sensor is reporting a value above the
setpoint. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.5998 |
| lgpCondId6009InverterOutputBreakerOpen The inverter output breaker indicates that it is in the open
position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6009 |
| lgpCondId6011EquipmentOverTempWarning Equipment over temperature warning is a summary event based on the
detection of at least one measured temperature exceeding a
threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6011 |
| lgpCondId6012EquipmentOvertemperatureLimit The equipment air temperature has exceeded its maximum set point. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6012 |
| lgpCondId6045RectifierInputBreakerOpen The rectifier isolation breaker indicates that it is in the open
position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6045 |
| lgpCondId6046LoadonUPS The output is being supplied power from the inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6046 |
| lgpCondId6047Core2CoreFuseFailure Core-2-core fuse failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6047 |
| lgpCondId6052SystemOutputBreakerOpen The system output breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6052 |
| lgpCondId6059InverterRelayFault The inverter relay has malfunctioned. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6059 |
| lgpCondId6060TransfertoBypassSystemOverload The UPS System has transferred to bypass because the active power
modules cannot support the critical load. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6060 |
| lgpCondId6061InputSourceBackfeed The battery is backfeeding the input source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6061 |
| lgpCondId6062LossofSynchronization The inverter and bypass are no longer synchronized. . | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6062 |
| lgpCondId6063BatteryConverterCurrentLimit The battery converter has reached is maximum current limit. . | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6063 |
| lgpCondId6064LBSCableFailure Load Bus Sync communications is abnormal. A problem with the LBS
cable may exist. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6064 |
| lgpCondId6065BatteryChargeEqualizationTimeout The battery equalizing is time out. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6065 |
| lgpCondId6066ParallelCableFailure The UPS parallel system communications is abnormal. A problem with
the parallel cable may exist. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6066 |
| lgpCondId6067BatteryFault A short circuit exists in the battery system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6067 |
| lgpCondId6068BatteryRoomAlarm The ambient temperature of the battery room is abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6068 |
| lgpCondId6080UPSCCommunicationFailure The UPSC has failed to communicate in a designated time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6080 |
| lgpCondId6092Compressor1BThermalOverload Fixed compressor 1B is shut down due to thermal overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6092 |
| lgpCondId6093Compressor2BThermalOverload Fixed compressor 2B is shut down due to thermal overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6093 |
| lgpCondId6094Compressor1BHoursExceeded Fixed compressor 1B run hours have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6094 |
| lgpCondId6095Compressor2BHoursExceeded Fixed compressor 2B run hours have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6095 |
| lgpCondId6100CondenserRemoteShutdown Condenser is shut down by a remote signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6100 |
| lgpCondId6105ExternalCondenserTVSSIssue The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed, as indicated by an external input
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6105 |
| lgpCondId6106ExternalCondenserVFDIssue The condenser fan Variable Frequency Drive is offline, as
indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6106 |
| lgpCondId6107ExternalCondenserIssue Condenser is not operating within its operational parameters, as
indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6107 |
| lgpCondId6119Slotsnotavailable The number of sensors exceeds the number of allocated slots and
cannot be displayed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6119 |
| lgpCondId6180BatteryUnderVoltage Battery voltage is too low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6180 |
| lgpCondId6182ReplaceBattery The battery is due for replacement. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6182 |
| lgpCondId6186InputFrequencyDeviation The input frequency is outside of the normal range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6186 |
| lgpCondId6187ShutdownPending Shutdown is pending. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6187 |
| lgpCondId6194SystemRebootCommandIssued Reboot command issued to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6194 |
| lgpCondId6203SensorAdded Sensor Added. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6203 |
| lgpCondId6204SensorRemoved Sensor Removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6204 |
| lgpCondId6205WaterLeakDetected Water leak detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6205 |
| lgpCondId6210FirmwareUpdateInProgress Firmware update has started and is in progress. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6210 |
| lgpCondId6211FirmwareUpdateCompletedSuccessfully Firmware update has completed successfully. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6211 |
| lgpCondId6212FirmwareUpdateCompletedUnsuccessfully Firmware update has completed, but was not successful. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6212 |
| lgpCondId6216PrechargeCircuitFailed DC Bus precharge/discharge didn't reach specified level within a
specified time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6216 |
| lgpCondId6217MemoryCardRemoved The memory card on the control board has been removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6217 |
| lgpCondId6218AutoCalibrationActive The system is automatically calibrating ADC channels. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6218 |
| lgpCondId6219AutoCalibrationFailed ADC channel calibration has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6219 |
| lgpCondId6220ModuleOutputBreakerOpen The module output breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6220 |
| lgpCondId6221NeutralVoltageFault Voltage observed on neutral line. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6221 |
| lgpCondId6222BranchLoadLoss Loss of load on branch detected. Branch circuit breaker might be
open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6222 |
| lgpCondId6225RemoteSensorLowHumidity Remote sensor humidity has dropped below a lower threshold. The
event is deactivated when the humidity rises above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6225 |
| lgpCondId6226RemoteSensorHighHumidity Remote sensor humidity has exceeded an upper threshold. The event
is deactivated when the humidity drops below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6226 |
| lgpCondId6227RemoteSensorAverageLowHumidity The average humidity of multiple remote sensors on the cooling
unit has dropped below a lower threshold. The event is
deactivated when the humidity rises above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6227 |
| lgpCondId6229RemoteSensorSystemAverageLowHumidity The average humidity of multiple remote sensors on interconnected
cooling units in a single system has dropped below a lower
threshold. The event is deactivated when the humidit… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6229 |
| lgpCondId6230RemoteSensorSystemAverageHighHumidity The average humidity of multiple remote sensors on interconnected
cooling units in a single system has exceeded an upper threshold.
The event is deactivated when the humidity drop… | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6230 |
| lgpCondId6231LowCompressorSuperheat Compressor suction superheat has dropped below a lower threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6231 |
| lgpCondId6232SECUnspecifiedGeneralEvent One or more unspecified events active for the Superheat and
Envelope Controller. See local unit display for further details. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6232 |
| lgpCondId6233SECCommunicationLost Communication with the Superheat and Envelope Controller has been
lost. The event is deactivated when communication is re
-established. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6233 |
| lgpCondId6236PowerSourceAIssue No power is detected at power source input 'A'. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6236 |
| lgpCondId6237PowerSourceBIssue No power is detected at power source input 'B'. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6237 |
| lgpCondId6239FluidValveHoursExceeded Operating hours for the fluid valve have exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6239 |
| lgpCondId6253BoosterFailure Booster failure - boost is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6253 |
| lgpCondId6254ChargerFailure Charger Failure - Charger is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6254 |
| lgpCondId6274UnitTopReturnAirSensorFailure Return air sensor at the top of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6274 |
| lgpCondId6275UnitMiddleReturnAirSensorFailure Return air sensor in the middle of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6275 |
| lgpCondId6276UnitBottomReturnAirSensorFailure Return air sensor at the bottom of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6276 |
| lgpCondId6277UnitTopSupplyAirSensorFailure Supply air sensor at the top of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6277 |
| lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure First supply air sensor in the middle of the unit is disconnected
or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6278 |
| lgpCondId6279UnitBottomSupplyAirSensorFailure Supply air sensor at the bottom of the unit is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6279 |
| lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure Second supply air sensor in the middle of the unit is disconnected
or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6284 |
| lgpCondId6293ChilledWaterControlActive Chilled water inlet temperature control function is enabled due to
'bad' water. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6293 |
| lgpCondId6294ChilledWaterFlowTransducerFailure Chilled water flow transducer is disconnected or the signal is out
of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6294 |
| lgpCondId6295ChilledWaterInletTemperatureSensorFailure Chilled water inlet temperature sensor is disconnected or the
signal is out of range. The sensor is mandatory for the chilled
water flow function. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6295 |
| lgpCondId6296ChilledWaterHighInletTemperature Chilled water inlet temperature has exceeded an upper threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6296 |
| lgpCondId6297Modbus010VModuleCommunicationFailure Modbus 0-10V module for managing the second Chilled Water circuit
valve is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6297 |
| lgpCondId6299RackDoorsOpen Rack doors opened due to supply air temperature exceeding the
[Rack Door Open High Supply Air Temperature Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6299 |
| lgpCondId6303TeamStaticPressureSensorFailure The team static pressure sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6303 |
| lgpCondId6304HeatingLockout Heating is shut down and disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6304 |
| lgpCondId6305FreeCoolingStoppedHighRoomTemp Free cooling is temporarily disabled due to room temperature
exceeding a preset delta above the the set point. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6305 |
| lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure Cold aisle team sensor measuring air temperature and humidity is
disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6306 |
| lgpCondId6309ColdAisleAirSensorFailure Cold aisle sensor measuring air temperature and humidity is
disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6309 |
| lgpCondId6310ChilledWaterInletTemperatureControlActive Chilled water inlet temperature control is active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6310 |
| lgpCondId6313ChilledWaterInletTemperatureSensorFailure Chilled water inlet temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6313 |
| lgpCondId6314ChilledWaterOutletTemperatureSensorFailure Chilled water outlet temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6314 |
| lgpCondId6315ChilledWaterFlowMeterSensorFailure Chilled water flow meter sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6315 |
| lgpCondId6333Bypassoutofsync Bypass and Inverter inputs are not in sync. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6333 |
| lgpCondId6348SystemOutputoffasrequested The UPS has shutdown as requested, i.e., the output is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6348 |
| lgpCondId6349SystemOffasrequested The entire UPS has shutdown as commanded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6349 |
| lgpCondId6350GeneralFault A general fault in the UPS has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6350 |
| lgpCondId6351UPSAwaitingPower The UPS output is off and the UPS is awaiting the return of input
power. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6351 |
| lgpCondId6352AutonomyCalibration Calibration test occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6352 |
| lgpCondId6353GeneralWarning A warning in the UPS has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6353 |
| lgpCondId6354BatteryCharging The UPS battery is charging (battery charge percentage lower than
98). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6354 |
| lgpCondId6355BackfeedRelayFailure Bypass SCR is wrongly on or commutated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6355 |
| lgpCondId6356BatteryCircuitOpen Battery Circuit Open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6356 |
| lgpCondId6357SystemRestartPending A request for UPS restart has been received. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6357 |
| lgpCondId6358PipeTemperatureSensorFailure Air temperature sensor located in the pipe is not sending a valid
value. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6358 |
| lgpCondId6362SFAReservedEvent26 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6362 |
| lgpCondId6363SFAReservedEvent27 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6363 |
| lgpCondId6364SFAReservedEvent28 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6364 |
| lgpCondId6365SFAReservedEvent29 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6365 |
| lgpCondId6366SFAReservedEvent30 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6366 |
| lgpCondId6367SFAReservedEvent31 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6367 |
| lgpCondId6368SFAReservedEvent32 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6368 |
| lgpCondId6369SFAReservedEvent33 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6369 |
| lgpCondId6370SFAReservedEvent34 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6370 |
| lgpCondId6371SFAReservedEvent35 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6371 |
| lgpCondId6372SFAReservedEvent36 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6372 |
| lgpCondId6373SFAReservedEvent37 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6373 |
| lgpCondId6374SFAReservedEvent38 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6374 |
| lgpCondId6375SFAReservedEvent39 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6375 |
| lgpCondId6376SFAReservedEvent40 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6376 |
| lgpCondId6377SFAReservedEvent41 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6377 |
| lgpCondId6378SFAReservedEvent42 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6378 |
| lgpCondId6379SFAReservedEvent43 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6379 |
| lgpCondId6380SFAReservedEvent44 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6380 |
| lgpCondId6381SFAReservedEvent45 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6381 |
| lgpCondId6382SFAReservedEvent46 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6382 |
| lgpCondId6383SFAReservedEvent47 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6383 |
| lgpCondId6384SFAReservedEvent48 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6384 |
| lgpCondId6385SFAReservedEvent49 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6385 |
| lgpCondId6386SFAReservedEvent50 Reserved event for SFA use. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6386 |
| lgpCondId6438PowerModuleInputCurrentAbnormal Input current of the power module is abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6438 |
| lgpCondId6439PowerModuleBalancerofDCBusFailure Balancer of DC Bus in the power module has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6439 |
| lgpCondId6440PowerModuleFuseFailure A summary event indicating one or more fuse failures in the power
module. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6440 |
| lgpCondId6441PowerModulePowerSupplyFailure Power module power supply failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6441 |
| lgpCondId6450PDUPoweredOn The PDU was powered on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6450 |
| lgpCondId6453InputWiringFault The neutral/ground conductors on the input wiring are not properly
bonded, or the line/neutral conductors have been swapped. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6453 |
| lgpCondId6454DCtoDCConverterFault A failure has occurred in the battery discharge circuit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6454 |
| lgpCondId6455LeakSensorCableFault A fault is detected in the 'Leak Sensor' cable. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6455 |
| lgpCondId6464RebootMonitoringAgent Request from managed device to reboot the monitoring agent. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6464 |
| lgpCondId6474SaveIPv4SettingstoAgent Request from managed device for the monitoring agent to save/set
IPv4 settings. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6474 |
| lgpCondId6488SaveIPv6SettingstoAgent Request from managed device for the monitoring agent to save/set
IPv6 settings. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6488 |
| lgpCondId6508SaveLIFETMSettingstoAgent Request from managed device for the monitoring agent to save/set
LIFE (TM) settings. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6508 |
| lgpCondId6518StandbyUnitActivatedDuetoChillerFailure External chiller unit has failed for this unit, so the standby
cooling unit has been activated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6518 |
| lgpCondId6522PDUResidualOverCurrent The system has detected a PDU residual over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6522 |
| lgpCondId6527PDUOverCurrentProtection The PDU over current protection is triggered. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6527 |
| lgpCondId6528PowerModuleLeverUnlocked The power module is inactive because the lever is in the unlocked
position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6528 |
| lgpCondId6529HardwareMismatch The assigned system model settings do not match the actual
installed hardware. The module count is wrong, or a module of the
wrong type is installed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6529 |
| lgpCondId6530SupplyNTCAirSensorIssue The supply NTC air sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6530 |
| lgpCondId6531ExternalAirSensorCIssue The external air sensor C is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6531 |
| lgpCondId6532ExternalAirSensorDIssue The external air sensor D is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6532 |
| lgpCondId6533ExternalAirSensorEIssue The external air sensor E is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6533 |
| lgpCondId6534PumpThermalOverload Pump is shut down due to thermal overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6534 |
| lgpCondId6535XDModuleCommunicationLost Communication with XD Module has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6535 |
| lgpCondId6536MMSCapacityExceeded The critical load is larger than the redundant rating of a 1+N
redundant multi-module system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6536 |
| lgpCondId6538TSAControlInputIssue The analog input used to set the air temperature set point for
cooling control is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6538 |
| lgpCondId6539ChilledWaterValveHoursExceeded [Chilled Water Valve Hours] has exceeded [Chilled Water Valve
Operating Hours Threshold]. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6539 |
| lgpCondId6540FSAControlInputIssue The analog input used to set the air temperature set point for fan
speed control is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6540 |
| lgpCondId6541AutoTuneLicenseExpiring License for the AutoTune feature has not been refreshed in 30 days
and will be expiring soon. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6541 |
| lgpCondId6542AutoTuneLicenseExpired License for the AutoTune feature has expired. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6542 |
| lgpCondId6543UnitInStandbyDueToCoolingLoss Unit forced into standby because it is unable to provide any
cooling. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6543 |
| lgpCondId6544ControlUnitsRemoteShutdownMismatch The remote shutdown status of the primary control unit does not
match the remote shutdown status of the secondary control unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6544 |
| lgpCondId6545SecondaryControlUnitCommunicationLost The primary control unit has lost Ethernet communications with the
secondary control unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6545 |
| lgpCondId6546ControlUnitsUnitCodeMismatch Unit codes for the primary and secondary control units do not
match. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6546 |
| lgpCondId6547SSAControlInputIssue The analog input used to set the static pressure set point for fan
speed control is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6547 |
| lgpCondId6587TransferCountCleared A system event indicating the transfer count has been cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6587 |
| lgpCondId6588EnergyCounterCleared A system event indicating the energy counter (e.g. KWH) has been
cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6588 |
| lgpCondId6589HistoryLogsFull The history logs are full. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6589 |
| lgpCondId6590HistoryLogsCleared History logs have been cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6590 |
| lgpCondId6591EventLogCleared All past alarms and faults have been cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6591 |
| lgpCondId6592SystemDateChanged The system date has been updated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6592 |
| lgpCondId6593SystemTimeChanged The system time has been updated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6593 |
| lgpCondId6594AccessPasswordChanged The access password has been changed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6594 |
| lgpCondId6595ConfigModified A setpoint has been updated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6595 |
| lgpCondId6612SCRShort The SCR is in a short condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6612 |
| lgpCondId6613SCROpen The SCR is in an open condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6613 |
| lgpCondId6614ACPowerSupplyFail A failure of the AC Power Supply has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6614 |
| lgpCondId6615DCPowerSupplyFail A failure of the DC Power Supply has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6615 |
| lgpCondId6616VoltageSensorFail A voltage sensor failure has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6616 |
| lgpCondId6617SCRSensorFail The SCR sensor module failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6617 |
| lgpCondId6618CurrentSensorFail The current sensor module failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6618 |
| lgpCondId6619GateDriveFail The Gate Drive module failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6619 |
| lgpCondId6620SurgeFail The surge module failed for the input source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6620 |
| lgpCondId6621FastUnderVoltage Fast under voltage detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6621 |
| lgpCondId6622SlowUnderVoltage Slow under voltage detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6622 |
| lgpCondId6623OverVoltage Over voltage detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6623 |
| lgpCondId6624OverUnderFrequencyFail An over or under frequency condition has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6624 |
| lgpCondId6625GeneralSourceFailure A non-specific failure has been detected in the source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6625 |
| lgpCondId6626OverCurrent An over current has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6626 |
| lgpCondId6627PeakCurrentOffLimit The peak current has exceeded the setpoint defined by I-PK Xfer
Lockout. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6627 |
| lgpCondId6628SyncFail A phase rotation/out of synchronization failure has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6628 |
| lgpCondId6629InputOverVoltage Input over voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6629 |
| lgpCondId6630InputUnderVoltage Input under voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6630 |
| lgpCondId6631InputOverUnderFrequency Input over/under frequency. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6631 |
| lgpCondId6635VoltageSenseFail Output voltage sense failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6635 |
| lgpCondId6636LoadonAlternateSource The load is on the alternate source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6636 |
| lgpCondId6637UnderVoltageFail Output under voltage failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6637 |
| lgpCondId6638OutputOverCurrent Output is over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6638 |
| lgpCondId6639GroundOverCurrent Ground is over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6639 |
| lgpCondId6640NeutralOverCurrent Neutral is over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6640 |
| lgpCondId6641LoadVoltageTHD Load voltage THD has exceeded the set limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6641 |
| lgpCondId6662ControlLogicFail A control logic module has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6662 |
| lgpCondId6663PowerSupplyLogicFail A power supply module has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6663 |
| lgpCondId6664ExternalCommsFailure External communications failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6664 |
| lgpCondId6665HeatSinkOverTemp The system heat sink temperature has exceeded design limits. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6665 |
| lgpCondId6666AutomaticTransferInhibited Automatic transfer is inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6666 |
| lgpCondId6667InputSourceTransferInhibited Input source transfer is inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6667 |
| lgpCondId6676CB1ShuntTrip CB1 Shunt Trip event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6676 |
| lgpCondId6677CB2ShuntTrip CB2 Shunt Trip event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6677 |
| lgpCondId6678CB6NeutralOpen CB6 neutral open event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6678 |
| lgpCondId6679ContactorNeutralFail Contactor Neutral Fail event. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6679 |
| lgpCondId6680CB1BreakerOpen CB1 Breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6680 |
| lgpCondId6681CB2BreakerOpen CB2 Breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6681 |
| lgpCondId6682CB4BreakerClosed CB4 breaker closed event. Normal state is breaker open. Latched
state is breaker closed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6682 |
| lgpCondId6683CB5BreakerClosed CB5 breaker closed event. Normal state is breaker open. Latched
state is breaker closed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6683 |
| lgpCondId6684CB3BreakerOpen CB3 breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6684 |
| lgpCondId6685CB3ABreakerOpen CB3A breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6685 |
| lgpCondId6686CB6BreakerOpen CB6 breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6686 |
| lgpCondId6687CB7BreakerOpen CB7 breaker open event. Normal state is breaker closed. Latched
state is breaker open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6687 |
| lgpCondId6691GroupIndependentOn The group standby/cascade state for this unit has been overridden.
The unit has been forced on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6691 |
| lgpCondId6692GroupIndependentOff The group standby/cascade state for this unit has been overridden.
The unit has been forced off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6692 |
| lgpCondId6693BranchResidualOverCurrent The system has detected a branch residual over current condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6693 |
| lgpCondId6694ReceptacleResidualOverCurrent The system has detected a receptacle residual over current
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6694 |
| lgpCondId6728BuckOn The input voltage is currently being bucked (lowered) by the
inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6728 |
| lgpCondId6729BoostOn The input voltage is currently being boosted (raised) by the
inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6729 |
| lgpCondId6739Compressor1HighPressure Compressor 1 High Pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6739 |
| lgpCondId6740Compressor2HighPressure Compressor 2 High Pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6740 |
| lgpCondId6741Compressor1ThermalOverload Compressor 1 Thermal Overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6741 |
| lgpCondId6742Compressor2ThermalOverload Compressor 2 Thermal Overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6742 |
| lgpCondId6758CompressorFreezeProtection Compressor has entered the freeze protection phase. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6758 |
| lgpCondId6773FanTemperatureCompensationLimitReached Unit is configured for fan temperature compensation, and the fan
control set point cannot be reduced any further due to high
remote air temperature sensor readings. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6773 |
| lgpCondId6774ModbusECFanCommunicationLost Communication with Modbus EC fan has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6774 |
| lgpCondId6785AnalogTemperatureControlIssue Analog input used for creating the control temperature (instead of
reading a sensor) is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6785 |
| lgpCondId6786SubgroupFirmwareUpdateRequired Mismatch of subgroup firmware. Both the primary and secondary
control boards must be running the same firmware version. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6786 |
| lgpCondId6787SubgroupSecondaryControlUnitIssue Subgroup secondary control unit is reporting an unspecified issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6787 |
| lgpCondId6788EEVCommunicationLost Communication with Electronic Expansion Valve unit has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6788 |
| lgpCondId6789EEVMotorIssue Electronic Expansion Valve stepper motor issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6789 |
| lgpCondId6790EEVFeedbackIssue Electronic Expansion Valve feedback error. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6790 |
| lgpCondId6791EEVPressureSensorIssue Electronic Expansion Valve refrigerant pressure sensor is
disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6791 |
| lgpCondId6792EEVCoilTemperatureSensorIssue Electronic Expansion Valve coil temperature sensor is disconnected
or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6792 |
| lgpCondId6793EEVDischargeTemperatureSensorIssue Electronic Expansion Valve discharge temperature sensor is
disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6793 |
| lgpCondId6794EEVSumpTemperatureSensorIssue Electronic Expansion Valve sump temperature sensor is disconnected
or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6794 |
| lgpCondId6795EEVBatteryTestIssue Electronic Expansion Valve battery state cannot be determined. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6795 |
| lgpCondId6796EEVBatteryPersistentIssue Electronic Expansion Valve has continuously detected a 'bad'
battery condition for an extended period of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6796 |
| lgpCondId6798PumpCycleLockOut Pump is locked out due to multiple pump-to-compressor transitions
at cold ambient air temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6798 |
| lgpCondId6799PumpBoardFirmwareUpdateRequired Mismatch of pump board firmware. All pump boards must be running
the same firmware version. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6799 |
| lgpCondId6800PumpControlBoardIssue Pump is shut down due to a pump control board issue. Control
board must be rebooted. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6800 |
| lgpCondId6801PumpInvalidDataShutdown Pump is shut down due to invalid data. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6801 |
| lgpCondId6802PumpInputPressureSensorIssue Pump input refrigerant pressure sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6802 |
| lgpCondId6803PumpInputTemperatureSensorIssue Pump input refrigerant temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6803 |
| lgpCondId6804PumpOutputPressureSensorIssue Pump output refrigerant pressure sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6804 |
| lgpCondId6805PumpOutputTemperatureSensorIssue Pump output refrigerant temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6805 |
| lgpCondId6806PumpCommunicationLost Communication with pump unit has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6806 |
| lgpCondId6807PumpRemoteShutdown Pump is shut down by a remote signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6807 |
| lgpCondId6808PumpUSBEthernetPortIssue Pump control board USB or Ethernet interface has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6808 |
| lgpCondId6809PumpStartupFailure Multiple attempts to start the pump have failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6809 |
| lgpCondId6810PumpInverterFailure Pump inverter is reporting a failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6810 |
| lgpCondId6811PumpTVSSIssue Pump Transient Voltage Surge Suppressor or Surge Protection Device
has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6811 |
| lgpCondId6812PumpHighSuperheat Pump inlet refrigerant superheat temperature is too high, or the
pump has been running too long with the condenser fan off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6812 |
| lgpCondId6813CondenserHighAmbientAirTempDelta The difference between condenser measured ambient air temperatures
has been too large for an extended period of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6813 |
| lgpCondId6814CondenserLeeTempOptionMismatch Lee-Temp option configured at a condenser unit does not match Lee
-Temp option configured at the control unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6814 |
| lgpCondId6815CondenserBoardFirmwareUpdateRequired Mismatch of condenser board firmware. All condenser boards must
be running the same firmware version. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6815 |
| lgpCondId6816CondenserToPumpHighRefrigerantTempDelta Temperature delta between the condenser output refrigerant and
pump inlet refrigerant is too large. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6816 |
| lgpCondId6817CondenserRefrigerantTypeMismatch Refrigerant type configured at condenser unit does not match
refrigerant type configured at the control unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6817 |
| lgpCondId6818ExternalSupplyFluidHighTemperature Supply fluid temperature has exceeded a threshold, as indicated by
an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6818 |
| lgpCondId6819ExternalSupplyFluidTempSensorIssue Supply fluid temperature sensor is disconnected or the signal is
out of range, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6819 |
| lgpCondId6822AuditLogUpdate Audit log has been updated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6822 |
| lgpCondId6824ExternalSupplyFluidFlowIssue Supply fluid flow issue, as indicated by an external input signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.6824 |
| lgpCondId7163ModbusAutomaticTransferSwitchCommunicationLost Communications with Modbus Automatic Transfer Switch has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7163 |
| lgpCondId7164BatteryDeepDischarge UPS depleted the batteries to the end of discharge(EOD) voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7164 |
| lgpCondId7461BatteryBreakerOpenFailure Battery circuit breaker failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7461 |
| lgpCondId7464LithiumIonBatterySystemAbnormal Lithium-Ion Battery System Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7464 |
| lgpCondId7465LithiumIonBatterySystemDisconnectRequest A request to disconnect the Lithium-Ion battery system was
received. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7465 |
| lgpCondId7467ThermalMarginWarning The thermal margin has dropped below the threshold value. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7467 |
| lgpCondId7474FlowSensorFailure Fluid flow sensor failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7474 |
| lgpCondId7475CheckWaterSystem Fluid check water system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7475 |
| lgpCondId7476PumpOperatingWithoutFlow Fluid pump operation with no flow. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7476 |
| lgpCondId7483PumpInverterFailure Fluid pump inverter failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7483 |
| lgpCondId7484PumpFlowFailure Fluid pump flow failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7484 |
| lgpCondId7485BatteryCircuitBreakerOpen Battery circuit breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7485 |
| lgpCondId7486LithiumIonBatterySystemCommunicationAbnormal Lithium-Ion Battery System Communication Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7486 |
| lgpCondId7487LithiumIonBatterySystemWarning The Lithium-Ion Battery system has one or more warnings. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7487 |
| lgpCondId7488LithiumIonBatterySystemFault The Lithium-Ion Battery system has one or more faults. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7488 |
| lgpCondId7489LowSupplyAirHumidity Supply air humidity has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7489 |
| lgpCondId7490HighSupplyAirHumidity Supply air humidity has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7490 |
| lgpCondId7491LowRemoteAirHumidity Remote air humidity has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7491 |
| lgpCondId7492HighRemoteAirHumidity Remote air humidity has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7492 |
| lgpCondId7493SupplyHumiditySensorIssue The humidity sensor at the outlet of the unit is disconnected or
the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7493 |
| lgpCondId7494ExternalHumiditySensorIssue The external humidity sensor is disconnected or the signal is out
of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7494 |
| lgpCondId7495ExternalAirSensorIssue The external air sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7495 |
| lgpCondId7496CompressorDriverFailureLockout Compressor lockout occurred due to multiple failures of the
compressor driver board. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7496 |
| lgpCondId7497CompressorDriverFailure Compressor driver board failure detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7497 |
| lgpCondId7498CompressorDriverCommunicationFailureLockout Compressor lockout occurred due to multiple communication failures
with the compressor driver board. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7498 |
| lgpCondId7499CompressorPressureDifferenceLockout Compressor lockout occurred due to multiple compressor pressure
differences. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7499 |
| lgpCondId7500CompressorDriverCommunicationFailure A communication failure occurred with the compressor driver board. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7500 |
| lgpCondId7501CompressorPressureDifference Compressor pressure difference is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7501 |
| lgpCondId7503ElectricalHeaterFailure The electric heater temperature exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7503 |
| lgpCondId7504WaterValveFailure There is an issue with the chilled water valve. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7504 |
| lgpCondId7506SupplyFluidLowFlow Supply fluid flow has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7506 |
| lgpCondId7507InletFluidLowPressure Inlet fluid pressure has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7507 |
| lgpCondId7508InletFluidHighPressure Inlet fluid pressure has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7508 |
| lgpCondId7509OutletFluidUnderTemp Outlet fluid temperature has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7509 |
| lgpCondId7510OutletFluidOverTemp Outlet fluid temperature has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7510 |
| lgpCondId7511InletFluidOverTemp Inlet fluid temperature has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7511 |
| lgpCondId7512InletFluidUnderTemp Inlet fluid temperature has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7512 |
| lgpCondId7515FanDetectionBoardCommunicationFailure Communication with the fan detection board has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7515 |
| lgpCondId7518SurgeProtectionDeviceAlarm Surge Protection Device Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7518 |
| lgpCondId7519PowerOppositePhase The power input phases are incorrectly connected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7519 |
| lgpCondId7520PowerLossOfPhase One of the input phases has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7520 |
| lgpCondId7522LossofAirflow Loss of airflow detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7522 |
| lgpCondId7523TeamworkMasterisofflineornotconnectedtothenetwork Loss of Teamwork Master. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7523 |
| lgpCondId7524LossofTeamworkSlave Teamwork Slave is offline or not connected to the network. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7524 |
| lgpCondId7525RepeatedTeamworkAddress The network address of two or more units in a teamwork are the
same. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7525 |
| lgpCondId7526AirDamperFailure There is an issue with the air damper. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7526 |
| lgpCondId7537FilterMaintenanceDue The operating hours of the filter has exceeded the threshold and
needs to be maintained or replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7537 |
| lgpCondId7538HeaterMaintenanceDue The operating hours of the heater has exceeded the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7538 |
| lgpCondId7539HighCompressorPressure Compressor pressure has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7539 |
| lgpCondId7540HighCompressorPresssureLockout Compressor lockout occurred due to high compressor pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7540 |
| lgpCondId7541LowCompressorPressure Compressor pressure has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7541 |
| lgpCondId7542LowCompressorPressureLockout Compressor lockout occurred due to low compressor pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7542 |
| lgpCondId7543HighCompressorDischargeTemperature Compressor discharge temperature has exceeded a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7543 |
| lgpCondId7544HighCompressorDischargeTemperatureLockout Compressor Lockout occurred due to high compressor discharge
temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7544 |
| lgpCondId7545LowCompressorDischargeTemperature Compressor discharge temperature has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7545 |
| lgpCondId7546LowCompressorDischargeTemperatureLockout Compressor lockout occurred due to low compressor discharge
temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7546 |
| lgpCondId7547LowCompressorDischargeSuperheat Compressor discharge superheat has dropped below a threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7547 |
| lgpCondId7548LowCompressorDischargeSuperheatLockout Compressor lockout occurred due to low compressor discharge
superheat temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7548 |
| lgpCondId7549HighCompressorPressureAbnormal Compressor pressure has exceeded a normal threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7549 |
| lgpCondId7550LowCompressorPressureAbnormal Compressor pressure has dropped below a normal threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7550 |
| lgpCondId7551EEVDriverCommunicationFailure A communication failure occurred with the EEV driver board. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7551 |
| lgpCondId7552EEVDriverFailure EEV driver board failure detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7552 |
| lgpCondId7553HighCompressorPressureSensorFailure High compressor pressure sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7553 |
| lgpCondId7554LowCompressorPressureSensorFailure Low compressor pressure sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7554 |
| lgpCondId7555LowCompressorPressureSensorFailureLockout Compressor lockout occurred due to low compressor pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7555 |
| lgpCondId7556CompressorDischargeTemperatureSensorFailure Compressor discharge temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7556 |
| lgpCondId7557CompressorSuctionTemperatureSensorFailure Compressor suction temperature sensor is disconnected or the
signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7557 |
| lgpCondId7558WaterFlowSensorFailure Water flow sensor is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7558 |
| lgpCondId7559LossofAirflowSensorFailure Airflow sensor is disconnected or the signal is out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7559 |
| lgpCondId7560FilterPressureDifferenceSensorFailure Filter pressure difference sensor is disconnected or the signal is
out of range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7560 |
| lgpCondId7561CustomAlarm Custom Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7561 |
| lgpCondId7562WaterPressureSensorFailure Water pressure sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7562 |
| lgpCondId7563FanStaticPressureSensorFailure Fan static pressure sensor is disconnected or the signal is out of
range. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7563 |
| lgpCondId7568SystemShutdownEPO Unit shutdown by Emergency Power Off (EPO) switch. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7568 |
| lgpCondId7569SystemShutdownUndervoltage System shutdown due to an undervoltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7569 |
| lgpCondId7570TransformerHighTemperature The transformer crossed the high temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7570 |
| lgpCondId7571TransformerTemperatureSensorFailure The transformer temperature sensor is reporting an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7571 |
| lgpCondId7572MeteringBoardCommunicationFail The metering board(s) reported a communication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7572 |
| lgpCondId7573AccessoryBoardCommunicationFail The accessory board(s) reported a communication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7573 |
| lgpCondId7574SystemMisconfiguration The system reported a misconfiguration. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7574 |
| lgpCondId7575SystemFirmwareIncompatibility The system reported a firmware incompatibility. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7575 |
| lgpCondId7576MainInputBreaker1Tripped The main input circuit breaker 1 reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7576 |
| lgpCondId7577MainInputBreaker1AccessoryError The main input circuit breaker 1 reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7577 |
| lgpCondId7578MainInputBreaker1OpenFail The main input circuit breaker 1 failed to open as commanded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7578 |
| lgpCondId7579MainInputBreaker2Tripped The main input circuit breaker 2 reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7579 |
| lgpCondId7580MainInputBreaker2AccessoryError The main input circuit breaker 2 reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7580 |
| lgpCondId7581MainInputBreaker2OpenFail The main input circuit breaker 2 failed to open as commanded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7581 |
| lgpCondId7588LossofCommunication The system board has stopped communicating. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7588 |
| lgpCondId7589NoInitialCommunication The system board has not established initial communications. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7589 |
| lgpCondId7590Misconfiguration The system board is misconfigured. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7590 |
| lgpCondId7591FirmwareIncompatibility The system board firmware is incompatible with the other
components. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7591 |
| lgpCondId7697OutputOvervoltage The output voltage crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7697 |
| lgpCondId7698OutputUndervoltage The output voltage crossed below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7698 |
| lgpCondId7699PhaseOvercurrent The phase current crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7699 |
| lgpCondId7700NeutralOvercurrent The neutral current crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7700 |
| lgpCondId7701GroundOvercurrent The ground current crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7701 |
| lgpCondId7702OutputFrequencyDeviation The output frequency deviated beyond the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7702 |
| lgpCondId7703EnergyMeasurementRollover The total accumulated energy value reached its limit and was reset
to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7703 |
| lgpCondId7704Input1Overvoltage The voltage crossed above the threshold of input 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7704 |
| lgpCondId7705Input1Undervoltage The voltage crossed below the threshold of input 1 . | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7705 |
| lgpCondId7706Input1PhaseLoss The voltage of one or more phases dropped below the threshold of
input 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7706 |
| lgpCondId7707Input1InvalidPhaseRotation The phases are not in the expected sequence for input 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7707 |
| lgpCondId7708Input1FrequencyDeviation The frequency deviated beyond the threshold of input 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7708 |
| lgpCondId7709Input1HighVoltageTHD The voltage total harmonic distortion crossed above the threshold
of input 1. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7709 |
| lgpCondId7710Input2Overvoltage The voltage crossed above the threshold of input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7710 |
| lgpCondId7711Input2Undervoltage The voltage crossed below the threshold of input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7711 |
| lgpCondId7712Input2PhaseLoss The voltage of one or more phases dropped below the threshold of
input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7712 |
| lgpCondId7713Input2InvalidPhaseRotation The phases are not in the expected sequence for input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7713 |
| lgpCondId7714Input2FrequencyDeviation The frequency deviated beyond the threshold of input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7714 |
| lgpCondId7715Input2HighVoltageTHD The voltage total harmonic distortion crossed above the threshold
of input 2. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7715 |
| lgpCondId7792PanelboardPhaseOvercurrent The phase current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7792 |
| lgpCondId7793PanelboardNeutralOvercurrent The neutral current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7793 |
| lgpCondId7794PanelboardGroundOvercurrent The ground current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7794 |
| lgpCondId7795PanelboardMainBreakerTripped The main panelboard circuit breaker reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7795 |
| lgpCondId7796PanelboardMainBreakerAccessoryError The main panelboard circuit breaker reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7796 |
| lgpCondId7797PanelboardEnergyMeasurementRollover The total accumulated energy value of the panelboard reached its
limit and was reset to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7797 |
| lgpCondId7822BranchPhaseOvercurrent The phase current crossed above the threshold of the branch. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7822 |
| lgpCondId7823BranchPhaseUndercurrent The phase current crossed below the threshold of the branch. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7823 |
| lgpCondId7824BranchEnergyMeasurementRollover The total accumulated energy value of the branch reached its limit
and was reset to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7824 |
| lgpCondId7896PanelboardPhaseOvercurrent The phase current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7896 |
| lgpCondId7897PanelboardNeutralOvercurrent The neutral current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7897 |
| lgpCondId7898PanelboardGroundOvercurrent The ground current crossed above the threshold of the panelboard. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7898 |
| lgpCondId7899PanelboardMainBreakerTripped The main panelboard circuit breaker reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7899 |
| lgpCondId7900PanelboardMainBreakerAccessoryError The main panelboard circuit breaker reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7900 |
| lgpCondId7901PanelboardEnergyMeasurementRollover The total accumulated energy value of the panelboard reached its
limit and was reset to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7901 |
| lgpCondId7953SubfeedPhaseOvercurrent The phase current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7953 |
| lgpCondId7954SubfeedNeutralOvercurrent The neutral current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7954 |
| lgpCondId7955SubfeedGroundOvercurrent The ground current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7955 |
| lgpCondId7956SubfeedBreakerTripped The subfeed circuit breaker reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7956 |
| lgpCondId7957SubfeedBreakerAccessoryError The subfeed circuit breaker reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7957 |
| lgpCondId7958SubfeedEnergyMeasurementRollover The total accumulated energy value reached its limit and was reset
to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.7958 |
| lgpCondId8029SubfeedPhaseOvercurrent The phase current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8029 |
| lgpCondId8030SubfeedNeutralOvercurrent The neutral current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8030 |
| lgpCondId8031SubfeedGroundOvercurrent The ground current crossed above the threshold of the subfeed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8031 |
| lgpCondId8032SubfeedBreakerTripped The subfeed circuit breaker reported a tripped state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8032 |
| lgpCondId8033SubfeedBreakerAccessoryError The subfeed circuit breaker reported an invalid state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8033 |
| lgpCondId8034SubfeedEnergyMeasurementRollover The total accumulated energy value reached its limit and was reset
to zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8034 |
| lgpCondId8045ExternalInputContactState The state of the external input contact. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8045 |
| lgpCondId8047InternalInputContactState The state of the internal input contact. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8047 |
| lgpCondId8051CompressorDriveFailureU00 Compressor Drive Failure U00. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8051 |
| lgpCondId8052CompressorDriveFailureU01 Compressor Drive Failure U01. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8052 |
| lgpCondId8053CompressorDriveFailureU02 Compressor Drive Failure U02. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8053 |
| lgpCondId8054CompressorDriveFailureU03 Compressor Drive Failure U03. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8054 |
| lgpCondId8055CompressorDriveFailureU04 Compressor Drive Failure U04. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8055 |
| lgpCondId8056CompressorDriveFailureU05 Compressor Drive Failure U05. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8056 |
| lgpCondId8057CompressorDriveFailureU06 Compressor Drive Failure U06. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8057 |
| lgpCondId8058CompressorDriveFailureU07 Compressor Drive Failure U07. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8058 |
| lgpCondId8059CompressorDriveFailureU08 Compressor Drive Failure U08. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8059 |
| lgpCondId8060CompressorDriveFailureU09 Compressor Drive Failure U09. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8060 |
| lgpCondId8061CompressorDriveFailureU10 Compressor Drive Failure U10. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8061 |
| lgpCondId8062CompressorDriveFailureU11 Compressor Drive Failure U11. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8062 |
| lgpCondId8063CompressorDriveFailureU12 Compressor Drive Failure U12. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8063 |
| lgpCondId8064CompressorDriveFailureU13 Compressor Drive Failure U13. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8064 |
| lgpCondId8065CompressorDriveFailureU14 Compressor Drive Failure U14. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8065 |
| lgpCondId8066CompressorDriveFailureU15 Compressor Drive Failure U15. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8066 |
| lgpCondId8067EEVDriverUnselectRefrigerant EEV Driver Unselect Refrigerant. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8067 |
| lgpCondId8068CompressorDriveHeatsinkHighTemperature Compressor Drive Heatsink High Temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8068 |
| lgpCondId8069CompressorDriveOverCurrent Compressor Drive Over Current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8069 |
| lgpCondId8070CompressorDrivePhaseLoss Compressor Drive Phase Loss. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8070 |
| lgpCondId8071CompressorDriveDCPowerAbnormal Compressor Drive DC Power Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8071 |
| lgpCondId807210DISensorCommunicationFail 10DI Sensor Communication Fail. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8072 |
| lgpCondId8073SystemLackOfRefrigerant System Lack Of Refrigerant. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8073 |
| lgpCondId8075ValveCommunicationsFailure A valve is configured to exist but communications cannot be
established. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8075 |
| lgpCondId8076ValveIssue Valve is reporting abnormal operating condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8076 |
| lgpCondId8083CondensatePumpFailure Condensate Pump Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8083 |
| lgpCondId8096BypasscontrollingtheSCRautonomously The bypass is controlling the SCR autonomously because not all
inverters are online. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8096 |
| lgpCondId8098PowerModuleCommunicationstatus The control has detected a power module communication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8098 |
| lgpCondId8100ECOmodeInhibited ECO mode is inhibited due to an external inhibit signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8100 |
| lgpCondId8105SupplyFanCommunicationLost Communications with Supply Fan has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8105 |
| lgpCondId8119CommunicationBusError The system board is experiencing an abnormal number of
communication errors. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8119 |
| lgpCondId8120ExternalBatteryCabinetRemoved One or more external battery cabinets have been removed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8120 |
| lgpCondId8125InternalBatteryBreakerOpen The internal battery breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8125 |
| lgpCondId8126AllChargersShutdown All chargers in system are shut down to avoid incompatibility in
external charger application, or to avoid over-charging in
Lithium-ion battery application. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8126 |
| lgpCondId8127SpecificChargerShutdown The charger in this power module is shut down to detect battery
connection status or to avoid Lithium-ion battery over-charging. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8127 |
| lgpCondId8166BIBBatteryBreakerPowerSupplyFailure Battery Interface Board power supply has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8166 |
| lgpCondId8170XDPumpCommunicationLost Communications with XD Pump has been lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8170 |
| lgpCondId8178EmergencyCooling Emergency Cooling. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8178 |
| lgpCondId8179BatteryManagementSystemPowerSupplyFailure The battery management system has reported a power supply failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8179 |
| lgpCondId8180SupplyFluidLowTemp [Supply Fluid Temperature] below Supply Fluid Low Temp Threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8180 |
| lgpCondId8181ReturnFluidLowTemp [Return Fluid Temperature] below Return Fluid Low Temp Threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8181 |
| lgpCondId8182FluidHighDifferentialPressure Fluid Loop High Differential Pressure (Supply - Return). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8182 |
| lgpCondId8183FluidLowDifferentialPressure Fluid Loop Low Differential Pressure (Supply - Return). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8183 |
| lgpCondId8184FluidFlowLowInletPressure Fluid Loop Flow Low Inlet Pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8184 |
| lgpCondId8185FluidFlowHighSupplyPressure Fluid Loop Flow High Supply Pressure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8185 |
| lgpCondId8186FluidLowSystemFlow Fluid Loop Low System Flow (Low total flow for units in group). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8186 |
| lgpCondId8187FluidFlowBlocked Fluid Loop Flow Blocked (Loss of Flow with High Supply Pressure). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8187 |
| lgpCondId8188FluidDewpointMarginControl Fluid Loop Dewpoint Margin Control is active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8188 |
| lgpCondId8189FluidSupplyPressureSensorIssue Fluid Loop Supply Pressure Sensor Issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8189 |
| lgpCondId8190FluidReturnPressureSensorIssue Fluid Loop Return Pressure Sensor Issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8190 |
| lgpCondId8191FluidInletPressureSensorIssue Fluid Loop Inlet Pressure Sensor Issue. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8191 |
| lgpCondId8192WaterLeakage Water Leakage - Typically indicates unit internal water leakage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8192 |
| lgpCondId8194BatteryManagementSystemRackisOfflineWarning The Battery Management System has reported a rack-is-offline
warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8194 |
| lgpCondId8195BatteryManagementSystemGeneralWarning The Battery Management System has reported a General Warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8195 |
| lgpCondId8196BatteryManagementSystemFault The Battery Management System has reported a Fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8196 |
| lgpCondId8197BatteryManagementSystemEndOfDischargeWarning The Battery Management System has reported an End-Of-Discharge
Warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8197 |
| lgpCondId8199LoadonBypassUnion The output power is supplied by the bypass and maintenance bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8199 |
| lgpCondId8200BypassControlModuleNotAvailable The bypass control module is not available. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8200 |
| lgpCondId8201BypassModuleNotAvailable The bypass module is not available. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8201 |
| lgpCondId8208BranchOverCurrent The PDU branch current is over limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8208 |
| lgpCondId8209BranchCurrentOverHL The current of pdu branch is over the high level. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8209 |
| lgpCondId8210BranchCurrentOverLL The current of pdu branch is over the low level. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8210 |
| lgpCondId8211BranchInrushOC The instantaneous current of pdu branch is large. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8211 |
| lgpCondId8212BranchBreakerFail A failure has been detected with the branch breaker. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8212 |
| lgpCondId8227SPMInternalCommFailure The communication with Server Power Management is lost. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8227 |
| lgpCondId8228SPMCRCCheckError Server Power Management CRC Check Error. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8228 |
| lgpCondId8229SPMBoardNotReady The Server Power Management sample board is not ready. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8229 |
| lgpCondId8231PHESupTemSnsrFail Plate Heat Exchanger Supply Temperature Sensor Fail. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8231 |
| lgpCondId8253PanelboardOvervoltage The panelboard voltage crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8253 |
| lgpCondId8254PanelboardUndervoltage The panelboard voltage crossed below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8254 |
| lgpCondId8255PanelboardFrequencyDeviation The panelboard frequency deviated beyond the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8255 |
| lgpCondId8259BranchNeutralOvercurrent The neutral current crossed above the threshold of the branch. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8259 |
| lgpCondId8262PanelboardOvervoltage The Panelboard voltage crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8262 |
| lgpCondId8263PanelboardUndervoltage The panelboard voltage crossed below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8263 |
| lgpCondId8264PanelboardFrequencyDeviation The panelboard frequency deviated beyond the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8264 |
| lgpCondId8267SubfeedOvervoltage The subfeed voltage crossed above the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8267 |
| lgpCondId8268SubfeedUndervoltage The subfeed voltage crossed below the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8268 |
| lgpCondId8269SubfeedFrequencyDeviation The subfeed frequency deviated beyond the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8269 |
| lgpCondId8273BatteryTempAbnormal Battery temperature is abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8273 |
| lgpCondId8274DischargerShutdown A condition is present that prevents the Battery Discharger from
working. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8274 |
| lgpCondId8283BypassUnabletoTrace The voltage amplitude or frequency of bypass is out of the range
of trace. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8283 |
| lgpCondId8284OutputBreakerOpen UPS internal or external output breaker is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8284 |
| lgpCondId8285PowerModuleInputCurrentHigh Input current of the power module is over limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8285 |
| lgpCondId8286ParameterConfigurationFailed Parameter configuration failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8286 |
| lgpCondId8287OutputDisabled Output Disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8287 |
| lgpCondId8288BatteryTerminalAbnormal Battery Terminal Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8288 |
| lgpCondId8290MOBAuxSensingFault There was a Master Output Breaker Aux Sensing Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8290 |
| lgpCondId8294SMPSInputPowerSupplyFailure Bypass Input power supply or Rectifier input power supply has
failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8294 |
| lgpCondId8295Rectifieroffduetofanpowernotavailable The Rectifier is off due to fan power not available. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8295 |
| lgpCondId8305Rectifieroverload Rectifier overload. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8305 |
| lgpCondId8306Rectifiersoftstartfailure Rectifier soft start failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8306 |
| lgpCondId8307Batterycabinetconnectionabnormal Battery cabinet connection abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8307 |
| lgpCondId8308Insufficientcapacitytostart Insufficient capacity to start. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8308 |
| lgpCondId8309Bypassdisabled Bypass disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8309 |
| lgpCondId8310Auxiliarypowerfault Auxiliary power fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8310 |
| lgpCondId8311Outputoffduetoabnormalbypass Output off due to abnormal bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8311 |
| lgpCondId8312Localoutputisdisconnected Local output is disconnected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8312 |
| lgpCondId8313Outputoffvoltageisnotzero Output off voltage is not zero. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8313 |
| lgpCondId8314Paralleloutputfrequencyabnormal Parallel output frequency abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8314 |
| lgpCondId8315ManualPowerOn Manual Power On. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8315 |
| lgpCondId8316RemotePowerOn Remote Power On. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8316 |
| lgpCondId8317Batterytoutilitytransition Battery to utility transition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8317 |
| lgpCondId8318UPSwasresettofactorydefaults UPS was reset to factory defaults. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8318 |
| lgpCondId8319DeviceFaultswereclearedasrequested Device Faults were cleared, as requested. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8319 |
| lgpCondId8320Scheduledpoweronoccurred Scheduled power on occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8320 |
| lgpCondId8321Scheduledpoweroffoccurred Scheduled power off occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8321 |
| lgpCondId8323NeutralSCRShort The Neutral SCR is in a short condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8323 |
| lgpCondId8324NeutralSCROpen The Neutral SCR is in an open condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8324 |
| lgpCondId8325InputNeutralOverCurrent An over current has been detected on the system input neutral. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8325 |
| lgpCondId8326NeutralSnubberFail The neutral snubber has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8326 |
| lgpCondId8331BatteryCabinetSerialNumberIllegalError Serial Number of the battery cabinet is illegal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8331 |
| lgpCondId8332LithiumBatteryCabinetOnlineNumberError The online battery cabinet number is different from the cofigured
number. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8332 |
| lgpCondId8333LithiumBatteryCabinetCommunicationFailure Battery cabinet communication has been disrupted. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8333 |
| lgpCondId8334LithiumBatteryCabinetmismatchtheunit The warning is triggered when the online lithium battery cabinet
can't be used by the UPS. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8334 |
| lgpCondId8335LithiumBatteryCabinetAddressSetError Lithium battery cabinet addresses have been set incorrectly. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8335 |
| lgpCondId8336LithiumBatteryCabinetWaitCharge The battery is waiting for charge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8336 |
| lgpCondId8337NumberofLithiumBatteryCabinetsOverLimit The number of batteries connected to the system exceeds the
maximum. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8337 |
| lgpCondId8338LithiumBatteryCabinetCheck Check if the battery is present. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8338 |
| lgpCondId8339ManualLithiumBatteryWakeUpOccurred Manual lithium battery wake up occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8339 |
| lgpCondId8344BatteryVoltageAbnormal Battery voltage out-of-range in the online lithium battery cabinet. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8344 |
| lgpCondId8345BatteryTemperatureAbnormal Battery Temperature out-of-range of the online Lithium Battery
Cabinet. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8345 |
| lgpCondId8346BatteryCurrentAbnormal Battery current out-of-range of the online lithium battery cabinet. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8346 |
| lgpCondId8347BatteryCabinetAddressFault Battery Cabinet Addresses are set incorrectly. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8347 |
| lgpCondId8348BatteryCabinetConnectFault Battery cabinet ports have reversed connections. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8348 |
| lgpCondId8349BatteryCabinetCommunicationFail Battery Cabinet Cable failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8349 |
| lgpCondId8362Turnonfailed Turn on failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8362 |
| lgpCondId8368SystemoutputInhibitExt System output is inhibited by an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8368 |
| lgpCondId8397BatteryCabinetOverTemperature Battery Cabinet Over Temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8397 |
| lgpCondId8398BatteryStringOpen Battery String Open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8398 |
| lgpCondId8399BatterySystemAbnormal Battery System Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8399 |
| lgpCondId8404AirFilterDifferentialPressureSensorFailure Air Filter Differential Pressure Sensor Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8404 |
| lgpCondId8405SupplyAirVolumeSensorCommunicationFailure Supply Air Volume Sensor Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8405 |
| lgpCondId8407CompressorinAlarmCondition Compressor in Alarm Condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8407 |
| lgpCondId8410FanCommunicationFailure Fan Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8410 |
| lgpCondId8412CondensatePressureSensorAlarm Condensate Pressure Sensor Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8412 |
| lgpCondId8421MotorizedBallValveFailure Motorized Ball Valve Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8421 |
| lgpCondId8422AisleStaticPressureSensorFailure Aisle static pressure sensor failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8422 |
| lgpCondId8423BPHECommunicationFailure Brazed Plate Heat Exchanger Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8423 |
| lgpCondId8424DataCollectorCommunicationFailure Data Collector Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8424 |
| lgpCondId8425EPIVFailure Electronic Pressure Independent Control Valve Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8425 |
| lgpCondId8426ATSCommunicationFailure ATS Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8426 |
| lgpCondId8427APFCommunicationFailure Active Power Filter Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8427 |
| lgpCondId8429BatterySystemCommunicationAbnormal Battery System Communication Abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8429 |
| lgpCondId8430BatterySystemWarning Battery System Warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8430 |
| lgpCondId8431BatterySystemFault Battery System Fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8431 |
| lgpCondId8435PanelboardMainBreakerOpenFail The main panelboard circuit breaker failed to open when tripped. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8435 |
| lgpCondId8436LoadLossDetected Load loss detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8436 |
| lgpCondId8438BatteryCabinetParallelFailure Battery Cabinet Parallel failure of the online lithium battery
cabinet. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8438 |
| lgpCondId8439BatteryCabinetSOHLow Battery cabinet state of health is low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8439 |
| lgpCondId8446ShutdownDueToSystemInputBackfeedFault UPS will shutdown due to a system input backfeed fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8446 |
| lgpCondId8447InputNeutralGroundAbnormal Input neutral ground abnormal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8447 |
| lgpCondId8448BypassAbnormalInECOMode UPS will return to inverter from bypass due to ECO Mode bypass
abnormal condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8448 |
| lgpCondId8449ShutdownDueToBypassOvercurrentTimeout UPS will shutdown due to bypass overcurrent. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8449 |
| lgpCondId8450ShutdownDueToBypassBackfeedFault UPS will shutdown due to a bypass backfeed fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8450 |
| lgpCondId8451ECOBypassMode ECO Mode Operation. Unit is On Bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8451 |
| lgpCondId8452ParallelBypassCableConnectionAbnormal Parallel bypass cable wiring error. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8452 |
| lgpCondId8454FanReplacementRequired Fan replacement required. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8454 |
| lgpCondId8455LoadOffDueToShutdownOnBattery Load Off Due To Shutdown On Battery. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8455 |
| lgpCondId8456SystemRedundantOverload System loss of redundancy. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8456 |
| lgpCondId8457DSPFaultCondition DSP Fault Condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8457 |
| lgpCondId8458OnIntelligentSleepMode Unit in intelligent sleep mode operation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8458 |
| lgpCondId8459FanReplaced Fan has been replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8459 |
| lgpCondId8461THCardAlarm TH Card Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8461 |
| lgpCondId8462CompressorLimitingAlarm Compressor Limiting Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8462 |
| lgpCondId8463OutdoorFanCommunicationFailure Outdoor Fan Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8463 |
| lgpCondId8464OutdoorFanDriverFailure Outdoor Fan Driver Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8464 |
| lgpCondId8467ProductRunOverTimeAlarm Product Run Over Time Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8467 |
| lgpCondId8468EnergyMeterCommunicationFailure Energy Meter Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8468 |
| lgpCondId8469ATSFailure ATS Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8469 |
| lgpCondId8470SMSStopInverterInhibit When active a single inverter stop cannot be initiated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8470 |
| lgpCondId8471UnitInSpecialCapacityMode When active in a MMS, the system will always be in capacity
condition, regardless of actual load. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8471 |
| lgpCondId8472RectifierOvercurrentWarning The rectifier stopped for overcurrent. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8472 |
| lgpCondId8474IncompatibleBatteryManagementSystemversion The Battery Management System software version is incompatible. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8474 |
| lgpCondId8475LithiumBatteryEOL Lithium battery is at the end of its life. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8475 |
| lgpCondId8476LithiumBatterySamplingCircuitFailure Lithium battery has sampling circuit failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8476 |
| lgpCondId8477LithiumBatteryHardwareCircuitProtectionActive Lithium battery has activated hardware circuit protection. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8477 |
| lgpCondId8478LithiumBatteryCellCapacityLow Lithium battery cell capacity is very low. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8478 |
| lgpCondId8479LithiumBatteryCableConnectionIssue Check the Lithium Battery cable connections. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8479 |
| lgpCondId8480DischargeableBatteryCountLessThanConfiguredNumber The number of connected battery cabinets is less than the
configured number. Prevent Discharge. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8480 |
| lgpCondId8481Ambienttemperaturelowerthanrecommended The ambient temperature is lower than the lower limit of the
recommended temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8481 |
| lgpCondId8482Ambienttemperaturehigherthanrecommended The ambient temperature is higher than the upper limit of the
recommended temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8482 |
| lgpCondId8483Ambienttemperaturelowprealarm The ambient temperature is close to the lower limit of the
operating temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8483 |
| lgpCondId8484Ambienttemperaturehighprealarm The ambient temperature is close to the upper limit of the
operating temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8484 |
| lgpCondId8489SystemBypassPhaseRotationError The power conductors on the input line are not wired to the UPS in
the sequence preferred for the bypass (A-B-C). | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8489 |
| lgpCondId8494SystemControlCardNotReady System control card is not ready. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8494 |
| lgpCondId8495SystemControlCardPowerSupplyFailure System control card power supply failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8495 |
| lgpCondId8496SystemControlCardCommunicationFail System control card communication fail. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8496 |
| lgpCondId8501BypassModuleNotReady Bypass Module is not ready. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8501 |
| lgpCondId8502BypassModulePowerSupplyFailure Bypass module power supply failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8502 |
| lgpCondId8503BypassModuleCommunicationFault The bypass module communication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8503 |
| lgpCondId8504BypassModuleOverTemperature The Bypass Module has detected an over temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8504 |
| lgpCondId8505BypassModuleFanFault The Bypass Module has detected a fan fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8505 |
| lgpCondId8510DischargerFailure Discharger failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8510 |
| lgpCondId8512PowerModuleNotReady Power module not ready. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8512 |
| lgpCondId8517BatteryCircuitBreaker9Open Battery circuit breaker 9 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8517 |
| lgpCondId8518BatteryCircuitBreaker10Open Battery circuit breaker 10 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8518 |
| lgpCondId8519BatteryCircuitBreaker11Open Battery circuit breaker 11 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8519 |
| lgpCondId8520BatteryCircuitBreaker12Open Battery circuit breaker 12 is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8520 |
| lgpCondId8521BatteryBreaker9OpenFailure Battery circuit breaker 9 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8521 |
| lgpCondId8522BatteryBreaker10OpenFailure Battery circuit breaker 10 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8522 |
| lgpCondId8523BatteryBreaker11OpenFailure Battery circuit breaker 11 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8523 |
| lgpCondId8524BatteryBreaker12OpenFailure Battery circuit breaker 12 failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8524 |
| lgpCondId8537BatteryCabinetHighOverallVoltage The system has detected a high battery cabinet overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8537 |
| lgpCondId8538BatteryCabinetLowOverallVoltage The system has detected a low battery cabinet overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8538 |
| lgpCondId8539BatteryCabinetHighCellVoltage The system has detected a high cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8539 |
| lgpCondId8540BatteryCabinetLowCellVoltage The system has detected a low cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8540 |
| lgpCondId8541BatteryCabinetOverOverallVoltage The system has detected a battery cabinet over overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8541 |
| lgpCondId8542BatteryCabinetUnderOverallVoltage The system has detected a battery cabinet under overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8542 |
| lgpCondId8543BatteryCabinetOverCellVoltage The system has detected a battery cabinet over cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8543 |
| lgpCondId8544BatteryCabinetUnderCellVoltage The system has detected a battery cabinet under cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8544 |
| lgpCondId8545BatteryCabinetChargeOverCurrent Battery Cabinet Charge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8545 |
| lgpCondId8546BatteryCabinetDischargeOverCurrent Battery Cabinet Discharge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8546 |
| lgpCondId8547BatteryCabinetOverTemperature The system has detected a battery cabinet over temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8547 |
| lgpCondId8548BatteryCabinetUnderTemperature The system has detected a battery cabinet under temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8548 |
| lgpCondId8558BatteryStringHighCellVoltage The system has detected a high cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8558 |
| lgpCondId8559BatteryStringLowCellVoltage The system has detected a low cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8559 |
| lgpCondId8560BatteryStringOverOverallVoltage The system has detected a battery string over overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8560 |
| lgpCondId8561BatteryStringUnderOverallVoltage The system has detected a battery string under overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8561 |
| lgpCondId8562BatteryStringOverCellVoltage The system has detected a battery string over cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8562 |
| lgpCondId8563BatteryStringUnderCellVoltage The system has detected a battery string under cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8563 |
| lgpCondId8564BatteryStringChargeOverCurrent Battery string Charge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8564 |
| lgpCondId8565BatteryStringDischargeOverCurrent Battery string Discharge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8565 |
| lgpCondId8566BatteryStringOverTemperature The system has detected a battery string over temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8566 |
| lgpCondId8567BatteryStringUnderTemperature The system has detected a battery string under temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8567 |
| lgpCondId8579BatteryModuleHighOverallVoltage The system has detected a high battery module overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8579 |
| lgpCondId8580BatteryModuleLowOverallVoltage The system has detected a low battery module overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8580 |
| lgpCondId8581BatteryModuleHighCellVoltage The system has detected a high cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8581 |
| lgpCondId8582BatteryModuleLowCellVoltage The system has detected a low cell voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8582 |
| lgpCondId8583BatteryModuleOverOverallVoltage The system has detected a battery module over overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8583 |
| lgpCondId8584BatteryModuleUnderOverallVoltage The system has detected a battery module under overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8584 |
| lgpCondId8585BatteryModuleOverCellVoltage The system has detected a battery module over cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8585 |
| lgpCondId8586BatteryModuleUnderCellVoltage The system has detected a battery module under cell voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8586 |
| lgpCondId8587BatteryModuleDisconnected Battery Module is disconnected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8587 |
| lgpCondId8588BatteryModuleChargeOverCurrent Battery Module Charge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8588 |
| lgpCondId8589BatteryModuleDischargeOverCurrent Battery Module Discharge over current. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8589 |
| lgpCondId8590BatteryModuleOverTemperature The system has detected a battery module over temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8590 |
| lgpCondId8591BatteryModuleUnderTemperature The system has detected a battery module under temperature
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8591 |
| lgpCondId8592BatteryModuleFault Battery module fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8592 |
| lgpCondId8605BatteryStringHighOverallVoltage The system has detected a high battery string overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8605 |
| lgpCondId8606BatteryStringLowOverallVoltage The system has detected a low battery string overall voltage
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8606 |
| lgpCondId8608BypassSCROpen The bypass SCR is in an open circuit condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8608 |
| lgpCondId8609BypassSCRShort The bypass SCR is in short circuit condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8609 |
| lgpCondId8612RectifierOverTemperature Rectifier temperature is too high to keep rectifier running. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8612 |
| lgpCondId8613RectifierCommunicationsFailure Communication between internal monitor and Rectifier has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8613 |
| lgpCondId8615InverterOverTemperature Inverter temperature is too high to keep inverter running. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8615 |
| lgpCondId8616InverterCommunicationsFailure Communication between internal monitor and Inverter has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8616 |
| lgpCondId8617UPSisinServiceMode UPS is in Service Mode. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8617 |
| lgpCondId8619AirEconHighMixedTemp Air Economizer High Mixed Temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8619 |
| lgpCondId8620AirEconLowMixedTemp Air Economizer Low Mixed Temperature. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8620 |
| lgpCondId8621RetDampFdbackFail Return Damper Feedback Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8621 |
| lgpCondId8622OutdoorDmpFdbackFail Outdoor Damper Feedback Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8622 |
| lgpCondId8623ThermalRunaway Thermal Runaway. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8623 |
| lgpCondId8624XDMMixValvePositionError XDM Mix Valve is reporting Out of Position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8624 |
| lgpCondId8625XDMPumpNoFlow XDM Pump Indicates No Flow. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8625 |
| lgpCondId8626XDMPumpPressureSensorFail XDM Pump Pressure Sensor Has Failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8626 |
| lgpCondId8627XDMPumpNotAvail XDM Pump is Not Available. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8627 |
| lgpCondId8628XDMFlowandLoadCycling XDM Flow is Cycling Between Flow and Load. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8628 |
| lgpCondId8629ShuntTripUnavailable Shunt trip power has failed. The voltage is insufficient to shunt
trip the input breaker. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8629 |
| lgpCondId8630PanelboardShuntTripUnavailable Shunt trip power has failed. The voltage is insufficient to shunt
trip the panelboard main breaker. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8630 |
| lgpCondId8718SystemControlCardsMissing System control cards missing. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8718 |
| lgpCondId8719LossofControlRedundancy Loss of control redundancy. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8719 |
| lgpCondId8724BatteryModuleNotReady Battery module is not ready. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8724 |
| lgpCondId8725BatteryModuleBalancingAbnormal Battery module voltage is not balanced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8725 |
| lgpCondId8726MainBatteryCircuitBreakerisOpen Main battery circuit is open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8726 |
| lgpCondId8727MainBatteryBreakerOpenFailure Main battery circuit breaker failed to open. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8727 |
| lgpCondId8734ExhaustDamperFeedbackFail Exhaust Damper Feedback Failure Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8734 |
| lgpCondId8735HighUnitDifferentialPressure High Unit Differential Pressure Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8735 |
| lgpCondId8736InputSurgeProtectionDeviceAlarm Input Surge Protection Device alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8736 |
| lgpCondId8737BypassSurgeProtectionDeviceAlarm Bypass Surge Protection Device alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8737 |
| lgpCondId8738ReturnTHSensorFailure Return Temperature/Humidity Sensor Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8738 |
| lgpCondId8742AggregateRemoteAirTempSensorFail Failure of Aggregated Remote Air Temperature Sensor. This event is
active when all configured Remote Sensor Issue events are active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8742 |
| lgpCondId8743AggregateMixedAirTempSensorFail Failure of Aggregated Mixed Air Temperature Sensor. This event is
active when Remote Sensor Issue and External Air Sensor E Issue
are active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8743 |
| lgpCondId8745FixedCompressorFailure Fixed Compressor Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8745 |
| lgpCondId8746FixedCompressorFailureLock Fixed Compressor Failure Lock. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8746 |
| lgpCondId8748SecondaryPowerSourceSupplyFailure Secondary Power Source Supply Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8748 |
| lgpCondId8751SprayCommunicationFailure Spray Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8751 |
| lgpCondId8752SprayHighPressureFailure Spray High Pressure Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8752 |
| lgpCondId8753SprayHighPressureFailureLock Spray High Pressure Failure Lock. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8753 |
| lgpCondId8754SprayLowPressureFailure Spray Low Pressure Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8754 |
| lgpCondId8755SprayAntifreezeMaintenance Spray Antifreeze Maintenance. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8755 |
| lgpCondId8756PowerMeterCommunicationFailure Power Meter Communication Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8756 |
| lgpCondId8757WetFilmMaintenanceAlarm Wet Film Maintenance Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8757 |
| lgpCondId8758LowRefrigerant Low Refrigerant. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8758 |
| lgpCondId8759RefrigerantLeakDetected Refrigerant Leak Detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8759 |
| lgpCondId8760RefrigerantLeakDetectorCommunicationsFailure Refrigerant Leak Detector Communications Failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8760 |
| lgpCondId8761RefrigerantLeakDetectLock Refrigerant Leak Detect Lock. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8761 |
| lgpCondId8762HighPressureSwitchAlarm High Pressure Switch Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8762 |
| lgpCondId8763HighPressureSwitchAlarmLock High Pressure Switch Alarm Lock. | node | - | .1.3.6.1.4.1.476.1.42.3.2.7.1.8763 |