lgpConditionInputCurrentUnbalanced
LIEBERT-GP-CONDITIONS-MIB ·
.1.3.6.1.4.1.476.1.42.3.2.1.91
Object
node
The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
Context
- MIB
- LIEBERT-GP-CONDITIONS-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.2.1.91- Type
- node
- Status
- current
- Parent
- lgpConditionsWellKnown
- Siblings
- 236
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| lgpConditionHighTemperature The temperature has exceeded the high temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.1 |
| lgpConditionCompressorLowSuctionPressure The pressure at a compressor inlet has dropped below the
minimum setting. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.10 |
| lgpConditionPowerModuleFailure The system has detected a power module failure condition in the
system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.100 |
| lgpConditionBatteryModuleFailure The system has detected a battery module failure condition in the
system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.101 |
| lgpConditionOutputToLoadOff The system has detected that there is no power being supplied to the
load. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.102 |
| lgpConditionSystemOff The system is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.103 |
| lgpConditionRectifierStartupFailure The system has detected a rectifier under voltage start-up failure
condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.104 |
| lgpConditionRectifierFault The system has detected a rectifier fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.105 |
| lgpConditionInverterShutdownLowDc The system has shutdown the inverter due to a DC bus under voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.106 |
| lgpConditionInverterFault The system has detected an inverter fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.107 |
| lgpConditionInverterDcOffsetOverrun The system has detected an over run of the inverter DC offset
voltage. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.108 |
| lgpConditionParallelSysLowBatteryWarning The parallel system has detected a low battery warning condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.109 |
| lgpConditionMainFanOverLoad The system has detected a main fan overload condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.11 |
| lgpConditionParallelSysLoadShareFault The parallel system has detected a load share fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.110 |
| lgpConditionBatteryFault The system has detected a battery fault condition. The battery
conductors are either reversed or disconnected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.111 |
| lgpConditionBatteryConverterFailure The system has detected a battery converter failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.112 |
| lgpConditionBatteryBalancerFault The system has detected a battery balancer fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.113 |
| lgpConditionpsUpsOperationFault deprecated The system has detected an operation fault. The UPS attempted to
transfer to maintenance bypass without following the proper sequence. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.114 |
| lgpConditionOutputToLoadOnJointMode The system load is being supported by both the battery and rectifier. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.115 |
| lgpConditionInputNeutralLost The system had detected the main input neutral is disconnected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.116 |
| lgpConditionLowBatteryWarning The battery's remaining charge is less than or equal to the
configured low threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.117 |
| lgpConditionInternalFault The system has detected an internal fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.118 |
| lgpConditionBatteryTestFailed The system has detected a battery self-test failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.119 |
| lgpConditionManualOverride The system has detected a manual override condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.12 |
| lgpConditionPowerModuleWarning The system has detected an alarm condition on one, or more,
power modules. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.120 |
| lgpConditionBatteryModuleWarning The system has detected an alarm condition on one, or more,
battery modules. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.121 |
| lgpConditionControlModuleWarning The system has detected a control module warning. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.122 |
| lgpConditionUpsOperationFault The system has detected an operation fault. The UPS attempted to
transfer to maintenance bypass without following the proper sequence. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.123 |
| lgpConditionActiveAlarm The system has detected an alarm condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.124 |
| lgpConditionRectifierCommunicationFailure The system has detected an internal communication failure
condition with the rectifier. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.125 |
| lgpConditionInverterCommunicationFailure The system has detected an internal communication failure
condition with the inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.126 |
| lgpConditionParallelSysConnectionFault The parallel system has detected a connection fault.
One or more of the devices are not properly connected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.127 |
| lgpConditionParallelSysCommunicationFailure The parallel system has detected a communication failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.128 |
| lgpConditionLostBatteryRedundancy The system has detected the number of redundant battery modules has
fallen below the configured redundant battery module threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.129 |
| lgpConditionStandbyGlycoolPumpOn The standby Glycol or Glycool pump is activated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.13 |
| lgpConditionCompPumpDownFailure The system has detected that a compressor has failed to pump down. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.130 |
| lgpConditionChilledWaterLowWaterFlow The system has detected a chilled water low water flow condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.131 |
| lgpConditionAirFilterClogged deprecated The system has detected a air filter clogged condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.132 |
| lgpConditionHumidifierFailure The system has detected a humidifier failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.133 |
| lgpConditionRunHoursExceeded The system has detected a pre-determined run hours threshold has been
exceeded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.134 |
| lgpConditionCommWarning The system has detected a loss of communications with another
module. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.135 |
| lgpConditionUnitOn The unit is on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.136 |
| lgpConditionUnitOff The unit is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.137 |
| lgpConditionSleepModeOff The system sleep mode operation has been turned off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.138 |
| lgpConditionPowerOn The system power is on. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.139 |
| lgpConditionWaterUnderFloor Moisture has been detected under the floor. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.14 |
| lgpConditionSystemOnStanby The system is on standby. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.140 |
| lgpConditionPowerOff The system power is off. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.141 |
| lgpConditionHighTemperatureGroup The system has detected a high temperature condition. This group
contains various high temperature conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.142 |
| lgpConditionLowTemperatureGroup The system has detected a low temperature condition. This group
contains various low temperature conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.143 |
| lgpConditionHighHumidityGroup The system has detected a high humidity condition. This group
contains various high humidity conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.144 |
| lgpConditionLowHumidityGroup The system has detected a low humidity condition. This group
contains various high humidity conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.145 |
| lgpConditionPeerNetworkNoMaster The system is unable to communicate with the master on the peer to
peer network. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.146 |
| lgpConditionNoOnOffPermissions The system lacks the permissions to execute the on/off operation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.147 |
| lgpConditionPeerNetworkFailure The system has detected a communication failure on the peer to
peer network. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.148 |
| lgpConditionUnitDisabled The unit is disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.149 |
| lgpConditionHumidifierProblem The system has detected a humidifier problem. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.15 |
| lgpConditionUnitShutdown The system has shutdown. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.150 |
| lgpConditionPeerNetworkDiscovered The system has established communications on the peer to peer
network. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.151 |
| lgpConditionLossOfWaterFlow The system has detected a loss of water flow condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.152 |
| lgpConditionCondensatePumpHighWater The system has detected high water in the condensate pump. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.153 |
| lgpConditionGeneralAlarm The system has detected a general alarm condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.154 |
| lgpConditionProductSpecific The system has detected a product specific condition. This condition
is not currently available via the agent card. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.155 |
| lgpConditionReheatLockout The system has locked out the electrical reheat operation for a
specified amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.156 |
| lgpConditionHumidifierLockout The system has locked out the humidifier operation for a
specified amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.157 |
| lgpConditionCompressorsLockout The system has locked out compressor operation for a specified amount
of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.158 |
| lgpConditionCallService The system has detected a condition that requires a service
representative be contacted. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.159 |
| lgpConditionLowWaterInHumidifier The system has detected a low water condition in the humidifier
reservoir. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.16 |
| lgpConditionLowMemoryGroup This group contains various low memory conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.160 |
| lgpConditionMemoryFailureGroup This group contains various memory device failure conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.161 |
| lgpConditionUnitCodeErrorGroup This group contains various memory device failure conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.162 |
| lgpConditionHighExternalDewPoint The system has detected a high external dew point condition.
The room dew point has exceeded the specified threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.163 |
| lgpConditionHcbDisconnected The system has detected the humidifier control board is disconnected
or not installed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.164 |
| lgpConditionBmsResetTimerExpired The BMS fan speed control reset counter has timed out. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.165 |
| lgpConditionAgentFirmwareCorrupt The firmware update to the agent card has failed and the firmware is now
corrupt. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.166 |
| lgpConditionSmokeDetected The system has detected smoke. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.17 |
| lgpConditionSystemAccessGroup This group contains various system access conditions. An examples is
an open access panel. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.175 |
| lgpConditionsDamperFailure This group contains various damper failure conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.176 |
| lgpConditionRemoteShutdown A remote shutdown occurred. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.177 |
| lgpConditionFireAlarm Fire Alarm. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.178 |
| lgpConditionHeatersOverheated Heaters Overheated. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.179 |
| lgpConditionLowWaterFlow The system has detected a low water flow rate condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.18 |
| lgpConditionCondenserFailureGroup This group contains condenser failure conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.180 |
| lgpConditionHumidifierCyclinderWorn The system has detected the humidifier cylinder is worn. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.181 |
| lgpConditionUnderCurrent The system has detected a low current condition. The current of
one or more sources in the system has fallen below a threshold for
a specified amount of time. The threshold and … | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.182 |
| lgpConditionHeatRejectorGroup This group contains failure conditions for the heat rejection unit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.183 |
| lgpConditionFreeCoolLockout The free cooling capability has been disabled. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.184 |
| lgpConditionWaterLeakSensorFailure The sensor used to detect water leaks is not connected or has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.185 |
| lgpConditionNoLoadDetectedWarning There is no load detected on the output. This can be an indication
that the output is being powered by an external bypass source and has
inadvertently been left on external bypas… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.186 |
| lgpConditionFirmwareGroup Grouping level for firmware related conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.187 |
| lgpConditionTestGroup Objects in this group of conditions are related to testing or test
events. This object is never active. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.188 |
| lgpConditionLostPower The system has lost power before being switched off using the
controls. This condition is activated when power is restored. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.19 |
| lgpConditionReceptacleBranchGroup Grouping level for receptacle branch conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.190 |
| lgpConditionInputUnqualified The input is not qualified to provide power to the system. This may
be due to system input over-voltage, system input under-voltage,
system input frequency out of range, or other… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.192 |
| lgpConditionBypassUnavailable This summary event is asserted when the bypass is not available.
Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass
Overvoltage, Bypass Undervoltage, Bypass Phas… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.193 |
| lgpConditionAutoTransferFailed The system is failing to automatically transfer the load to the
alternate source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.194 |
| lgpConditionSBSUnavailable A Static Bypass Switch (SBS) Failure has been detected. Possible
causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier)
Shorted, SBS Overload Exceeded, Bypass Powe… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.195 |
| lgpConditionSBSOverload On at least one phase of the static bypass switch (SBS), the power
dissipation limit has been exceeded. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.196 |
| lgpConditionExcessPulseParallel The system has performed too many pulse parallel operations within
the specified time interval. A pulse parallel operation is a
momentary operation of the static bypass switch (S… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.197 |
| lgpConditionRemoteBypassSwitchOffExt The static bypass switch is off due to the state of an external
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.198 |
| lgpConditionManTransferInhibited Manual transfer from inverter to bypass is inhibited. Bypass is not
qualified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.199 |
| lgpConditionLowTemperature The temperature is below the low temperature threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.2 |
| lgpGeneralFault A fault condition has been detected that is not identified
in the well known list. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.20 |
| lgpConditionManReTransferInhibited Manual retransfer from bypass to inverter is inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.200 |
| lgpConditionBatteryChargeError The battery is not charging properly. Some reasons for this condition
include, but are not limited to: battery charger failure,
battery failure, etc. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.201 |
| lgpConditionBatteryAutoTestInhibited Automatic (scheduled) battery tests are inhibited. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.202 |
| lgpConditionBatteryChargeReducedExt A reduced battery charging algorithm is being used due to an external
signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.203 |
| lgpConditionBatteryCapacityLow The battery capacity is low. Some reasons for this condition include,
but are not limited to: a battery is offline, the battery age has
reduced its capabilities, etc. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.204 |
| lgpConditionBatteryTempImbalance The temperature difference between two batteries in the system
exceeds the predefined threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.205 |
| lgpConditionBatteryEqualize The rectifier output voltage has been increased to equalize the battery
voltage level. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.206 |
| lgpConditionBatteryChargeInhibitedExt Battery charging is inhibited due to an external inhibit signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.207 |
| lgpConditionServiceExtBatteryMonitorGroup This group contains battery monitor service conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.208 |
| lgpConditionBatteryGroundFault Battery system ground fault amperage exceeds the threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.209 |
| lgpConditionLocalAlarm This system has detected a local, or customer, alarm condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.21 |
| lgpConditionBatteryLowShutdown With the battery breaker closed, the battery voltage has dropped
below the calculated End-Of-Discharge (EOD) limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.210 |
| lgpConditionEmergencyPowerOffLocal The system has detected an Emergency Power Off (EPO) condition.
The local EPO switch has cut off the power source to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.211 |
| lgpConditionOutputLowPFLagging The system has detected a lagging output power factor below the
threshold, resulting in reduced load capacity. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.212 |
| lgpConditionOutputLowPFLeading The system has detected a leading output power factor below the
threshold, resulting in reduced load capacity. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.213 |
| lgpConditionOutputToLoadFault The system has detected an output to load fault. This could be
caused by over or under voltage, or by over or under frequency. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.214 |
| lgpConditionInvRestartInhibitedExt Restart of the inverter is inhibited by an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.215 |
| lgpConditionInverterShutdownOverload The system has shutdown the inverter due to a sustained overload.
This event does not indicate if the load has been dropped or
transferred to bypass. At least one phase of the in… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.216 |
| lgpConditionInverterOffExt The inverter is off due to the state of an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.217 |
| lgpConditionInputContactGroup The system has detected an active input contact. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.218 |
| lgpConditionRectifierOperInhibited The operation of the rectifier is inhibited by an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.219 |
| lgpConditionStandbyUnitOn The system has detected the standby unit is operating. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.22 |
| lgpConditionBypassBackFeedBrkrOpen The bypass backfeed breaker is in the open position. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.220 |
| lgpConditionAutoRestartInProgress Auto restart is in progress. Becomes inactive when auto restart
completes or fails. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.221 |
| lgpConditionAutoRestartInhibitedExt Auto restart is inhibited due to an external signal. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.222 |
| lgpConditionAutoRestartFailed Auto restart has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.223 |
| lgpConditionInputOnGenerator A generator is supplying the power to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.224 |
| lgpConditionInputFilterCycleLock The input filter disconnect has opened too many times within a given
period of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.225 |
| lgpConditionServiceCodeActive The system is in an operational mode intended for testing. In normal
operating conditions, the system should not be in this state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.226 |
| lgpConditionLoadBusSyncActive Load Bus Sync Operation is active. This synchronizes the UPS output
with the output of another UPS. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.227 |
| lgpConditionLoadBusSyncInhibited The system has detected that conditions to perform Load Bus Sync
Operation are not satisfied. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.228 |
| lgpConditionControlsResetRequired A controls reset is required because one or more critical settings
have changed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.229 |
| lgpConditionCompressorLowPressure This system has detected a low head compressor condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.23 |
| lgpConditionEquipTempSensorFailed A temperature sensor is reporting a value outside the bounds of a
properly operating sensor. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.230 |
| lgpConditionInputCurrentImbalance The current on one input phase is much greater or lower than the
average current of all the phases. This may indicate improper operation
of the rectifier or input filter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.231 |
| lgpConditionPumpGroup The system has detected an alarm with one of the pumps. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.232 |
| lgpConditionValveGroup The system has detected an alarm with one of the valves. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.233 |
| lgpConditionCondensationDetected The system has detected condensation. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.234 |
| lgpConditionMaintenanceGroup The system has detected a maintenance condition. This group
contains various maintenance conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.235 |
| lgpConditionExternalEventSignalGroup This group contains various conditions signalled by external inputs.
Each event is deactivated when the signal is inactive. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.236 |
| lgpConditionComponentShutdownGroup This group contains conditions signaling shutdown of various system
components. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.237 |
| lgpConditionCondenserProblemGroup This group contains condenser conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.238 |
| lgpConditionHumidityOutOfPropBand The system has detected a humidity reading that remained outside of
the proportional control band for an extended period of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.239 |
| lgpConditionHighWaterInPan The system has detected a high water condition in the condenser pan. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.24 |
| lgpConditionEnvRemoteSensorGroup This group contains remote sensors. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.240 |
| lgpConditionNeutralSnubberBoardCommFailure The Neutral Snubber board has stopped communicating. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.241 |
| lgpConditionRedundantChargerFailure The redundant charger has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.242 |
| lgpConditionBoardInputContactorPowerFailure Board input contactor power failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.243 |
| lgpConditionFaultySensor The system has detected a faulty temperature/humidity sensor. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.25 |
| lgpConditionServiceCooling The Cooling system requires scheduled maintenance. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.26 |
| lgpConditionServiceHumidifier The Humidifier requires scheduled maintenance. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.27 |
| lgpConditionSystemControlBatteryLow Charge level of the system control's battery is below the
alarm set point. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.28 |
| lgpConditionGroundSystemFault The system has detected a ground system fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.29 |
| lgpConditionHighHumidity The humidity has exceeded the high humidity threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.3 |
| lgpConditionGroundFailure The system has detected a ground failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.30 |
| lgpConditionSecurityBreach The system has detected a security breach. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.31 |
| lgpConditionEmergencyShutdown The system has detected an emergency shutdown condition. The System
is shutting down as a result of this emergency. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.32 |
| lgpConditionOnBypass This system has detected the load is being powered by a bypass
source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.33 |
| lgpConditionOutputToLoadVoltTHD The total harmonic distortion (THD) of the output voltage has exceeded a
pre-determined threshold for a device, or system, defined amount of
time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.34 |
| lgpConditionLogicFailure The system has detected a control logic failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.35 |
| lgpConditionPowerSupplyFault This system had detected a power supply fault condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.36 |
| lgpConditionPowerSupplyFailure This system has detected a power supply failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.37 |
| lgpConditionOverVoltage This system has detected an over voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.38 |
| lgpConditionUnderVoltage This system has detected an under voltage condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.39 |
| lgpConditionLowHumidity The humidity is below the low humidity threshold. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.4 |
| lgpConditionOverload This system has detected an overload condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.40 |
| lgpConditionScrShort This system has detected a Silicon Controlled Rectifier (SCR)
short condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.41 |
| lgpConditionScrOpen This system has detected a Silicon Controlled Rectifier (SCR)
open condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.42 |
| lgpConditionFanFailure This system has detected a fan failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.43 |
| lgpConditionTransferInhibited The system is preventing a transfer of the load to the alternate
source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.44 |
| lgpConditionAutoReTransferPrimed The system is capable to retransfer to the preferred source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.45 |
| lgpConditionSourcesOutOfSync The system has detected that the input sources are not within the
specified phase difference (synchronization window). | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.46 |
| lgpConditionSourceFailure This system has detected an input source failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.47 |
| lgpConditionAutoReTransferInhibited The system is preventing a retransfer of the load back to the
preferred source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.48 |
| lgpConditionAutoReTransferFailed The system is failing to automatically retransfer the load back to the
preferred source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.49 |
| lgpConditionLossOfAirflow The system has detected a loss of air flow. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.5 |
| lgpConditionFuseOpen This system has detected an open fuse condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.50 |
| lgpConditionDisconnect The system has detected a disconnect condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.51 |
| lgpConditionFrequencyDeviation This system has detected a frequency deviation condition.
The frequency of a source is outside of the pre-determined thresholds
for a specified amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.52 |
| lgpConditionOverCurrent This system has detected an over-current condition. The current of a
source has risen above a pre-determined threshold for a device,
or system, defined amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.53 |
| lgpConditionSensorFailure This system has detected a sensor failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.54 |
| lgpConditionTooManySensors The number of sensors installed on the device has exceeded the
pre-determined limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.5423 |
| lgpConditionDoorSwitchOpen An open door has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.5471 |
| lgpConditionContactClosureOpen An open circuit has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.5479 |
| lgpConditionContactClosureClosed A closed circuit has been detected. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.5480 |
| lgpConditionInternalCommunicationFailure This system has detected an internal communication failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.55 |
| lgpConditionExternalCommunicationFailure This system has detected an external communication failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.56 |
| lgpConditionSourceGateDriveFailure This system has detected a source gate drive failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.57 |
| lgpConditionDisconnectFailure This system has detected a disconnect failure condition.
A disconnect is a device which disconnects a conductor of a circuit
from its supply (ex. circuit breaker, contactor, isola… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.58 |
| lgpConditionOverTemperature This system has detected an over temperature condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.59 |
| lgpConditionChangeFilter The system has detected a condition indicating the air filter
should be changed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.6 |
| lgpConditionLoadOnAlternateSource The system has detected that the load is being supplied by the
alternate source. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.60 |
| lgpConditionPhaseRotationError This system has detected a phase rotation error condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.61 |
| lgpConditionSensorsNotDisplayed The number of sensors that can be displayed (monitored) on the
device has exceeded the pre-determined limit. Note this condition
differs from the lgpConditionTooManySensors in th… | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.6119 |
| lgpConditionControlModuleFailure This system has detected a control module failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.62 |
| lgpConditionHistoryLogFull The system has detected the history log is full. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.63 |
| lgpConditionConfigurationModified The system has detected the configuration has been modified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.64 |
| lgpConditionPasswordModified The system has detected the password has been modified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.65 |
| lgpConditionTimeModified The system has detected the time has been modified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.66 |
| lgpConditionDateModified The system has detected the date has been modified. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.67 |
| lgpConditionEventLogCleared The system has detected the event log has been cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.68 |
| lgpConditionHistoryLogCleared The system has detected the history log has been cleared. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.69 |
| lgpConditionCompressorHighHeadPressure This system has detected an excessive head pressure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.7 |
| lgpConditionUtilityFailure The system has detected a utility failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.70 |
| lgpConditionBatteryTestInProgress The system is performing a battery test at this time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.71 |
| lgpConditionLoadOnBattery The system load is being supported by the battery. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.72 |
| lgpConditionReplaceBattery The system has detected the batteries are due to be replaced. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.74 |
| lgpConditionUpsShutdownPending The system is in a shutdown pending condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.75 |
| lgpConditionBatteryChargerFailed The system has detected the battery charger has failed. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.76 |
| lgpConditionBypassVoltageUnqualified The system has detected the bypass voltage is unqualified.
The voltage measurement is outside a pre-determined threshold range for
a specified amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.77 |
| lgpConditionCheckAirFilter The system has detected it is time to check the air filter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.78 |
| lgpConditionBrownOut The system has detected a brown out condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.79 |
| lgpConditionCompressorOverload This system has detected a compressor overload condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.8 |
| lgpConditionMultipleTransferLockout The system has locked out transfers to bypass. Too many transfers
have occurred over a specified amount of time. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.80 |
| lgpConditionBypassPhaseLost The system has detected one or more bypass phases are missing. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.81 |
| lgpConditionMaintenceBypassInhibited The system is preventing a transfer of the load to maintenance bypass. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.82 |
| lgpConditionLoadLockedOnBypass An error has been detected requiring the system to be put into a
'locked on bypass' state. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.83 |
| lgpConditionOutputToLoadShort The system has detected an output to load short circuit condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.84 |
| lgpConditionEmergencyTransferToInverter The system has detected an emergency transfer of the load to
inverter. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.85 |
| lgpConditonEmergencyPowerOff The system has detected an Emergency Power Off (EPO) condition.
An external EPO switch has cut off the power source to the system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.86 |
| lgpConditionInverterBackFeed The system has detected an inverter back-feed condition. The inverter
is feeding power through the bypass back to the input. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.87 |
| lgpConditionDcGroundFault The system has detected a DC ground fault. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.88 |
| lgpConditionStaticTransferSwitchInhibited The system is preventing the use of the static transfer switch. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.89 |
| lgpConditionCompressorShortCycle A compressor has exceeded the maximum number of starts in a
minimum time period. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.9 |
| lgpConditionBatteryLogFullWarning The system has detected the battery log is approaching the maximum
record limit. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.90 |
| lgpConditionSelfTestFailed The system has detected a self-test failure. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.92 |
| lgpConditionInverterOutOfSynchronization The system has detected an Inverter out of sync condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.93 |
| lgpConditionModuleAlarm This system has detected an alarm within the multi-module system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.94 |
| lgpConditionActiveModuleAlarm The system has detected an active alarm in one, or more, of the
sub-modules of the multi-module system. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.95 |
| lgpConditionControlFailure This system has detected a control failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.96 |
| lgpConditionControlWarning This system has detected a control warning conditions. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.97 |
| lgpConditionUserInterfaceFailure The system has detected a user interface control failure condition. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.98 |
| lgpConditionLostPowerRedundancy The system has detected the number of redundant power modules has
fallen below the minimum redundant power module setting. | node | - | .1.3.6.1.4.1.476.1.42.3.2.1.99 |