hm2DPIProfileDnp3FunctionCodeList
HM2-FW-MIB ·
.1.3.6.1.4.1.248.11.79.1.3.21.6.1.3
Object
column
r/w
OctetString
The function codes for this enforcer as string.
A function code has the syntax:
<val>
If more than one value is given for a function code, values are
separated by a , sign (comma).
Note: The user can define any number between 0-255. The code must be a number (in decimal format).
Following function codes are defined by the DNP3 standard IEEE 1815-2012:
0 confirm
1 read
2 write
3 select
4 operate
5 direct_operate
6 direct_operate_nr
7 immed_freeze
8 immed_freeze_nr
9 freeze_clear
10 freeze_clear_nr
11 freeze_at_time
12 freeze_at_time_nr
13 cold_restart
14 warm_restart
15 initialize_data
16 initialize_appl
17 start_appl
18 stop_appl
19 save_config
20 enable_unsolicited
21 disable_unsolicited
22 assign_class
23 delay_measure
24 record_current_time
25 open_file
26 close_file
27 delete_file
28 get_file_info
29 authenticate_file
30 abort_file
31 activate_config
32 authenticate_req
33 authenticate_err
129 response
130 unsolicited_response
131 authenticate_resp
Context
- MIB
- HM2-FW-MIB
- OID
.1.3.6.1.4.1.248.11.79.1.3.21.6.1.3- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- hm2DPIProfileDnp3Entry
Syntax
OctetString
Values & Constraints
Object Constraints
range: 1-1400