podCircuitBreakerConfigOverloadRestriction
ENLOGIC-PDU2-MIB ·
.1.3.6.1.4.1.38446.3.4.2.1.4
Object
column
r/w
Enumeration
This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the podCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the podCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Context
- MIB
- ENLOGIC-PDU2-MIB
- OID
.1.3.6.1.4.1.38446.3.4.2.1.4- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- podCircuitBreakerConfigEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnOn |
2 | restrictOnUpperWarning |
3 | restrictOnUpperCritical |
4 | notSupported |