cfgPsInvTestAutoStopTimer
ELECTROLINE-DHT-CONFIG-MIB ·
.1.3.6.1.4.1.5802.1.3.1.2.2.2.2.1
Object
scalar r/w
Integer32
This MIB defines the maximum duration of a remote inverter test, in minutes.
The transponder uses a default 15-minute period.
When the timer reaches the end of the set period, the test stops automatically.
Note that the internal Power Supply settings may stop the inverter test
before this timer has expired.
The DHT will also stop the Inverter test if the voltage of any battery drops below
10.875V.
The value of this MIB is stored in non-volatile memory.