Operational state of the ring coupling configuration.
              
slaveCouplingLinkError(2) indicates that the coupling link
is not connected with the coupling port of the slave but with
another port of the slave.
              
In case of outband control additional failures can be
detected:
slaveControlLinkError(3) indicates that the control
port of the slave has either no link or the link
fails.
masterControlLinkError(4) indicates that the control
link is not connected with the control port of the
master but with another port of the master.
twoSlaves(5) is returned when two slaves are connected
by the control line.
              
localPartnerLinkError(6) indicates that the partner coupling link
is not connected with the partner port of the slave but with
another port of the slave in local control mode.
localInvalidCouplingPort(7) indicates that in local mode the coupling
line is connected to another switch and not on the same switch like
the partner line.
              
couplingPortNotAvailable(8), controlPortNotAvailable(9) and
partnerPortNotAvailable(10) indicate that this port is not available
because the module related to this port is not available or the port
does not exist on this module.

Context

MIB
HM2-L2REDUNDANCY-MIB
OID
.1.3.6.1.4.1.248.11.40.1.8.1.1.13
Type
column
Access
readonly
Status
current
Parent
hm2RingCouplingEntry
Table
hm2RingCouplingTable
Siblings
17

Syntax

Enumeration

Values & Constraints

Enumerated Values
1noError
2slaveCouplingLinkError
3slaveControlLinkError
4masterControlLinkError
5twoSlaves
6localPartnerLinkError
7localInvalidCouplingPort
8couplingPortNotAvailable
9controlPortNotAvailable
10partnerPortNotAvailable