lgpConditionNoLoadDetectedWarning

LIEBERT-GP-CONDITIONS-MIB · .1.3.6.1.4.1.476.1.42.3.2.1.186

Object

node
There is no load detected on the output.  This can be an indication
that the output is being powered by an external bypass source and has
inadvertently been left on external bypass.  This warning is triggered
after a delay.  The delay is specified by the object
'lgpPwrNoLoadWarningDelay'.  The alarm is triggered when the output
current falls below a certain threshold specified by the object
'lgpPwrNoLoadWarningLimit'